Carry out push button test and record the results below.
RCD Details (Biennial)
Distribution Board No.
Circuit No.
Push Button (YorN)
0 Degrees
180 Degrees
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB-B3A
2
Y
33
34
P
9
Y
24
16
P
10
Y
24
15
P
11
Y
24
15
P
12
Y
25
16
P
13
Y
24
15
P
14
Y
24
16
P
15
Y
24
15
P
16
Y
28
18
P
17
Y
24
16
P
18
y
24
18
P
19
Y
28
18
P
20
Y
45
177
P
21
Y
25
17
P
22
Y
75
57
P
23
Y
26
18
P
24
Y
24
17
P
25
Y
25
21
P
26
Y
27
18
P
27
Y
61
17
P
28
Y
40
30
P
29
Y
24
15
P
30
Y
24
15
P
31
Y
25
16
P
32
Y
25
17
P
33
Y
28
18
P
34
Y
28
18
P
38
Y
27
17
P
40
Y
27
18
P
48
Y
30
40
P
DB-B3B
7
Y
24
16
P
8
Y
43
32
P
9
Y
29
18
P
10
Y
26
17
P
11
Y
25
17
P
12
Y
31
25
P
13
Y
24
16
P
14
Y
25
17
P
15
Y
24
17
P
16
Y
26
20
P
17
Y
26
17
P
18
Y
28
18
P
19
Y
24
18
P
20
Y
28
16
P
21
Y
26
17
P
22
Y
28
18
P
23
Y
25
16
P
24
Y
28
18
P
26
Y
28
18
P
28
Y
28
18
P
30
Y
28
18
P
31
Y
24
17
P
32
Y
28
18
P
33
Y
29
18
P
34
Y
28
18
P
35
Y
30
34
P
36
Y
28
18
P
37
Y
38
44
P
38
Y
28
18
P
39
Y
25
21
P
40
Y
28
18
P
41
Y
23
20
P
42
Y
28
18
P
43
Y
24
15
P
44
Y
28
18
P
45
Y
26
17
P
46
Y
28
38
P
47
Y
24
17
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB-B3-A
10
R
Y
Y
Y
P
DB-B3-A
11
R
Y
Y
Y
P
DB-B3-A
12
R
Y
Y
Y
P
DB-B3-A
13
R
Y
Y
Y
P
DB-B3-A
14
R
Y
Y
Y
P
DB-B3-A
15
R
Y
Y
Y
P
DB-B3-A
16
R
Y
Y
Y
P
DB-B3-A
17
R
Y
Y
Y
P
DB-B3-A
18
R
Y
Y
Y
P
DB-B3-A
19
R
Y
Y
Y
P
DB-B3-A
20
R
Y
Y
Y
P
DB-B3-A
21
R
Y
Y
Y
P
DB-B3-A
22
R
Y
Y
Y
P
DB-B3-A
23
R
Y
Y
Y
P
DB-B3-A
24
R
Y
Y
Y
P
DB-B3-B
25
R
Y
Y
Y
P
DB-B3-B
26
R
Y
Y
Y
P
DB-B3-B
27
R
Y
Y
Y
P
DB-B3-B
28
R
Y
Y
Y
P
DB-B3-B
29
R
Y
Y
Y
P
DB-B3-B
30
R
Y
Y
Y
P
DB-B3-B
31
R
Y
Y
Y
P
DB-B3-A
32
R
Y
Y
Y
P
DB-B3-A
33
R
Y
Y
Y
P
DB-B3-B
34
R
Y
Y
Y
P
DB-B3-B
35
R
Y
Y
Y
P
DB-B3-B
36
R
Y
Y
Y
P
DB-B3-B
37
R
Y
Y
Y
P
DB-B3-B
38
R
Y
Y
Y
P
DB-B3-B
39
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB-B3-A
1
Y
Y
Y
P
DB-B3-A
2
Y
Y
Y
P
DB-B3-A
3
Y
Y
Y
P
DB-B3-A
4
Y
Y
Y
P
DB-B3-A
5
Y
Y
Y
P
DB-B3-A
6
Y
Y
Y
P
DB-B3-B
7
Y
Y
Y
P
DB-B3-B
8
Y
Y
Y
P
DB-B3-B
9
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
36W Diffuser Troffer Lights
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Haier
Fridges
1
New Fridge Stands require Droppers
N
N
N
FYI - Fridges have no power. Manager has requested new droppers be installed.
Droppers throughout store
Throughout store
Multiple
Stands without power
N
N
N
FYI - Many stands throughout store are without power or just powered with extension lead. Customers cannot demo products. Store Manager requested droppers.
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
11/05/2020
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.