Partner NameBuilt Electrical Australia
StateVIC
Date of Visit18/11/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51765
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICnunawading

Location NameNUNAWADING
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-7/1 04 Y 29 37 P
DB-7/1 06 Y 29 37 P
DB-7/1 08 Y 33 31 P
DB-7/1 10 Y 32 33 P
DB-7/1 12 Y 37 32 P
DB-7/1 14 Y 33 37 P
DB-7/1 16 Y 29 37 P
DB-7/1 22 Y 47 31 P
DB-7/1 24 Y 31 31 P
DB-7/1 25 Y 29 37 P
DB-7/1 26 Y 39 32 P
DB-7/1 28 Y 29 30 P
DB-7/1 30 Y 41 38 P
DB-7/1 32 Y 31 31 P
DB-7/1 34 Y 31 31 P
DB-7/1 36 Y 28 21 P
DB-7/1 50 Y 31 31 P
DB-7/1 52 Y 39 32 P
DB-7/1 54 Y 30 31 P
DB-7/1 56 Y 29 39 P
DB-7/1 58 Y 33 32 P
DB-7/1 60 Y 33 32 P
DB-7/1 62 Y 31 30 P
DB-7/1 64 Y 31 31 P
DB-7/1 66 Y 31 31 P
DB-7/1 68 Y 31 39 P
DB-7/1 70 Y 32 32 P
DB-7/1 72 Y 33 32 P
DB-7/4 01 Y 33 37 P
DB-7/4 03 Y 32 43 P
DB-7/4 05 Y 32 30 P
DB-7/4 07 Y 31 31 P
DB-7/4 09 Y 29 30 P
DB-7/4 10 Y 30 32 P
DB-7/4 11 Y 37 33 P
DB-7/4 12 Y 37 37 P
DB-7/4 13 Y 32 41 P
DB-7/4 14 Y 32 31 P
DB-7/4 15 Y 32 39 P
DB-7/4 16 Y 34 37 P
DB-7/4 17 Y 32 31 P
DB-7/4 18 Y 32 32 P
DB-7/4 19 Y 32 32 P
DB-7/4 21 Y 31 31 P
DB-7/4 22 Y 30 37 P
DB-7/4 23 Y 31 30 P
DB-7/4 24 Y 29 36 P
DB-7/4 29 Y 32 21 P
DB-7/4 32 Y 32 33 P
DB-7/4 34 Y 38 40 P
DB-7/4 36 Y 34 34 P
DB-7/4 38 Y 40 37 P
DB-7/4 39 Y 31 38 P
DB-7/4 40 Y 41 38 P
DB-7/4 41 Y 28 21 P
DB-7/4 42 Y 33 37 P
DB-7/4 44 Y 34 32 P
DB-7/2 12 Y 32 32 P
DB-7/2 14 Y 33 34 P
DB-7/2 16 Y 32 30 P
DB-7/2 18 Y 33 33 P
DB-7/2 20 Y 32 33 P
DB-7/2 22 Y 31 32 P
DB-7/2 24 Y 31 32 P
DB-7/2 26 Y 32 32 P
DB-7/2 28 Y 33 29 P
DB-7/2 30 Y 33 34 P
DB-7/2 32 Y 40 32 P
DB-7/2 34 Y 36 33 P
DB-7/2 36 Y 39 37 P
DB-7/2 38 Y 33 34 P
DB-7/2 40 Y 31 31 P
DB-7/2 42 Y 32 32 P
DB-7/2 44 Y 33 31 P
DB-7/2 46 Y 32 36 P
DB-7/2 48 Y 38 29 P
DB-7/2 54 Y 30 29 P
DB-7/2 56 Y 31 31 P
DB-7/2 58 Y 33 32 P
DB-7/2 60 Y 32 31 P
DB-7/2 62 Y 32 31 P
DB-7/2 64 Y 31 31 P
DB-7/2 66 Y 30 31 P
DB-7/2 68 Y 32 31 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-7/2 2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
14 S Y Y Y P
DB-7/1 15 S Y Y Y P
16 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
21 S Y N Y F FAILED BATTERY TEST Y N
22 S Y Y Y P
23 S Y Y Y P
25 S Y N Y F FAILED BATTERY TEST Y N
26 S Y Y Y P
27 S Y Y Y P
DB-7/4 29 R Y Y Y P
30 R Y Y Y P
31 R Y Y Y P
32 R Y Y Y P
34 R Y Y Y P
DB-7/1 38 S Y Y Y P
DB-7/4 41 S Y Y Y P
43 R Y Y Y P
45 R Y Y Y P
46 R Y Y Y P
47 R Y Y Y P
48 R Y Y Y P
DB-7/3 50 S Y Y Y P
51 S Y Y Y P
53 R Y N Y F FAILED BATTERY TEST Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-7/2 1 Y Y Y P
5 Y Y Y P
6 Y Y Y P
10 Y Y Y P
13 Y Y Y P
DB-7/1 17 Y Y Y P
20 Y Y Y P
24 Y Y Y P
DB-7/4 28 Y Y Y P
DB-7/1 33 Y Y Y P
35 Y Y Y P
36 Y N Y F FAILED BATTERY TEST Y N
37 Y Y Y P
39 Y Y Y P
DB-7/4 40 Y Y Y P
42 Y Y Y P
44 Y Y Y P
DB-7/3 49 Y Y Y P
52 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED HIBAY LIGHTS Y
DOUBLE DIFFUSED 36W FLUORESCENT LIGHTS Y
SINGLE DIFFUSED 36W FLUORESCENT LIGHTS Y
DOUBLE BARE 36W FLUORESCENT LIGHTS Y
SINGLE BARE 36W FLUORESCENT LIGHTS Y
70MM DOWNLIGHTS Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
CB35 AND CB37 DB-7/4 2 CBS HAVE TAPE OVER THEM WITH LABEL "DANGER QUALIFIED PERSONS ONLY" Y N N IS LINKED TO FAULTY BLUE TV LIGHTS. REMOVED CIRCUITS FROM FITTINGS. INSTALLED 2 X LARGE JUNCTION BOX
BLUE LIGHTS TV AREA - FAILED TO ILLUMINATE, POSSIBLE FAULTY FITTINGS LINKED WITH ABOVE CIRCUITS CB35 AND CB37 THAT HAVE BEEN ISOLATED. N TBA TBA REMOVED EXISTING BLUE LIGHT FITTINGS. REQUIRES TO BE REPLACED WITH NEW LED STRIP. HEAD OFFICE TO ADVISE IF THEY WOULD LIKE THIS QUOTED.
SINGLE 36W/840 DIFFUSED BATTEN STAFF ENTRANCE STAIRWELL 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW LAMP AND STARTER
DOWNLIGHT FEMALE TOILET 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
EM53 BASEMENT 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
EX36 BOH OLD TV AREA 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
TWIN 36W/840 DIFFUSED BATTEN VAULT 2 LAMPS FAILED TO ILLUMINATE Y N N INVESTAGTED AND FOUND WHOLE FITTING FAULTY. REPLACED WITH NEW FITTING
EM21 ABOVE COUNTER 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
EM25 RHS OF COUNTER NEAR SINGLE MAN DOOR 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
Site Status SelectorStore now fully compliant
Next Test Due in 6 months18/05/2021