Date of Visit19/11/2020
Technician's NameAdam Hoes
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51810
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAo'connor

Location NameO'Connor
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 01 1 Y 029 038 P
2 Y 034 045 P
3 Y 028 038 P
4 Not RCD Not RCD Not RCD P
5 Blank Blank Blank P
6 Not RCD Not RCD Not RCD P
7 Not RCD Not RCD Not RCD P
8 Y 038 038 P
9 Y 038 038 P
10 Y 028 035 P
11 Y 028 028 P
12 Y 038 038 P
13 Y 038 038 P
14 Not RCD Not RCD Not RCD P
15 Y 038 038 P
16 Y 038 038 P
17 Y 039 039 P
18 Y 031 031 P
19 Y 038 039 P
20 Y 061 073 P
21 Not RCD Not RCD Not RCD P
22 Y 039 038 P
23 Y 059 062 P
24 Y 046 039 P
25 Y 041 041 P
26 Y 068 053 P
27 Y 039 043 P
28 Y 062 042 P
29 Y 039 043 P
30 Y 062 042 P
31 Not RCD Not RCD Not RCD P
32 Not RCD Not RCD Not RCD P
33 Not RCD Not RCD Not RCD P
34 Y 039 039 P
35 Y 039 040 P
36 Y 047 047 P
37 Y 047 048 P
38 Not RCD Not RCD Not RCD P
39 Not RCD Not RCD Not RCD P
40 Not RCD Not RCD Not RCD P
41 Not RCD Not RCD Not RCD P
42 Not RCD Not RCD Not RCD P
43 Y 047 047 P
44 Y 052 053 P
45 Y 042 045 P
46 Y 039 039 P
47 Y 040 039 P
48 Not RCD Not RCD Not RCD P
49 Not RCD Not RCD Not RCD P
50 Y 048 048 P
51 Y 047 048 P
52 Blank Blank Blank P
53 Blank Blank Blank P
54 Y 065 065 P
55 Y 039 039 P
56 Y 039 039 P
57 Y 041 039 P
58 Y 028 038 P
59 Y 036 038 P
60 Not RCD Not RCD Not RCD P
61 Y 038 038 P
62 Spare Spare Spare P
63 Spare Spare Spare P
64 Y 039 039 P
65 Spare Spare Spare P
66 Y 048 048 P
67 Y 043 039 P
68 Y 049 048 P
69 Spare Spare Spare P
70 Not RCD Not RCD Not RCD P
71 Not RCD Not RCD Not RCD P
72 Y 024 024 P
73 Not RCD Not RCD Not RCD P
DB 02 74 Y 023 018 P
75 Y 025 036 P
76 Not RCD Not RCD Not RCD P
77 Y 028 038 P
78 Spare Spare Spare P
79 Spare Spare Spare P
80 Y 058 056 P
81 Spare Spare Spare P
82 Y 023 043 P
83 Y 038 052 P
84 Spare Spare Spare P
85 Spare Spare Spare P
86 Spare Spare Spare P
87 Spare Spare Spare P
88 Spare Spare Spare P
89 Spare Spare Spare P
90 Spare Spare Spare P
91 Y 047 047 P
92 Y 039 039 P
93 Y 024 023 P
94 Y 039 039 P
95 Y 047 047 P
96 Y 057 057 P
97 Y 039 039 P
98 Y 055 054 P
99 Y 054 030 P
100 Not RCD Not RCD Not RCD P
101 Not RCD Not RCD Not RCD P
102 Not RCD Not RCD Not RCD P
103 Not RCD Not RCD Not RCD P
104 Not RCD Not RCD Not RCD P
105 Not RCD Not RCD Not RCD P
106 Not RCD Not RCD Not RCD P
107 Y 039 041 P
108 Y 039 041 P
109 Y 040 043 P
110 Y 039 042 P
111 Y 020 024 P
112 Not RCD Not RCD Not RCD P
113 Y 055 058 P
114 Y 037 037 P
115 Not RCD Not RCD Not RCD P
116 Not RCD Not RCD Not RCD P
117 Not RCD Not RCD Not RCD P
118 Not RCD Not RCD Not RCD P
119 Not RCD Not RCD Not RCD P
120 Not RCD Not RCD Not RCD P
DB 03 1 Not RCD Not RCD Not RCD P
3 Y 029 038 P
5 Y 022 038 P
7 Y 040 039 P
9 Y 029 040 P
11 Y 022 018 P
13 Y 043 042 P
15 Y 022 019 P
17 Not RCD Not RCD Not RCD P
19 Not RCD Not RCD Not RCD P
21 Y 039 039 P
23 Not RCD Not RCD Not RCD P
25 Not RCD Not RCD Not RCD P
27 Not RCD Not RCD Not RCD P
29 Not RCD Not RCD Not RCD P
31 Not RCD Not RCD Not RCD P
33 Not RCD Not RCD Not RCD P
35 Not RCD Not RCD Not RCD P
37 Not RCD Not RCD Not RCD P
39 Not RCD Not RCD Not RCD P
41 Not RCD Not RCD Not RCD P
43 Not RCD Not RCD Not RCD P
45 Not RCD Not RCD Not RCD P
47 Y 030 040 P
2 Y 028 038 P
4 Y 022 017 P
6 Spare Spare Spare P
8 Y 027 037 P
10 Y 028 037 P
12 Y 028 035 P
14 Y 032 041 P
16 Y 029 039 P
18 Y 025 018 P
20 Y 031 039 P
22 Blank Blank Blank P
24 Blank Blank Blank P
26 Blank Blank Blank P
28 Blank Blank Blank P
30 Blank Blank Blank P
32 Blank Blank Blank P
34 Not RCD Not RCD Not RCD P
36 Not RCD Not RCD Not RCD P
38 Not RCD Not RCD Not RCD P
40 Not RCD Not RCD Not RCD P
42 Not RCD Not RCD Not RCD P
44 Not RCD Not RCD Not RCD P
46 Not RCD Not RCD Not RCD P
48 Not RCD Not RCD Not RCD P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 01 3 Twin Emergency Spot Y Y Y P
4 Twin Emergency Spot Y Y Y P
5 Twin Emergency Spot Y Y Y P
6 Twin Emergency Spot Y Y Y P
11 R Y Y Y P
12 R Y Y Y P
14 Twin Emergency Spot Y Y Y P
16 Twin Emergency Spot Y Y Y P
17 Twin Emergency Spot Y Y Y P
18 Twin Emergency Spot Y Y Y P
19 Twin Emergency Spot Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
7 Y Y Y P
8 Y Y Y P
9 Y Y Y P
10 Y Y Y P
13 Y Y Y P
15 Y Y Y P
20 Y Y Y P
21 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400w MH Hibay Y
40w Batten Globe Y
12v Downlights Y
2 by 36w Troffer Y
2 by 36w Defused Battens Y
1 by 36w Battens Y
1 by 18w Battens Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Exit/Emergencies Tenancy Additional spitfires, exits and jumbo exits required Not compliant N Y TBA
Site Status SelectorStore now fully compliant
Next Test Due in 6 months19/05/2021