StateVIC
Date of Visit09/12/2020
Technician's NameAnthony Zammit
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number51772
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICrefinery_training_centre

Location NameREFINERY TRAINING CENTRE
HTML Block
Test PeriodBiennial Test (once every two years)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Biennial)
Distribution Board No. Circuit No. Push Button (YorN) 0 Degrees 180 Degrees Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-A 19 Y 24 16 P
DB-A 21 Y 28 19 P
DB-A 23 Y 30 20 P
DB-A 37 Y 28 18 P
DB-A 39 Y 25 17 P
DB-A 41 Y 29 38 P
DB-A 43 Y 28 18 P
DB-A 44 Y 28 18 P
DB-A 46 Y 28 19 P
DB-A 49 Y 29 19 P
DB-A 52 Y 29 19 P
DB-A 54 Y 30 20 P
DB-A 56 Y 29 19 P
DB-A 60 Y 29 19 P
DB-A 62 Y 29 20 P
DB-A 66 Y 28 18 P
DB-A 68 Y 51 38 P
DB-A 69 Y 28 18 P
DB-A 70 Y 28 18 P
DB-B 2 Y 21 27 P
DB-B 4 Y 15 24 P
DB-B 6 Y 20 30 P
DB-B 8 Y 19 33 P
DB-B 10 Y 21 31 P
DB-B 12 Y 20 28 P
DB-B 14 Y 21 31 P
DB-B 16 Y 18 26 P
DB-B 18 Y 21 27 P
DB-B 20 Y 18 26 P
DB-B 21 Y 32 43 P
DB-B 22 Y 20 30 P
DB-B 23 Y 21 31 P
DB-B 24 Y 19 29 P
DB-B 25 Y 21 31 P
DB-B 26 Y 20 30 P
DB-B 27 Y 18 28 P
DB-B 28 Y 18 28 P
DB-B 29 Y 18 28 P
DB-B 30 Y 18 28 P
DB-B 32 Y 117 117 P
DB-B 33 Y 18 28 P
DB-B 34 Y 18 28 P
DB-B 36 Y 69 36 P
DB-B 37 Y 19 27 P
DB-B 38 Y 29 30 P
DB-B 40 Y 18 29 P
DB-B 42 Y 39 39 P
DB-B 44 Y 38 38 P
DB-B 46 Y 18 27 P
DB-B 48 Y 18 26 P
DB-B 50 Y 18 28 P
DB-C 2 Y 29 39 P
DB-C 4 Y 29 19 P
DB-C 6 Y 28 19 P
DB-C 8 Y 28 19 P
DB-C 9 Y 17 7 P
DB-C 10 Y 28 19 P
DB-C 11 Y 17 7 P
DB-C 12 Y 25 18 P
DB-C 13 Y 17 7 P
DB-C 15 Y 28 19 P
DB-C 17 Y 29 18 P
DB-C 19 Y 28 19 P
DB-C 21 Y 29 19 P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 S Y Y Y P
2 S Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
5 R Y Y Y P
6 R Y Y Y P
7 R Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
11 R Y Y Y P
12 R Y Y Y P
13 R Y Y Y P
14 R Y Y Y P
15 R Y N Y F Failed Battery Test Y N
16 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
19 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Downlight Y
Double 36W Fluorescent Light Y
Single 18W Fluorescent Light Y
Double 21W Fluorescent Light Y
Hi-Bay Lights Y
LED HiBay Y
Recessed Emergency Light Y
Surface Mount Emergency Lights Y
Exit Lights Y
LED Panel Y
Stair Lights Y
14W Double Fluorescent Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency Test Facility DB-A 1 No emergency test facility N Y TBC Quote to be sent for approval
Emergency test facility DB-B 1 No emergency test facility N Y TBC Quote to be sent for approval
Double 36W Fluorescent Light Above DB-C 1 Failed to illuminate N Y TBC Quote to be sent for approval
Double 21W Fluorescent Light Near female toilets 1 Failed to illuminate Y N N Replaced with 2x 14W lamps
Double 36W Fluorescent Light Supply room 1 Failed to illuminate Y N N Replaced with 35W Fitting
Recessed Emergency Light Female toilets 1 Failed Battery Test Y N N Replaced with new
Site Status SelectorCompleted but with repairs required
Next Test Due in 6 months11/06/2020