Date of Visit25/11/2020
Technician's NameMatthew Belperio
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51793
EmailEmail hidden; Javascript is required.
The Good Guys Site in SAnoarlunga

Location NameNoarlunga
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB shop 5 Y 25 41 P
DB shop 7 Y 33 43 P
DB shop 9 Y 30 40 P
DB shop 11 Y 30 40 P
DB shop 13 Y 30 40 P
DB shop 15 Y 30 40 P
DB shop 17 Y 30 40 P
DB shop 19 Y 30 40 P
DB shop 21 Y 24 34 P
DB shop 23 Y 32 42 P
DB shop 25 Y 32 42 P
DB shop 27 Y 33 43 P
DB shop 29 Y 33 42 P
DB shop 31 Y 33 40 P
DB shop 33 Y 30 40 P
DB shop 35 Y 32 42 P
DB shop 37 Y 33 42 P
DB shop 39 Y 32 42 P
DB shop 41 Y 26 36 P
DB shop 43 Y 31 22 P
DB shop 47 Y 29 35 P
DB shop 49 Y 30 40 P
DB shop 10 Y 24 34 P
DB shop 12 Y 24 34 P
DB shop 14 Y 32 42 P
DB shop 16 Y 32 44 P
DB shop 18 Y 32 42 P
DB shop 22 Y 25 35 P
DB shop 24 Y 30 40 P
DB shop 26 Y 31 35 P
DB shop 30 Y 33 43 P
DB shop 32 Y 24 34 P
DB shop 36 Y 30 40 P
DB shop 38 Y 30 40 P
DB shop 40 Y 26 36 P
DB shop 42 Y 27 40 P
DB shop 44 Y 30 40 P
DB shop 48 Y 29 39 P
DB shop 50 Y 24 29 P
DB shop 52 Y 33 44 P
DB shop 54 Y 30 40 P
DB shop 56 Y 33 43 P
DB shop 60 Y 30 40 P
DB shop 62 Y 32 42 P
DB shop 64 Y 31 42 P
DB shop 66 Y 29 34 P
DB shop 68 Y 28 37 P
DB shop 70 Y 29 34 P
MDB Red Y 144 144 P
MDB White Y 170 170 P
MDB Blue Y 174 175 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 R Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 R Y Y Y P
5 R Y Y Y P
6 R Y Y Y P
11 R Y Y Y P
12 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
36w bare batten Y
48w bare batten Y
28w bare batten Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
LED Shop Lighting Oven section 1 Faulty LED panel Haneco LED light Various N Warranty Return visit to be scheduled once materials arrive
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Flood Lights Road signage 4 Broken fittings N Y TBA Quote to be sent for approval. Boom lift required.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months25/05/2021