Partner NameBuilt Electrical Australia
StateVIC
Date of Visit23/11/2020
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51768
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICcranbourne

Location NameCRANBOURNE
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 15 Y 29 20 P
DB1 16 Y 50 368 F FAILED RCD TEST Y
DB1 17 Y 31 31 P
DB1 18 Y 37 37 P
DB1 19 Y 40 240 P
DB1 20 Y 62 72 P
DB1 21 Y 42 83 P
DB1 22 Y 22 32 P
DB1 23 Y 39 31 P
DB1 24 Y 31 41 P
DB1 25 Y 54 48 P
DB1 26 Y 34 22 P
DB1 27 Y 56 53 P
DB1 28 Y 59 37 P
DB1 29 Y 29 57 P
DB1 30 Y 37 91 P
DB1 31 Y 30 29 P
DB1 32 Y 39 59 P
DB1 34 Y 51 75 P
DB1 36 Y 177 104 P
DB1 44 Y 89 37 P
DB1 46 Y 37 48 P
DB1 48 Y 49 38 P
DB1-1 01 Y 38 40 P
DB1-1 02 Y 43 44 P
DB1-1 03 Y 38 45 P
DB1-1 04 Y 41 42 P
DB1-1 05 Y 49 73 P
DB1-1 06 Y 46 47 P
DB1-1 07 Y 43 44 P
DB1-1 08 Y 30 30 P
DB1-1 09 Y 44 40 P
MSB-24 13 Y 28 38 P
MSB-24 16 Y 28 19 P
MSB-24 19 Y 32 29 P
MSB-24 20 Y 51 41 P
MSB-24 21 Y 38 42 P
MSB-24 22 Y 43 44 P
MSB-24 23 Y 31 30 P
MSB-24 24 Y 40 43 P
MSB-24 25 Y 37 37 P
MSB-24 26 Y 41 42 P
MSB-24 27 Y 46 39 P
MSB-24 28 Y 37 37 P
MSB-24 29 Y 49 46 P
MSB-24 30 Y 36 36 P
MSB-24 31 Y 36 36 P
MSB-24 32 Y 43 206 P
MSB-24 33 Y 55 62 P
MSB-24 34 Y 42 266 P
MSB-24 35 Y 29 38 P
MSB-24 36 Y 29 33 P
MSB-24 44 Y 38 39 P
MSB-24 46 Y 105 32 P
MSB-24 48 Y 37 37 P
MSB-24 49 Y 107 31 P
MSB-24 51 Y 41 42 P
MSB-24 52 Y 37 36 P
MSB-24 53 Y 42 43 P
MSB-24 54 Y 53 50 P
MSB-24 55 Y 236 98 P
MSB-24 56 Y 35 34 P
MSB-24 57 Y 41 42 P
MSB-24 58 Y 29 30 P
MSB-24 59 Y 31 21 P
MSB-24 60 Y 46 54 P
MSB-24 61 Y 48 38 P
MSB-24 63 Y 26 36 P
MSB-24 65 Y 23 37 P
MSB-24 67 Y 22 19 P
MSB-24 69 Y 25 28 P
MSB-24 71 Y 28 19 P
MSB-24 73 Y 28 20 P
MSB-24 74 Y 29 48 P
MSB-24 75 Y 23 18 P
MSB-24 76 Y 28 38 P
MSB-24 77 Y 28 38 P
MSB-24 78 Y 28 38 P
MSB-24 79 Y 28 38 P
MSB-24 80 Y 29 39 P
TDB1 09 Y 10 18 P
TDB1 15 Y 35 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB-24 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
DB1 13 S Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
TDB.1 16 R Y N Y F FAILED BATTERY TEST Y N
17 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB-24 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
DB1 8 Y Y Y P
MSB-24 9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
TDB.1 13 Y Y Y P
14 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400W HIGHBAY MERCURY VAPOUR FITTING Y
4FT 36W FLUORESCENT FITTINGS Y
36W FLUORESCENT SINGLE BATTEN EMERGENCY FITTING Y
36W FLUORESCENT DOUBLE BATTEN EMERGENCY FITTING Y
70MM DOWNLIGHTS Y
36W FLUORESCENT SINGLE BATTEN FITTING Y
200W HIGHBAY MERCURY VAPOUR FITTING Y
SINGLE BATTEN 36W FLUORESCENT DIFFUSER Y
RECESSED EMERGENCY LIGHT FITTING Y
90MM LED DOWNLIGHT Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
CB16 DB1 BOH 1 FAILED RCD TEST Y N N REPLACED WITH SCHNEIDER 20A RCBO
CB44 DB1 BOH 1 TRIPPING N TBC TBC TRIPPING DUE TO FAULTY TV BLUE LIGHTS. PLEASE ADVISE IF QUOTE IS REQUIRED.
DB LEG3NDS DB1/DB1-1/MSB-24 3 NO LEGENDS Y N N PRINTED AND INSTALLED ON RETURN VISIT
EM16 STAIRWELL 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
LED DIFFUSED SINGLE BATTEN FRONT ENTRANCE EXTERNAL 2 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW 35W FITTING
FLASHING LAMPS FRONT ENTRANCE EXTERNAL 11 FAILED TO ILLUMIMATE Y N N REPLACED WITH NEW
LED FLOOD LIGHT EXTERNAL SIDE CAR PARK 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW - SCISSOR REQUIRED
LED DIFFUSER UPSTAIRES OFFICE 1 DIFFUSER HANGING Y N N REFIT FITTING
Site Status SelectorStore now fully compliant
Next Test Due in 6 months23/05/2021