StateVIC
Date of Visit02/02/2021
Technician's NameCale Johnstone
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54266
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICshepparton

Location Nameshepparton
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Main switchboard 2 Y P
Main switchboard 4 Y P
Main switchboard 6 Y P
Main switchboard 8 Y P
Main switchboard 10 Y P
Main switchboard 14 Y P
Main switchboard 18 Y P
Main switchboard 24 Y P
Main switchboard 51 Y P
Main switchboard 59 Y P
Main switchboard 61 Y P
Main switchboard 63 Y P
Main switchboard 65 Y P
Main switchboard 67 Y P
Main switchboard 69 Y P
Main switchboard 71 Y P
Main switchboard 73 Y P
Main switchboard 74 Y P
Main switchboard 75 Y P
Main switchboard 76 Y P
Main switchboard 77 Y P
Main switchboard 78 Y P
Main switchboard 79 Y P
Main switchboard 80 Y P
Main switchboard 81 Y P
Main switchboard 82 Y P
Main switchboard 83 Y P
Main switchboard 84 Y P
Main switchboard 86 Y P
Main switchboard 87 Y P
Sub board DB 01 2 Y P
Sub board DB 01 4 Y P
Sub board DB 01 6 Y P
Sub board DB 01 7 Y P
Sub board DB 01 8 Y P
Sub board DB 01 10 Y P
Sub board DB 01 11 Y P
Sub board DB 01 12 Y P
Sub board DB 01 13 Y P
Sub board DB 01 14 Y P
Sub board DB 01 15 Y P
Sub board DB 01 16 Y P
Sub board DB 01 17 Y P
Sub board DB 01 18 Y P
Sub board DB 01 19 Y P
Sub board DB 01 20 Y P
Sub board DB 01 21 Y P
Sub board DB 01 22 Y P
Sub board DB 01 23 N N/A Circuit breaker locked in off position by previous electrician.
Sub board DB 01 24 Y P
Sub board DB 01 25 Y P
Sub board DB 01 26 Y P
Sub board DB 01 27 Y P
Sub board DB 01 28 Y P
Sub board DB 01 29 Y P
Sub board DB 01 30 Y P
Sub board DB 01 32 Y P
Sub board DB 01 34 Y P
Sub board DB 01 36 Y P
Sub board DB 01 37 Y P
Sub board DB 01 38 Y P
Sub board DB 01 39 Y P
Sub board DB 01 40 Y P
Sub board DB 01 41 Y P
Sub board DB 01 42 Y P
Sub board DB 01 43 Y P
Sub board DB 01 44 Y P
Sub board DB 01 45 Y P
Sub board DB 01 46 Y P
Sub board DB 01 47 Y P
Sub board DB 01g 48 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Main switchboard 2 S Y Y Y P
Main switchboard 3 S Y Y Y P
Main switchboard 4 S Y Y Y P
Main switchboard 5 S Y Y Y P
Main switchboard 6 S Y Y Y P
Main switchboard 10 S Y Y Y P
Main switchboard 14 R Y Y Y P
Main switchboard 15 R Y Y Y P
Main switchboard 16 R Y Y Y P
Main switchboard 20 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Main switchboard 1 Y Y Y P
Main switchboard 7 Y Y Y P
Main switchboard 8 Y Y Y P
Main switchboard 9 Y Y Y P
Main switchboard 11 Y Y Y P
Main switchboard 12 Y Y Y P
Main switchboard 13 Y Y Y P
Main switchboard 17 Y Y Y P
Main switchboard 18 Y Y Y P
Main switchboard 19 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Exit Lights LED Y
Exit Lights 10W Fluorescent Y
Surface Emergency Lights Y
Recessed Emergency Lights Y
MH Hi-Bay Lights 400W Y
2 x 36W Fluorescent Lights Y
70mm LED Downlights MR16 Y
18W Fluorescent Lights Y
Are there any Warranty items needing to be repaired?No
Site Status SelectorStore now fully compliant
Next Test Due in 6 months03/08/2021