State | VIC |
---|
Date of Visit | 09/11/2020 |
---|
Technician's Name | Nathan McBain |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51758 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | frankston |
---|
|
|
---|
Location Name | Frankston |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DSB M5 SECA |
01 |
Y |
21 |
11 |
P |
|
|
DSB M5 SECA |
03 |
Y |
19 |
9 |
P |
|
|
DSB M5 SECA |
05 |
Y |
18 |
8 |
P |
|
|
DSB M5 SECA |
06 |
Y |
19 |
8 |
P |
|
|
DSB M5 SECA |
08 |
Y |
20 |
10 |
P |
|
|
DSB M5 SECA |
10 |
Y |
21 |
12 |
P |
|
|
DSB M5 SECA |
17 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
19 |
Y |
25 |
35 |
P |
|
|
DSB M5 SECA |
20 |
Y |
18 |
8 |
P |
|
|
DSB M5 SECA |
21 |
Y |
101 |
41 |
P |
|
|
DSB M5 SECA |
22 |
Y |
19 |
9 |
P |
|
|
DSB M5 SECA |
23 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
24 |
Y |
21 |
11 |
P |
|
|
DSB M5 SECA |
25 |
Y |
31 |
23 |
P |
|
|
DSB M5 SECA |
26 |
Y |
24 |
34 |
P |
|
|
DSB M5 SECA |
27 |
Y |
23 |
37 |
P |
|
|
DSB M5 SECA |
28 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
29 |
Y |
32 |
41 |
P |
|
|
DSB M5 SECA |
30 |
Y |
24 |
34 |
P |
|
|
DSB M5 SECA |
31 |
Y |
27 |
33 |
P |
|
|
DSB M5 SECA |
32 |
Y |
43 |
33 |
P |
|
|
DSB M5 SECA |
33 |
Y |
52 |
91 |
P |
|
|
DSB M5 SECA |
34 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
35 |
Y |
27 |
37 |
P |
|
|
DSB M5 SECA |
36 |
Y |
27 |
36 |
P |
|
|
DSB M5 SECA |
37 |
Y |
27 |
39 |
P |
|
|
DSB M5 SECA |
38 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECA |
39 |
Y |
43 |
33 |
P |
|
|
DSB M5 SECA |
40 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECA |
41 |
Y |
24 |
34 |
P |
|
|
DSB M5 SECA |
42 |
Y |
27 |
37 |
P |
|
|
DSB M5 SECA |
43 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
44 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
45 |
Y |
24 |
34 |
P |
|
|
DSB M5 SECA |
46 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECA |
47 |
Y |
25 |
35 |
P |
|
|
DSB M5 SECA |
48 |
Y |
24 |
16 |
P |
|
|
DSB M5 SECA |
49 |
Y |
25 |
35 |
P |
|
|
DSB M5 SECA |
50 |
Y |
26 |
17 |
P |
|
|
DSB M5 SECA |
51 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
52 |
Y |
29 |
19 |
P |
|
|
DSB M5 SECA |
53 |
Y |
26 |
36 |
P |
|
|
DSB M5 SECA |
54 |
Y |
24 |
15 |
P |
|
|
DSB M5 SECA |
55 |
Y |
25 |
18 |
P |
|
|
DSB M5 SECA |
56 |
Y |
25 |
35 |
P |
|
|
DSB M5 SECA |
57 |
Y |
28 |
19 |
P |
|
|
DSB M5 SECA |
58 |
Y |
23 |
33 |
p |
|
|
DSB M5 SECA |
59 |
Y |
27 |
33 |
P |
|
|
DSB M5 SECA |
60 |
Y |
23 |
33 |
p |
|
|
DSB M5 SECA |
61 |
Y |
24 |
35 |
P |
|
|
DSB M5 SECA |
62 |
Y |
24 |
33 |
P |
|
|
DSB M5 SECA |
63 |
Y |
44 |
54 |
P |
|
|
DSB M5 SECA |
64 |
Y |
25 |
17 |
P |
|
|
DSB M5 SECA |
65 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
66 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECA |
67 |
Y |
27 |
37 |
P |
|
|
DSB M5 SECA |
68 |
Y |
24 |
16 |
P |
|
|
DSB M5 SECA |
69 |
Y |
23 |
33 |
P |
|
|
DSB M5 SECA |
70 |
Y |
25 |
35 |
P |
|
|
DSB M5 SECA |
71 |
Y |
24 |
35 |
P |
|
|
DSB M5 SECA |
72 |
Y |
24 |
17 |
P |
|
|
DSB M5 SECB |
01 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
02 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
03 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
04 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
05 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
06 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
07 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
08 |
Y |
24 |
16 |
P |
|
|
DSB M5 SECB |
09 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
10 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
11 |
Y |
28 |
18 |
p |
|
|
DSB M5 SECB |
12 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
13 |
Y |
29 |
19 |
P |
|
|
DSB M5 SECB |
14 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
15 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
16 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
17 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
18 |
Y |
28 |
18 |
P |
|
|
DSB M5DSB M5 SECB SECB |
19 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
20 |
Y |
19 |
18 |
P |
|
|
DSB M5 SECB |
21 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
22 |
Y |
25 |
20 |
P |
|
|
DSB M5 SECB |
23 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
24 |
Y |
27 |
37 |
P |
|
|
DSB M5 SECB |
25 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
26 |
Y |
28 |
35 |
P |
|
|
DSB M5 SECB |
27 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
28 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
29 |
Y |
41 |
38 |
P |
|
|
DSB M5 SECB |
30 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
31 |
Y |
30 |
32 |
P |
|
|
DSB M5 SECB |
32 |
Y |
24 |
15 |
P |
|
|
DSB M5 SECB |
33 |
Y |
34 |
36 |
P |
|
|
DSB M5 SECB |
34 |
Y |
28 |
21 |
P |
|
|
DSB M5 SECB |
35 |
Y |
29 |
102 |
P |
|
|
DSB M5 SECB |
36 |
Y |
29 |
17 |
P |
|
|
DSB M5 SECB |
37 |
Y |
68 |
58 |
P |
|
|
DSB M5 SECB |
38 |
Y |
25 |
17 |
P |
|
|
DSB M5 SECB |
39 |
Y |
29 |
36 |
P |
|
|
DSB M5 SECB |
40 |
Y |
25 |
17 |
P |
|
|
DSB M5 SECB |
41 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
42 |
Y |
28 |
18 |
P |
|
|
DSB M5 SECB |
44 |
Y |
25 |
17 |
P |
|
|
DSB M5 SECB |
46 |
Y |
24 |
17 |
P |
|
|
DSB M5 SECB |
48 |
Y |
26 |
18 |
P |
|
|
DSB M5 SECB |
50 |
Y |
26 |
18 |
P |
|
|
DB M5 1 |
07 |
Y |
27 |
37 |
P |
|
|
DB M5 1 |
09 |
Y |
23 |
33 |
P |
|
|
DB M5 1 |
10 |
Y |
31 |
40 |
p |
|
|
DB M5 1 |
11 |
Y |
108 |
33 |
p |
|
|
DB M5 1 |
12 |
Y |
45 |
36 |
P |
|
|
DB M5 1 |
13 |
y |
27 |
37 |
P |
|
|
DB M5 1 |
14 |
y |
25 |
35 |
p |
|
|
DB M5 1 |
15 |
Y |
27 |
37 |
P |
|
|
DB M5 1 |
16 |
Y |
25 |
35 |
P |
|
|
DB M5 1 |
17 |
Y |
27 |
37 |
P |
|
|
DB M5 1 |
18 |
Y |
24 |
34 |
P |
|
|
DB M5 1 |
19 |
Y |
23 |
33 |
P |
|
|
DB M5 1 |
21 |
Y |
27 |
37 |
P |
|
|
DB M5 1 |
22 |
Y |
27 |
37 |
P |
|
|
DB M5 1 |
23 |
Y |
24 |
15 |
P |
|
|
DB M5 1 |
24 |
Y |
24 |
20 |
P |
|
|
DB M5 1 |
25 |
Y |
31 |
21 |
P |
|
|
DB M5 1 |
26 |
Y |
25 |
15 |
P |
|
|
DB M5 1 |
27 |
Y |
29 |
16 |
P |
|
|
DB M5 1 |
28 |
Y |
24 |
18 |
P |
|
|
DB M5 1 |
29 |
Y |
27 |
19 |
P |
|
|
DB M5 1 |
30 |
Y |
24 |
18 |
P |
|
|
DB M5 1 |
31 |
Y |
28 |
18 |
P |
|
|
DB M5 1 |
32 |
Y |
28 |
16 |
P |
|
|
DB M5 1 |
33 |
Y |
29 |
30 |
P |
|
|
DB M5 1 |
34 |
Y |
29 |
18 |
P |
|
|
DB M5 1 |
36 |
Y |
28 |
17 |
P |
|
|
DB M5 1 |
37 |
Y |
22 |
26 |
P |
|
|
DB M5 1 |
38 |
Y |
26 |
18 |
P |
|
|
DB M5 1 |
39 |
y |
17 |
25 |
P |
|
|
DB M5 1 |
40 |
Y |
28 |
18 |
P |
|
|
DB M5 1 |
41 |
Y |
16 |
24 |
P |
|
|
DB M5 1 |
42 |
Y |
25 |
17 |
P |
|
|
DB M5 1 |
44 |
Y |
26 |
18 |
P |
|
|
DB M5 1 |
46 |
Y |
24 |
18 |
P |
|
|
DB M5 1 |
61 |
Y |
12 |
22 |
P |
|
|
DB M5 1 |
63 |
Y |
10 |
20 |
P |
|
|
DB M5 1 |
65 |
Y |
9 |
19 |
P |
|
|
DB M5 1 |
68 |
Y |
10 |
19 |
P |
|
|
DB M5 1 |
70 |
Y |
10 |
20 |
P |
|
|
DB M5 1 |
72 |
Y |
12 |
22 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DSB M5 |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
14 |
R |
Y |
N |
Y |
F |
FAILED TEST |
Y |
N |
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
R |
Y |
Y |
Y |
P |
|
|
|
|
18 |
R |
Y |
Y |
Y |
P |
|
|
|
|
19 |
R |
Y |
Y |
Y |
P |
|
|
|
|
20 |
R |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
N |
Y |
F |
FAILED TEST |
Y |
N |
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
27 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DSB M5 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
90mm LED Downlights |
Y |
70mm LED Downlights |
Y |
300W Mercury Hi-Bay Lights |
Y |
250W Metal Halide Hi-Bay Lights |
Y |
36W Single Fluorescent Batten Lights |
Y |
36W Double Diffused Fluorescent Batten Lights |
Y |
36W Single Diffused Fluorescent Batten Lights |
Y |
Recessed Emergency Lights |
Y |
Clevertronics Ceiling Mount Exit Lights |
Y |
Clevertronics Wall Mount Exit Lights |
Y |
LED Hi-Bay Light Fitting (Store Room) |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
DAVIS LED HIGHBAY |
BOH |
2 |
FAILED TO ILLUMINATE |
DAVIS |
N/A |
N |
SCISSOR REQUIRED 8.0M TO FITTING/CEILING |
DAVIS LED HIGHBAY |
FRIDGES |
1 |
FAILED TO ILLUMINATE |
DAVIS |
N/A |
N |
SCISSOR REQUIRED 8.0M TO FITTING/CEILING |
DAVIS LED HIGHBAY |
KITCHENS F AND P |
1 |
FAILED TO ILLUMINATE |
DAVIS |
N/A |
N |
SCISSOR REQUIRED 7.0M TO CEILING |
DAVIS LED HIGHBAY |
MICROSOFT SURFACE |
1 |
FAILED TO ILLUMINATE |
DAVIS |
N/A |
N |
SCISSOR REQUIRED 6.0M TO FITTING/CEILING |
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
TEST AND TAG |
SAT CO7NTERS/COUNTER/STAFF AREAS/BOH |
50+ |
TEST AND TAG OUT OF DATE 05/APRIL/2020 |
N |
TBA |
TBA |
FYI |
RACK SIGN LIGHT BOX |
FRIDGES(3)/TELEVISIONS/MOBILE PLANS/GAMING/HEADPHONES/SOUNDBARS |
8 |
FAILED TO ILLUMINATE |
N |
TBA |
TBA |
QUOTE 2635 SUBMITTED FOR APPROVAL |
RACK SIGN LIGHT BOX |
FRIDGES |
1 |
FAILED TO ILLUMINATE |
N |
TBA |
TBA |
QUOTE 2635 SUBMITTED FOR APPROVAL |
TV BLUE LIGHT |
TV AREA |
Multiple |
FAULTY LIGHTS - RECOMEND REPLACING WITH LED STRIP LIGHTING |
N |
TBA |
TBA |
QUOTE 2635 SUBMITTED FOR APPROVAL |
EM14 |
BOH OFFICE |
1 |
FAILED BATTERY TEST |
Y |
N |
N |
|
EM24 |
LUNCHROOM |
1 |
FAILED BATTERY TEST |
Y |
N |
N |
|
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 09/05/2021 |
---|
| |
---|
| |