StateNSW
Date of Visit22/02/2021
Technician's NameEddie Zaida
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54483
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWchatswood

Location NameChatswood
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
36 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y F Failed push button test Y
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
57 Y P
59 Y P
DB01 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
16 Y P
18 Y P
28 Y P
DB02 15 Y P
16 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EM1 S Y Y Y P
DB1 EM2 S Y Y Y P
DB1 EM3 S Y Y Y P
DB1 EM4 S Y Y Y P
DB1 EM5 S Y Y Y P
DB1 EM6 S Y Y Y P
DB1 EM7 S Y Y Y P
DB1 EM8 S Y Y Y P
DB1 EM9 S Y Y Y P
DB1 EM10 S Y Y Y P
DB1 EM11 S Y Y Y P
DB1 EM8a S Y Y Y P
DB1 EM9a R Y Y Y P
DB1 EM10a R Y Y Y P
DB1 EM11a R Y Y Y P
DB1 EM12a R Y Y Y P
DB1 EM13a R Y Y Y P
DB1 EM14a R Y Y Y P
DB1 EM15a R Y Y Y P
DB1 EM16a R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 EX1 Y Y Y P
DB1 EX2 Y Y Y P
DB1 EX3 Y Y Y P
DB1 EX4 Y Y Y P
DB1 EX5 Y Y Y P
DB1 EX6 Y Y Y P
DB1 EX7 Y Y Y P
DB1 EX8 Y Y Y P
DB1 EX12 Y Y Y P
DB1 EX16 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
High Bays Halo Globe Y
2 x 8W Fluoro Y
50mm LED Downlight Y
1200mm Fluoro Troffer Y
Fluorescent T5 Fluoro Pelmet Lights Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
Davis LED Panels Upstairs offices 66 Yellowing and half dim Davis - N To be replaced on warranty job
Hi-Bay Mobiles 1 Intermittently turns off Davis - N To be replaced on warranty job
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCBO 50 DB1 1 Failed push button test Y N N Nhp DinT 20amp RCBO installed
18W Batten Air Handler 1 Not illuminated Y N N Replaced lamp & starter
Wall Bay Light Boxes Wall Bays 20 Not illuminated Y N N Replaced 62 lamps, 2 x technicians required
Circuit Breakers DB01 6 circuits Staff using CB's to turn lights on and off, large number of displays stay on at night. N Y TBA Quote to be sent for approval, pre-trade works, installation of additional switches.
Tripping Circuits DB1 5 Circuits trip every morning N Y TBA Quote to be sent for approval, additional circuits and new sub board required as store is very old and run down
Site Status SelectorStore now fully compliant
Next Test Due in 6 months23/08/2021