Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit18/11/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51809
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAcockburn

Location NameCockburn
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1R SPARE SPARE SPARE P
1W SPARE SPARE SPARE P
1B Y 028 018 P
3R Y 028 038 P
3W Y 048 058 P
3B Y 027 018 P
5R Y 028 038 P
5W Y 047 017 P
5B Y 028 037 P
7R Y 028 037 P
7W SPARE SPARE SPARE P
7B SPARE SPARE SPARE P
9R SPARE SPARE SPARE P
9W SPARE SPARE SPARE P
9B Y 047 018 P
11R Y 027 037 P
11W Y 028 018 P
11B Y 028 018 P
13R Y 048 018 P
13W Y 028 038 P
13B Y 047 070 P
15R Y 047 018 P
15W BLANK BLANK BLANK P
15B Y 038 016 P
2R NOT RCD NOT RCD NOT RCD P
2W NOT RCD NOT RCD NOT RCD P
2B Y 048 018 P
4R Y 048 017 P
4W Y 028 017 P
4B Y 028 017 P
6R Y 028 018 P
6W Y 048 018 P
6B Y 027 018 P
8R Y 028 017 P
8W Y 047 018 P
8B NOT RCD NOT RCD NOT RCD P
10R BLANK BLANK BLANK P
10W BLANK BLANK BLANK P
10B Y 047 055 P
12R Y 047 020 P
12W Y 028 038 P
12B Y 028 038 P
14R Y 028 018 P
14W Y 027 017 P
14B Y 024 038 P
16R Y 025 015 P
16 R, W, B NOT RCD NOT RCD NOT RCD P
DB 02 17R Y 025 035 P
17W Y 028 018 P
17B Y 047 017 P
19 - W21 Y 019 008 P
21 SPARE SPARE SPARE P
23 R, W, B NOT RCD NOT RCD NOT RCD P
25 R, W, B NOT RCD NOT RCD NOT RCD P
27 R, W, B NOT RCD NOT RCD NOT RCD P
29 R, W, B NOT RCD NOT RCD NOT RCD P
31R Y 044 015 P
31W Y 028 018 P
31B Y 048 057 P
18R Y 029 018 P
18W Y 025 016 P
18B Y 024 015 P
20R Y 028 018 P
20W Y 028 037 P
20B Y 024 034 P
22R SPARE SPARE SPARE P
22W Y 027 018 P
22B Y 028 018 P
24 R, W, B NOT RCD NOT RCD NOT RCD P
26 R, W, B NOT RCD NOT RCD NOT RCD P
28 R, W, B NOT RCD NOT RCD NOT RCD P
30 R, W, B NOT RCD NOT RCD NOT RCD P
32 R, W, B NOT RCD NOT RCD NOT RCD P
DB 03 1R Y 055 016 P
1W Y 028 016 P
1B Y 026 015 P
3R Y 025 035 P
3W Y 023 033 P
3B Y 025 035 P
5R Y 048 018 P
5W NOT RCD NOT RCD NOT RCD NOT RCD
5B NOT RCD NOT RCD NOT RCD NOT RCD
7R SPARE SPARE SPARE P
7W SPARE SPARE SPARE P
7B BLANK BLANK BLANK P
9R BLANK BLANK BLANK P
9W BLANK BLANK BLANK P
9B BLANK BLANK BLANK P
2R Y 030 021 P
2W Y 031 041 P
2B BLANK BLANK BLANK P
4R BLANK BLANK BLANK P
4W Y 023 036 P
4B Y 028 039 P
6R Y 047 058 P
6W Y 048 018 P
6B BLANK BLANK BLANK P
8R BLANK BLANK BLANK P
8W BLANK BLANK BLANK P
8B BLANK BLANK BLANK P
10R BLANK BLANK BLANK P
10W BLANK BLANK BLANK P
10B BLANK BLANK BLANK P
DB 04 1R Y 026 016 P
1W Y 023 033 P
1B Y 023 033 P
3R NOT RCD NOT RCD NOT RCD P
3W Y 027 018 P
3B Y 025 035 P
5R Y 024 015 P
5W Y 023 016 P
5B Y 025 015 P
7R NOT RCD NOT RCD NOT RCD P
7W Y 048 038 P
7B Y 025 020 P
9R - W11 Y 009 019 P
B11 BLANK BLANK BLANK P
RB - W15 Y 009 018 P
2R Y 009 019 P
2W Y 025 017 P
2B Y 024 017 P
4R Y 027 019 P
4W Y 025 016 P
4B Y 048 020 P
6R Y 044 017 P
6W Y 027 016 P
8R Y 026 017 P
8W Y 028 018 P
8B Y 028 018 P
W14 Y 029 020 P
B14 Y 028 017 P
R16 Y 028 018 P
W16 Y 023 015 P
B16 Y 025 017 P
DB 05 1 Y 048 017 P
3 Y 036 016 P
5 NOT RCD NOT RCD NOT RCD P
7 Y 048 016 P
9 Y 025 017 P
11 Y 029 017 P
13 Y 048 018 P
15 Y 048 015 P
17 Y 044 018 P
19 Y 029 018 P
21 Y 032 015 P
23 Y 023 033 P
25 Y 031 021 P
27 Y 028 018 P
29 Y 024 035 P
31 Y 026 037 P
33 NOT RCD NOT RCD NOT RCD P
35 NOT RCD NOT RCD NOT RCD P
2 NOT RCD NOT RCD NOT RCD P
4 Y 048 035 P
6 Y 028 018 P
8 Y 047 017 P
10 Y 027 038 P
12 NOT RCD NOT RCD NOT RCD P
14 - 18 NOT RCD NOT RCD NOT RCD P
20 NOT RCD NOT RCD NOT RCD P
22 NOT RCD NOT RCD NOT RCD P
24 Y 031 020 P
26 Y 041 031 P
28 Y 024 033 P
30 Y 027 038 P
32 Y 023 033 P
34 Y 024 015 P
36 Y 025 037 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 2 r Y Y Y P
DB 01 3 s Y Y Y P
DB 01 4 s Y Y Y P
DB 01 5 s Y Y Y P
DB 01 8 s Y Y Y P
DB 01 11 s Y Y Y P
DB 01 12 s Y Y Y P
DB 01 13 s Y Y Y P
DB 01 14 s Y Y Y P
DB 01 15 s Y Y Y P
DB 01 22 s Y Y Y P
DB 01 23 s Y Y Y P
DB 01 24 s Y Y Y P
DB 01 26 s Y Y Y P
DB 01 27 s Y Y Y P
DB 01 28 s Y Y Y P
DB 05 29 r Y Y Y P
DB 05 30 r Y Y Y P
DB 05 31 r Y Y Y P
DB 05 32 r Y Y Y P
DB 05 33 r Y Y Y P
DB 05 34 r Y Y Y P
DB 05 35 r Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 1 Y Y Y P
DB 01 6 Y Y Y P
DB 01 7 Y Y Y P
DB 01 9 Y Y Y P
DB 01 10 Y Y Y P
DB 01 16 Y Y Y P
DB 01 17 Y Y Y P
DB 01 18 Y Y Y P
DB 01 19 Y Y Y P
DB 01 20 Y Y Y P
DB 01 21 Y Y Y P
DB 01 25 Y Y Y P
DB 01 37 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
40W B27 BATTEN GLOBE Y
250W MH FLOOD LIGHT Y
80W MH BUNKER LIGHT Y
250W LOWBAY RECESSED Y
80W MH SHOP LIGHT Y
400W HIBAY Y
EMERGENCY BATTEN 2 BY 36W Y
LED DOWN LIGHT 10W Y
BARE BATTEN TV WALL Y
EXITS Y
400W LOWBAY Y
1 BY 36W DEFUSED BATTEN Y
100W LED FLOOD LIGHT Y
TWIN PAR 38 FLOOD LIGHT Y
OYSTER LIGHT 18W 4 PIN PLC LAMP Y
1 BY 18W BARE BATTEN Y
EMERGENCY SPITFIRES Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
BUNKER LIGHTS FRONT/SIDE OF STORE x6 NOT ILLUMINATED N Y TBA
BUNKER LIGHTS LOADING DOCK x1 NOT ILLUMINATED N Y TBA
LOWBAYS ENTRY x3 NOT ILLUMINATED N Y TBA
LOWBAYS LOADING DOCK x2 NOT ILLUMINATED N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months18/05/2021