State | VIC |
---|
Date of Visit | 01/12/2020 |
---|
Technician's Name | Nathan McBain |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 51775 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | dandenong |
---|
|
|
---|
Location Name | Dandenong |
---|
| |
---|
HTML Block |
|
---|
Test Period | Biennial Test (once every two years) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Biennial) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
0 Degrees |
180 Degrees |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
FITOUT DB |
01 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
02 |
Y |
28 |
19 |
P |
|
|
FITOUT DB |
03 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
04 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
05 |
Y |
28 |
19 |
P |
|
|
FITOUT DB |
06 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
07 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
08 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
09 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
10 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
11 |
Y |
28 |
19 |
P |
|
|
FITOUT DB |
12 |
Y |
26 |
19 |
P |
|
|
FITOUT DB |
13 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
14 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
15 |
Y |
26 |
20 |
P |
|
|
FITOUT DB |
16 |
Y |
28 |
18 |
P |
|
|
FITOUT DB |
17 |
Y |
28 |
19 |
P |
|
|
FITOUT DB |
18 |
Y |
28 |
22 |
P |
|
|
FITOUT DB |
19 |
Y |
29 |
19 |
P |
|
|
FITOUT DB |
20 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
49 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
50 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
51 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
52 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
53 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
54 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
55 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
56 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
57 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
58 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
59 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
60 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
61 |
Y |
95 |
23 |
P |
|
|
LEONARDS |
62 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
63 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
64 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
65 |
Y |
24 |
16 |
P |
|
|
LEONARDS |
66 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
67 |
Y |
31 |
24 |
P |
|
|
LEONARDS |
68 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
69 |
Y |
25 |
18 |
P |
|
|
LEONARDS |
70 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
71 |
Y |
210 |
26 |
P |
|
|
LEONARDS |
72 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
73 |
Y |
24 |
16 |
P |
|
|
LEONARDS |
74 |
Y |
28 |
19 |
P |
|
|
LEONARDS |
75 |
Y |
24 |
19 |
P |
|
|
LEONARDS |
76 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
77 |
Y |
129 |
29 |
P |
|
|
LEONARDS |
78 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
79 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
80 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
81 |
Y |
28 |
17 |
P |
|
|
LEONARDS |
82 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
83 |
Y |
24 |
16 |
P |
|
|
LEONARDS |
84 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
85 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
86 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
87 |
Y |
24 |
16 |
P |
|
|
LEONARDS |
88 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
89 |
Y |
24 |
16 |
P |
|
|
LEONARDS |
90 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
91 |
Y |
25 |
17 |
P |
|
|
LEONARDS |
92 |
Y |
25 |
30 |
P |
|
|
LEONARDS |
93 |
Y |
29 |
19 |
P |
|
|
LEONARDS |
95 |
Y |
30 |
19 |
P |
|
|
LEONARDS |
97 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
99 |
Y |
28 |
18 |
P |
|
|
LEONARDS |
106 |
Y |
30 |
20 |
P |
|
|
LEONARDS |
108 |
Y |
29 |
20 |
P |
|
|
DB1 |
1 |
Y |
28 |
18 |
P |
|
|
DB1 |
3 |
Y |
28 |
39 |
P |
|
|
DB1 |
4 |
Y |
26 |
18 |
P |
|
|
DB1 |
5 |
Y |
28 |
18 |
P |
|
|
DB1 |
6 |
Y |
28 |
18 |
P |
|
|
DB1 |
7 |
Y |
28 |
18 |
P |
|
|
DB1 |
8 |
Y |
28 |
18 |
P |
|
|
DB1 |
9 |
Y |
29 |
22 |
P |
|
|
DB1 |
10 |
Y |
25 |
16 |
P |
|
|
DB1 |
11 |
Y |
27 |
17 |
P |
|
|
DB1 |
12 |
Y |
28 |
19 |
P |
|
|
DB1 |
13 |
Y |
23 |
23 |
P |
|
|
DB1 |
14 |
Y |
28 |
18 |
P |
|
|
DB1 |
15 |
Y |
36 |
39 |
P |
|
|
DB1 |
16 |
Y |
28 |
18 |
P |
|
|
DB1 |
17 |
Y |
39 |
33 |
P |
|
|
DB1 |
18 |
Y |
28 |
19 |
P |
|
|
DB1 |
19 |
Y |
26 |
18 |
P |
|
|
DB1 |
20 |
Y |
28 |
18 |
P |
|
|
DB1 |
21 |
Y |
25 |
19 |
P |
|
|
DB1 |
22 |
Y |
24 |
17 |
P |
|
|
DB1 |
23 |
Y |
28 |
18 |
P |
|
|
DB1 |
24 |
Y |
24 |
15 |
P |
|
|
DB1 |
25 |
Y |
25 |
17 |
P |
|
|
DB1 |
26 |
Y |
29 |
19 |
P |
|
|
DB1 |
27 |
Y |
28 |
18 |
P |
|
|
DB1 |
28 |
Y |
25 |
17 |
P |
|
|
DB1 |
29 |
Y |
24 |
18 |
P |
|
|
DB1 |
30 |
Y |
29 |
18 |
P |
|
|
DB1 |
31 |
Y |
24 |
16 |
P |
|
|
DB1 |
32 |
Y |
27 |
19 |
P |
|
|
DB1 |
33 |
Y |
25 |
18 |
P |
|
|
DB1 |
34 |
Y |
46 |
19 |
P |
|
|
DB1 |
35 |
Y |
25 |
18 |
P |
|
|
DB1 |
36 |
Y |
24 |
15 |
P |
|
|
DB1 |
37 |
Y |
24 |
19 |
P |
|
|
DB1 |
39 |
Y |
25 |
17 |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
19 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
21 |
S |
Y |
Y |
Y |
P |
|
|
|
|
22 |
S |
Y |
Y |
Y |
P |
|
|
|
|
23 |
S |
Y |
Y |
Y |
P |
|
|
|
|
24 |
S |
Y |
Y |
Y |
P |
|
|
|
|
26 |
S |
Y |
Y |
Y |
P |
|
|
|
|
27 |
S |
Y |
Y |
Y |
P |
|
|
|
|
28 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB1 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
25 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
HI-BAY LIGHTS |
Y |
LED DOWNLIGHT |
Y |
T5 TWIN BATTEN LIGHTS |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
DAVIS BLACK HIGHBAY LED |
COFFEE ACCESSORIES/TV BRACKETS/BOH AISLE(3)/BOH/TECH PHONES |
7 |
FAILED TO ILLUMINATE |
DAVIS |
|
N |
To be completed on warranty job |
|
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
EXTERNAL FRONT FLOODLIGHTS |
FRONT |
- |
GLOBES REPLACEMENT REQUIRED |
N |
TBC |
TEC |
QUOTE 2050 PREVIOUSLY SUBMITTED. RE-QUOTING REQUIRED IF APPROVAL GRANTED. |
EXTERNAL FRONT SIGN |
FRONT |
1 |
TRIPPING CIRCUIT, ISOLATED AT ISOLATOR ON PREVIOUS AUDIT |
N |
TBA |
TBA |
QUOTE 190522 PREVIOUSLY SUBMITTED. RE-QUOTING REQUIRED IF APPROVAL GRANTED. |
TEST AND TAG |
STORE |
80+ |
TEST AND TAG EXPIRED 12/FEB/2020 |
N |
N |
N |
FYI |
LED LARGE RECESSED DOWNLIGHT |
FRONT AIRLOCK |
1 |
FAILED TO ILLUMINATE |
Y |
N |
N |
FOUND LOOSE CONNECTION , RETERMINATED ELV SIDE OF TRANSFORMER. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 01/06/2021 |
---|
| |
---|
| |