Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit24/11/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51812
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAbunbury

Location NameBunbury
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1R Not RCD Not RCD Not RCD P
1W Not RCD Not RCD Not RCD P
1B Not RCD Not RCD Not RCD P
3R Not RCD Not RCD Not RCD P
3W Not RCD Not RCD Not RCD P
3B Not RCD Not RCD Not RCD P
5R Not RCD Not RCD Not RCD P
5W Not RCD Not RCD Not RCD P
5B Not RCD Not RCD Not RCD P
7R Not RCD Not RCD Not RCD P
7W Not RCD Not RCD Not RCD P
7B Not RCD Not RCD Not RCD P
9R Blank Blank Blank P
9W Not RCD Not RCD Not RCD P
9B Not RCD Not RCD Not RCD P
11R Not RCD Not RCD Not RCD P
11W Not RCD Not RCD Not RCD P
11B Not RCD Not RCD Not RCD P
13R Y 040 039 P
13W Y 051 051 P
13B Y 041 041 P
15R Spare Spare Spare P
15W Spare Spare Spare P
15B Y 041 042 P
17R Y 039 039 P
17W Y 039 039 P
17B Y 040 040 P
19R Y 040 042 P
19W Y 045 046 P
19B Y 040 051 P
21R Y 028 038 P
21W Y 044 045 P
21B Y 063 064 P
23R Y 042 044 P
23W Y 039 039 P
23B Y 059 041 P
25 R, W, B Not RCD Not RCD Not RCD P
27R Blank Blank Blank P
27W Blank Blank Blank P
27B Blank Blank Blank P
2R Not RCD Not RCD Not RCD P
2W Not RCD Not RCD Not RCD P
2B Not RCD Not RCD Not RCD P
4R Not RCD Not RCD Not RCD P
4W Not RCD Not RCD Not RCD P
4B Not RCD Not RCD Not RCD P
6R Not RCD Not RCD Not RCD P
6W Not RCD Not RCD Not RCD P
6B Not RCD Not RCD Not RCD P
8R Not RCD Not RCD Not RCD P
8W Not RCD Not RCD Not RCD P
8B Not RCD Not RCD Not RCD P
10 R, W, B Not RCD Not RCD Not RCD P
12R Not RCD Not RCD Not RCD P
12W Not RCD Not RCD Not RCD P
12B Not RCD Not RCD Not RCD P
14R Y 039 039 P
14W Y 070 067 P
14B Y 039 058 P
16R Y 050 060 P
16W Y 041 041 P
16B Not RCD Not RCD Not RCD P
18R Y 039 047 P
18W Y 058 055 P
18B Y 041 041 P
20R Y 039 040 P
20W Y 039 040 P
20B Y 049 051 P
22R Y 039 039 P
22W Y 039 039 P
22B Y 039 039 P
24R Y 039 039 P
24W Blank Blank Blank P
24B Blank Blank Blank P
26R Not RCD Not RCD Not RCD P
26W Blank Blank Blank P
26B Blank Blank Blank P
28R Blank Blank Blank P
28W Blank Blank Blank P
28B Blank Blank Blank P
DB 02 29R Not RCD Not RCD Not RCD P
29W Not RCD Not RCD Not RCD P
29B Not RCD Not RCD Not RCD P
31R Y 039 039 P
31W Y 042 042 P
31B Y 039 039 P
33R Not RCD Not RCD Not RCD P
33W Blank Blank Blank P
33B Blank Blank Blank P
35R Blank Blank Blank P
35W Blank Blank Blank P
35B Blank Blank Blank P
37R Blank Blank Blank P
37W Blank Blank Blank P
37B Blank Blank Blank P
39R Blank Blank Blank P
39W Blank Blank Blank P
39B Blank Blank Blank P
41R Blank Blank Blank P
41W Blank Blank Blank P
41B Blank Blank Blank P
30R Not RCD Not RCD Not RCD P
30W Y 046 046 P
30B Y 039 039 P
32R Y 044 044 P
32W Y 039 039 P
32B Y 041 041 P
34R Y 029 038 P
34W Y 034 040 P
34B Y 037 040 P
36R Blank Blank Blank P
36W Blank Blank Blank P
36B Blank Blank Blank P
38R Blank Blank Blank P
38W Blank Blank Blank P
38B Blank Blank Blank P
40R Blank Blank Blank P
40W Blank Blank Blank P
40B Blank Blank Blank P
42R Blank Blank Blank P
42W Blank Blank Blank P
42B Blank Blank Blank P
DB 03 1R Y 056 050 P
1W Not RCD Not RCD Not RCD P
1B Y 038 038 P
3R Y 031 031 P
3W Y 030 030 P
3B Y 049 048 P
5R Y 039 043 P
5W Y 041 047 P
5B Y 040 040 P
7R Not RCD Not RCD Not RCD P
7W Not RCD Not RCD Not RCD P
7B Not RCD Not RCD Not RCD P
9R Not RCD Not RCD Not RCD P
9W Not RCD Not RCD Not RCD P
9B Not RCD Not RCD Not RCD P
11R Y 028 032 P
11W Y 027 018 P
11B Y 026 037 P
2R Y 041 038 P
2W Y 044 045 P
2B Not RCD Not RCD Not RCD P
4R Y 041 041 P
4W Y 045 037 P
4B Y 039 039 P
6R Y 028 038 P
6W Y 028 038 P
6B Y 033 041 P
8R Y 028 038 P
8W Y 027 037 P
8B Y 028 038 P
10R Y 038 038 P
10W Y 027 037 P
10B Y 028 036 P
12R Y 027 037 P
12W Y 051 041 P
12B Y 034 042 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 2 Twin tubed Y Y Y P
3 Twin tubed Y Y Y P
4 Twin tubed Y Y Y P
5 Twin tubed Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 R Y Y Y P
13 Twin tubed Y Y Y P
14 Twin tubed Y Y Y P
15 Twin tubed Y Y Y P
17 Twin tubed Y Y Y P
18 Twin tubed Y Y Y P
19 Twin tubed Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
28 R Y Y Y P
29 R Y Y Y P
30 R Y Y Y P
31 R Y Y Y P
32 Twin tubed Y Y Y P
33 Twin tubed Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 1 Y Y Y P
6 Y Y Y P
7 Y Y Y P
16 Y Y Y P
20 Y Y Y P
21 Y Y Y P
24 Y Y Y P
27 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED hibay Y
LED down lights Y
Spit fire emergency Y
Twin 18w emergency battens Y
Exit sign Y
1 by 18w plc fitting Y
2 by 18w plc fitting Y
1 by 36w defused batten Y
80w edison screw bunker light Y
250w defused low bay Y
18w bare batten Y
36w bare batten Y
LED defused sealed batten - Davis Y
80w edison screw recessed light Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency test switch DB 01 x1 faulty Y N N OH&S
Flood light roller door Rear of store x1 New installation for safety purposes N Y TBA
Bunker light Loading dock door x1 Faulty, replacement required N Y TBA
Lowbays Front of store x3 Faulty, replacement required N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months24/05/2021