Partner NameBuilt Electrical Australia
StateVIC
Date of Visit20/11/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51767
EmailEmail hidden; Javascript is required.
The Good Guys Site in VIChoppers_crossing

Location NameHOPPERS CROSSING
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB3 01 Y 24 15 P
Db3 03 Y 28 18 P
Db3 05 Y 28 18 P
Db3 07 Y 28 18 P
Db3 09 Y 28 18 P
Db3 11 Y 28 18 P
Db3 13 Y 9 16 P
Db3 15 Y 25 16 P
Db3 17 Y 32 23 P
Db3 19 Y 28 18 P
Db3 21 Y 26 17 P
Db3 23 Y 27 19 P
Db3 37 Y 42 19 P
Db3 39 Y 25 16 P
Db3 41 Y 28 38 P
Db3 43 Y 28 38 P
Db3 45 Y 25 21 P
Db3 46 Y 25 16 P
Db3 47 Y 28 18 P
Db3 48 Y 25 16 P
Db3 51 Y 21 18 P
Db3 53 Y 24 16 P
Db3 55 Y 25 16 P
Db3 56 Y 25 17 P
Db3 57 Y 24 15 P
Db3 58 Y 28 18 P
Db3 59 Y 28 18 P
Db3 61 Y 27 18 P
Db3 63 Y 29 39 P
Db3 65 Y 25 17 P
Db3 66 Y 30 20 P
Db3 67 Y 25 16 P
Db3 68 Y 26 18 P
Db3 69 Y 26 17 P
Db3 70 Y 28 18 P
Db3 71 Y 26 18 P
Db1 01 Y 14 24 P
Db1 03 Y 11 21 P
Db1 05 Y 9 19 P
Db1 11 Y 30 40 P
Db1 13 Y 25 34 P
Db1 15 Y 26 17 P
Db1 17 Y 75 18 P
Db1 19 Y 27 19 P
Db1 21 Y 29 19 P
Db1 23 Y 25 17 P
Db1 25 Y 25 16 P
Db1 27 Y 26 16 P
Db1 34 Y 28 18 P
Db1 35 Y 26 18 P
Db1 36 Y 30 20 P
Db1 38 Y 30 20 P
Db1 40 Y 28 18 P
Db1 42 Y 25 17 P
Db1 47 Y 28 18 P
Db2 01 Y 28 39 P
Db2 03 Y 29 17 P
Db2 05 Y 28 18 P
Db2 07 Y 28 38 P
Db2 09 Y Ol Ol F FAILED TEST Y
Db2 11 Y 28 33 P
Db2 13 Y 28 38 P
Db2 15 Y 29 39 P
Db2 17 Y 29 39 P
Db2 18 Y 25 16 P
Db2 19 Y 30 40 P
Db2 20 Y 30 20 P
Db2 21 Y 145 44 P
Db2 22 Y 30 40 P
Db2 23 Y 28 38 P
Db2 24 Y 24 22 P
Db2 25 Y 216 180 P
Db2 26 Y 26 17 P
Db2 27 Y 100 33 P
Db2 28 Y 28 18 P
Db2 29 Y 30 40 P
Db2 31 Y 28 38 P
Db2 33 Y 29 39 P
Db2 35 Y 27 20 P
Db2 37 Y 24 15 P
Db2 39 Y 25 16 P
Db2 41 Y 28 38 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-3 2 S Y Y Y P
DB-3 5 S Y Y Y P
DB-3 6 S Y Y Y P
DB-3 7 S Y Y Y P
DB-3 8 S Y Y Y P
DB-3 9 S Y N Y F FAILED BATTERY TEST Y N
DB-3 10 S Y Y Y P
DB-3 15 S Y Y Y P
DB-3 16 R Y Y Y P
DB-3 17 R Y Y Y P
DB-1 18 R Y Y Y P
DB-1 19 S Y Y Y P
DB-1 20 S Y Y Y P
DB-1 21 S Y Y Y P
DB-1 22 S Y Y Y P
DB-1 24 S Y Y Y P
DB-1 25 S Y Y Y P
DB-1 27 S Y Y Y P
DB-1 28 S Y Y Y P
DB-2 31 R Y Y Y P
DB-2 32 R Y Y Y P
DB-2 33 S Y Y Y P
DB-2 34 S Y Y Y P
DB-2 37 R Y Y Y P
DB-2 38 R Y Y Y P
DB-2 39 R Y Y Y P
DB-2 40 R Y Y Y P
DB-2 41 R Y Y Y P
DB-2 42 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-3 1 Y Y Y P
DB-3 3 Y Y Y P
DB-3 4 Y Y Y P
DB-3 11 Y Y Y P
DB-3 12 Y Y Y P
DB-3 13 Y Y Y P
DB-3 14 Y Y Y P
DB-1 23 Y Y Y P
DB-1 26 Y Y Y P
DB-1 29 Y Y Y P
DB-2 30 Y Y Y P
DB-2 35 Y Y Y P
DB-2 36 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
HI-BAY LIGHTS Y
LED DOWNLIGHTS Y
36W DIFFUSER LIGHTS Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
DAVIS LED HI-BAY CORDLESS PHONES 1 FAILED TO ILLUMINATE DAVIS N SCISSOR REQUIRED FOR HIGH ACCESS, TO INVOICED SEPARATELY
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LED LAMP FRONT ENTRANCE 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
CB09 DB2 UPSTAIRS LUNCHROOM 1 FAILED RCD TEST Y N N REPLACED WITH 20A RCBO
EM09 SLOW COOKERS 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR REQUIRED
SINGLE 18W/840 WP BATTEN BOH SINGLE MAN ENTRY DOOR 1 FAULTY Y N N REPLACED WITH WP LED ALTERNATIVE
DOWNLIGHTS TV AREA 1 1 OF 3 BAYS OF DOWNLIGHTS NOT WORKING DUE TO FAULTY CBUS UNIT N TBC TBC QUOTE 0743 PREVIOUSLY QUOTED
RACK LIGHT BOX SOUNDBARS/SMART HOME(2)/MONITORS DESKTOPS/HEADPHONES/HEATING COOLING/FRIDGES/WINE COOLERS/TELEVISIONS 9 FAULTY N TBC TBC QUOTE TO BE SENT FOR APPROVAL
Site Status SelectorStore now fully compliant
Next Test Due in 6 months20/05/2021