State | VIC |
---|
Date of Visit | 19/11/2020 |
---|
Technician's Name | Nathan McBain |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51766 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | Springvale |
---|
|
|
---|
Location Name | Springvale |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB-1 |
13 |
Y |
26 |
16 |
P |
|
|
DB-1 |
15 |
Y |
28 |
19 |
P |
|
|
DB-1 |
16 |
Y |
28 |
18 |
P |
|
|
DB-1 |
17 |
Y |
24 |
19 |
P |
|
|
DB-1 |
18 |
Y |
28 |
18 |
P |
|
|
DB-1 |
19 |
Y |
28 |
19 |
P |
|
|
DB-1 |
20 |
Y |
31 |
19 |
P |
|
|
DB-1 |
26 |
Y |
28 |
18 |
P |
|
|
DB-1 |
28 |
Y |
28 |
18 |
P |
|
|
DB-1 |
30 |
Y |
27 |
18 |
P |
|
|
DB-1 |
31 |
Y |
29 |
20 |
P |
|
|
DB-1 |
32 |
Y |
28 |
20 |
P |
|
|
DB-1 |
33 |
Y |
29 |
19 |
P |
|
|
DB-1 |
34 |
Y |
30 |
20 |
P |
|
|
DB-1 |
36 |
Y |
18 |
20 |
P |
|
|
DB-1 |
49 |
Y |
26 |
17 |
P |
|
|
DB-1 |
50 |
Y |
26 |
17 |
P |
|
|
DB-1 |
51 |
Y |
26 |
17 |
P |
|
|
DB-1 |
52 |
Y |
25 |
17 |
P |
|
|
DB-1 |
53 |
Y |
25 |
17 |
P |
|
|
DB-1 |
54 |
Y |
25 |
17 |
P |
|
|
DB-2 |
04 |
Y |
29 |
38 |
P |
|
|
DB-2 |
08 |
Y |
28 |
38 |
P |
|
|
DB-2 |
09 |
Y |
28 |
38 |
P |
|
|
DB-2 |
10 |
Y |
29 |
38 |
P |
|
|
DB-2 |
11 |
Y |
29 |
39 |
P |
|
|
DB-2 |
12 |
Y |
29 |
20 |
P |
|
|
DB-2 |
13 |
Y |
28 |
21 |
P |
|
|
DB-2 |
14 |
Y |
104 |
38 |
P |
|
|
DB-2 |
15 |
Y |
23 |
19 |
P |
|
|
DB-2 |
16 |
Y |
27 |
19 |
P |
|
|
DB-2 |
17 |
Y |
75 |
26 |
P |
|
|
DB-2 |
18 |
Y |
31 |
20 |
P |
|
|
DB-2 |
19 |
Y |
30 |
21 |
P |
|
|
DB-2 |
20 |
y |
40 |
50 |
P |
|
|
DB-2 |
21 |
Y |
23 |
33 |
P |
|
|
DB-2 |
22 |
Y |
30 |
40 |
P |
|
|
DB-2 |
23 |
Y |
24 |
35 |
P |
|
|
DB-2 |
24 |
Y |
29 |
20 |
P |
|
|
DB-2 |
25 |
Y |
28 |
38 |
P |
|
|
DB-2 |
28 |
Y |
28 |
38 |
P |
|
|
DB-2 |
29 |
Y |
28 |
38 |
P |
|
|
DB-2 |
30 |
Y |
31 |
41 |
P |
|
|
DB-2 |
31 |
Y |
29 |
23 |
P |
|
|
DB-2 |
32 |
Y |
31 |
42 |
P |
|
|
DB-2 |
33 |
Y |
30 |
24 |
P |
|
|
DB-2 |
34 |
Y |
26 |
32 |
P |
|
|
DB-2 |
35 |
Y |
26 |
25 |
P |
|
|
DB-2 |
37 |
Y |
28 |
39 |
P |
|
|
DB-2 |
38 |
Y |
28 |
38 |
P |
|
|
DB-2 |
39 |
Y |
28 |
38 |
P |
|
|
DB-2 |
40 |
Y |
28 |
38 |
P |
|
|
DB-2 |
41 |
Y |
28 |
38 |
P |
|
|
DB-2 |
42 |
Y |
28 |
38 |
P |
|
|
DB-2 |
43 |
Y |
28 |
38 |
P |
|
|
DB-2 |
44 |
Y |
28 |
38 |
P |
|
|
DB-2 |
45 |
Y |
28 |
38 |
P |
|
|
DB-2 |
46 |
Y |
28 |
38 |
P |
|
|
DB-2 |
47 |
Y |
28 |
38 |
P |
|
|
DB-2 |
48 |
Y |
28 |
38 |
P |
|
|
DB-2 |
49 |
Y |
30 |
20 |
P |
|
|
DB-2 |
50 |
Y |
30 |
40 |
P |
|
|
DB-2 |
51 |
Y |
25 |
19 |
P |
|
|
DB-2 |
52 |
Y |
23 |
37 |
P |
|
|
DB-2 |
53 |
Y |
29 |
24 |
P |
|
|
DB-2 |
54 |
Y |
26 |
39 |
P |
|
|
DB-2 |
55 |
Y |
23 |
18 |
P |
|
|
DB-2 |
56 |
Y |
23 |
19 |
P |
|
|
DB-2 |
57 |
Y |
28 |
38 |
P |
|
|
DB-2 |
58 |
Y |
28 |
38 |
P |
|
|
DB-2 |
59 |
Y |
28 |
19 |
P |
|
|
DB-2 |
60 |
Y |
29 |
24 |
P |
|
|
DB-2 |
61 |
Y |
22 |
14 |
P |
|
|
DB-2 |
64 |
Y |
23 |
38 |
P |
|
|
DB-2 |
65 |
Y |
23 |
20 |
P |
|
|
DB-2 |
66 |
Y |
31 |
41 |
P |
|
|
DB-2 |
67 |
Y |
28 |
38 |
P |
|
|
DB-2 |
68 |
Y |
28 |
38 |
P |
|
|
DB-2 |
69 |
Y |
29 |
39 |
P |
|
|
DB-2 |
70 |
Y |
27 |
33 |
P |
|
|
DB-2 |
71 |
Y |
26 |
39 |
P |
|
|
DB-2 |
73 |
Y |
30 |
40 |
P |
|
|
DB-2 |
74 |
Y |
30 |
40 |
P |
|
|
DB-2 |
75 |
Y |
25 |
19 |
P |
|
|
DB-2 |
76 |
Y |
30 |
40 |
P |
|
|
DB-2 |
77 |
Y |
28 |
36 |
P |
|
|
DB-2 |
78 |
Y |
27 |
38 |
P |
|
|
DB-2 |
79 |
Y |
30 |
20 |
P |
|
|
DB-2 |
80 |
Y |
31 |
20 |
p |
|
|
DB-2 |
81 |
Y |
26 |
116 |
P |
|
|
DB-2 |
82 |
Y |
28 |
41 |
P |
|
|
DB-2 |
83 |
Y |
23 |
44 |
P |
|
|
DB-2 |
84 |
Y |
29 |
39 |
P |
|
|
DB-2 |
85 |
Y |
29 |
38 |
P |
|
|
DB-2 |
86 |
Y |
186 |
178 |
P |
|
|
DB-2 |
87 |
Y |
189 |
188 |
P |
|
|
DB-2 |
88 |
Y |
166 |
187 |
P |
|
|
DB-2 |
89 |
Y |
30 |
21 |
P |
|
|
DB-2 |
90 |
Y |
30 |
41 |
P |
|
|
DB-2 |
91 |
Y |
27 |
23 |
P |
|
|
DB-2 |
95 |
Y |
30 |
41 |
P |
|
|
DB-2 |
96 |
Y |
29 |
39 |
P |
|
|
DB-2 |
97 |
Y |
29 |
39 |
P |
|
|
DB-2 |
98 |
Y |
31 |
40 |
P |
|
|
DB-2 |
99 |
Y |
30 |
23 |
P |
|
|
DB-2 |
100 |
Y |
29 |
38 |
P |
|
|
DB-2 |
101 |
Y |
28 |
38 |
P |
|
|
DB-2 |
102 |
Y |
28 |
38 |
P |
|
|
DB-2 |
103 |
Y |
28 |
38 |
P |
|
|
DB-2 |
104 |
Y |
28 |
38 |
P |
|
|
DB-2 |
109 |
Y |
28 |
38 |
P |
|
|
DB-2 |
110 |
Y |
28 |
38 |
P |
|
|
DB-2 |
111 |
Y |
28 |
38 |
P |
|
|
DB-2 |
112 |
Y |
28 |
38 |
P |
|
|
DB-2 |
113 |
Y |
28 |
38 |
P |
|
|
DB-2 |
114 |
Y |
28 |
38 |
P |
|
|
DB-2 |
115 |
Y |
28 |
38 |
P |
|
|
DB-2 |
116 |
Y |
28 |
38 |
P |
|
|
DB-2 |
117 |
Y |
29 |
39 |
P |
|
|
DB-2 |
118 |
Y |
36 |
48 |
P |
|
|
DB-2 |
119 |
Y |
25 |
45 |
P |
|
|
DB-2 |
120 |
Y |
30 |
19 |
P |
|
|
DB-2 |
121 |
Y |
28 |
38 |
P |
|
|
DB-2 |
122 |
Y |
25 |
35 |
P |
|
|
DB-2 |
123 |
Y |
30 |
25 |
P |
|
|
DB-2 |
124 |
Y |
28 |
38 |
P |
|
|
DB-2 |
125 |
Y |
28 |
38 |
P |
|
|
DB-2 |
126 |
Y |
28 |
38 |
P |
|
|
DB-2 |
127 |
Y |
28 |
38 |
P |
|
|
DB-2 |
128 |
Y |
28 |
38 |
P |
|
|
DB-2 |
129 |
Y |
28 |
38 |
P |
|
|
DB-2 |
130 |
Y |
28 |
38 |
P |
|
|
DB-2 |
131 |
Y |
28 |
38 |
P |
|
|
DB-2 |
132 |
Y |
28 |
38 |
P |
|
|
DB-2 |
133 |
Y |
28 |
38 |
P |
|
|
DB-2 |
134 |
Y |
28 |
38 |
P |
|
|
DB-2 |
135 |
Y |
28 |
38 |
P |
|
|
DB-2 |
136 |
Y |
28 |
38 |
P |
|
|
DB-2 |
137 |
Y |
28 |
38 |
P |
|
|
DB-2 |
138 |
Y |
28 |
38 |
P |
|
|
DB-2 |
139 |
Y |
28 |
38 |
P |
|
|
DB-2 |
140 |
Y |
28 |
38 |
P |
|
|
DB-2 |
142 |
Y |
28 |
38 |
P |
|
|
DB-2 |
143 |
Y |
28 |
38 |
P |
|
|
DB-2 |
144 |
Y |
28 |
38 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB-1 |
EM2 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM3 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM4 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM5 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM6 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM7 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM8 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM9 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM10 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM11 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM12 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM13 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM16 |
R |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM19 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM20 |
S |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EM21 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB-1 |
EX-1 |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EX-14 |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EX-15 |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EX-17 |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EX-18 |
Y |
Y |
Y |
P |
|
|
|
DB-1 |
EX-22 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
DAVIS LED HIGHBAY |
Y |
LED BATTEN LIGHT |
Y |
DUEL LED SURFACE MOUNT |
Y |
EXITL LIGHT |
Y |
RECESSED EMERGENCY |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
20A 3PHASE OUTLET |
BOH |
1 |
HAS COME OFF WALL, ONLY HANGING BY CABLE |
Y |
N |
N |
REFIX WITH LONGER SCREWS |
DROPPER |
TVS |
1 |
UNUSED DROPPER HAD BEEN WRAPED AROUND A POLE |
Y |
N |
N |
FYI - REMOVED FROM POLE AND COILED UP |
TEST AND TAG |
STORE |
30+ |
NO TEST AND TAG HAS BEEN PERFORMED ON STORE. |
N |
N |
N |
FYI |
25W LAMPS |
KINSMAN DISPLAY |
3 |
FAILED TO ILLUMINATE |
Y |
N |
N |
REPLACED WITH NEW |
14W LAMP |
KINSMAN |
1 |
FAILED TO ILLUMINATE |
Y |
N |
N |
REPLACED WITH NEW |
EX22 |
BOH |
1 |
NOT VISABLE DUE TO LADDER BEING STORED IN FRONT OF FITTING |
Y |
N |
N |
RAISED FITTING 500MM ABOVE LADDERS, NOW VISABLE. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 18/05/2021 |
---|
| |
---|
| |