Partner NameBuilt Electrical Australia
StateVIC
Date of Visit02/12/2020
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51776
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICchirnside_park

Location NameChirnside Park
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DBT 11 2 Y 36 77 P
4 Y 20 32 P
6 Y 34 45 P
8 Y 38 43 P
9 Y 28 36 P
10 Y 28 45 P
11 Y 28 48 P
12 Y 32 43 P
13 Y 34 38 P
14 Y 32 34 P
15 Y 28 34 P
17 Y 32 36 P
19 Y 33 37 P
21 Y 28 40 P
22 Y 28 32 P
23 Y 32 36 P
24 Y 34 39 P
25 Y 32 36 P
26 Y 32 49 P
27 Y 38 52 P
28 Y 28 53 P
29 Y 160 180 P
30 Y 34 34 P
31 Y 32 38 P
32 Y 32 32 P
33 Y 28 34 P
34 Y 29 40 P
35 Y 28 34 P
36 Y 29 31 P
37 Y 30 34 P
38 Y 32 34 P
39 Y 33 36 P
40 Y 44 48 P
41 Y 34 37 P
42 Y 35 50 P
44 Y 35 43 P
46 Y 34 42 P
48 Y 29 48 P
50 Y 28 46 P
52 Y 29 37 P
54 Y 27 43 P
55 Y 32 42 P
56 Y 31 41 P
57 Y 30 38 P
58 Y 33 34 P
59 Y 28 45 P
60 Y 32 34 P
61 Y 34 45 P
62 Y 29 35 P
63 Y 30 32 P
64 Y 32 35 P
65 Y 33 36 P
66 Y 34 36 P
67 Y 35 38 P
68 Y 34 39 P
69 Y 32 37 P
70 Y 33 35 P
71 Y 31 33 P
72 Y 32 35 P
73 Y 32 37 P
74 Y 40 44 P
75 Y 122 188 P
76 Y 111 176 P
78 Y 38 43 P
80 Y 40 45 P
82 Y 32 47 P
84 Y 32 42 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB T11 8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 R Y Y Y P
13 R Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
16 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB T11 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
20 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Troffer Y
LED Downlight Y
Exit Light Y
Recessed Emergency Light Y
Flood Lights Y
Oyster Light Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Circuit breaker 1, 2, 3, 4, 5 43,45 & 51 Switchboard DB-T11 14 Switchboard scratching and doesn't close correctly because circuit breakers get in the way N N N Replace with circuit breakers to resolve issue. Head office advised do not proceed with replacement.
Oyster Light Front of store (outside) 6 Failed to Illuminate Y N N Replaced with new WP LED bunker lights
LED Panel Light Above Dyson vacuum cleaner 1 Failed to Illuminate Y N N Replaced with new
3.6m Rack Light Box Sound Systems 1 Failed to Illuminate Y N N Replaced with 8 new 12W linkable lights
3.6m Rack Light Box Phone Accessories 1 Failed to Illuminate Y N N Replaced with 8 new 12W linkable lights
Site Status SelectorStore now fully compliant
Next Test Due in 6 months02/06/2020