Partner NameBuilt Electrical Australia
StateVIC
Date of Visit06/11/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51756
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmaribyrnong_warehouse

Location NameMARIBYRNONG WAREHOUSE
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
SB UNIT 3 7 Y 9 18 P
SB UNIT 3 11 Y 8 18 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-4 5 S Y N Y F FAILED BATTERY TEST Y N
DB-4 6 S Y N Y F FAILED BATTERY TEST Y N
DB-4 7 S Y Y Y P
DB-4 8 R Y Y Y P
DB-4 9 R Y Y Y P
DB-4 10 R Y N Y F FAILED BATTERY TEST Y N
DB-3 11 S Y Y Y P
DB-3 12 S Y Y Y P
DB-3 13 S Y Y Y P
DB-3 14 S Y Y Y P
DB-4 15 R Y Y Y P
DB-4 16 R Y Y Y P
DB-4 19 S Y N Y F FAILED BATTERY TEST Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-4 1 Y Y Y P
DB-4 2 Y Y Y P
DB-4 3 Y Y Y P
DB-4 4 Y Y Y P
DB-4 17 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED HIGHBAY LIGHTS Y
36W DIFFUSED LIGHTS Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
SWITCHBOARD LEGEND UNIT 4 UPSTAIRS STORAGE 1 MISSING N N N REPLACE NEXT AUDIT
SWITCHBOARD LEGEND UNIT 3 DB UNNIT 3 1 MISSING N N N REPLACE NEXT AUDIT
FLUORESCENT LIGHT DISABLED TOILET 1 FAULTY FITTING Y N N REPLACED WITH 35W FITTING
LIGHT FITTING SHOWER ROOM 2 FAILED TO ILLUMINATE Y N N REPLACE WITH 12W FITTING
FLUORESCENT LIGHT MALE TOILET 3 FAILED TO ILLUMINATE Y N N REPLACED WITH 35W FITTING
LED HIGHBAY WAREHOUSE AISLE 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW - SCISSOR REQUIRED
EM05 WAREHOUSE AISLE 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR REQUIRED
EM06 WAREHOUSE AISLE 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR REQUIRED
EM10 DISABLED TOILET 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
EM19 WAREHOUSE AISLE 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR REQUIRED
Site Status SelectorStore now fully compliant
Next Test Due in 6 months05/05/2021