State | VIC |
---|
Date of Visit | 12/03/2021 |
---|
Technician's Name | Nathan McBain |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 54175 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in VIC | sunbury |
---|
|
|
---|
Location Name | SUNBURY |
---|
| |
---|
HTML Block |
|
---|
Test Period | 6 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
RCD Details (6 Month) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
MAIN DB POWER |
02 |
Y |
P |
|
|
MAIN DB POWER |
04 |
Y |
P |
|
|
MAIN DB POWER |
06 |
Y |
P |
|
|
MAIN DB POWER |
07 |
Y |
P |
|
|
MAIN DB POWER |
08 |
Y |
P |
|
|
MAIN DB POWER |
09 |
Y |
P |
|
|
MAIN DB POWER |
10 |
Y |
P |
|
|
MAIN DB POWER |
11 |
Y |
P |
|
|
MAIN DB POWER |
12 |
Y |
P |
|
|
MAIN DB POWER |
13 |
Y |
P |
|
|
MAIN DB POWER |
14 |
Y |
P |
|
|
MAIN DB POWER |
15 |
Y |
P |
|
|
MAIN DB POWER |
16 |
Y |
P |
|
|
MAIN DB POWER |
17 |
Y |
P |
|
|
MAIN DB POWER |
18 |
Y |
P |
|
|
MAIN DB POWER |
19 |
Y |
P |
|
|
MAIN DB POWER |
20 |
Y |
P |
|
|
MAIN DB POWER |
21 |
Y |
P |
|
|
MAIN DB POWER |
22 |
Y |
P |
|
|
MAIN DB POWER |
23 |
Y |
P |
|
|
MAIN DB POWER |
24 |
Y |
p |
|
|
MAIN DB POWER |
25 |
Y |
P |
|
|
MAIN DB POWER |
26 |
Y |
P |
|
|
MAIN DB POWER |
27 |
Y |
P |
|
|
MAIN DB POWER |
28 |
Y |
P |
|
|
MAIN DB POWER |
29 |
Y |
P |
|
|
MAIN DB POWER |
30 |
Y |
P |
|
|
MAIN DB POWER |
31 |
Y |
P |
|
|
MAIN DB POWER |
32 |
Y |
P |
|
|
MAIN DB POWER |
33 |
Y |
P |
|
|
MAIN DB POWER |
34 |
Y |
P |
|
|
MAIN DB POWER |
35 |
Y |
P |
|
|
MAIN DB POWER |
36 |
Y |
P |
|
|
MAIN DB POWER |
37 |
Y |
P |
|
|
MAIN DB POWER |
38 |
Y |
P |
|
|
MAIN DB POWER |
40 |
Y |
P |
|
|
MAIN DB POWER |
41 |
Y |
P |
|
|
MAIN DB POWER |
42 |
Y |
P |
|
|
MAIN DB POWER |
44 |
Y |
P |
|
|
MAIN DB POWER |
46 |
Y |
P |
|
|
MAIN DB POWER |
48 |
Y |
P |
|
|
MAIN DB POWER |
49 |
Y |
P |
|
|
MAIN DB POWER |
50 |
Y |
P |
|
|
MAIN DB POWER |
51 |
Y |
P |
|
|
MAIN DB POWER |
52 |
Y |
P |
|
|
MAIN DB POWER |
53 |
Y |
P |
|
|
MAIN DB POWER |
54 |
Y |
P |
|
|
MAIN DB POWER |
55 |
Y |
P |
|
|
MAIN DB POWER |
56 |
Y |
P |
|
|
MAIN DB POWER |
57 |
Y |
P |
|
|
MAIN DB POWER |
58 |
Y |
P |
|
|
MAIN DB POWER |
59 |
Y |
P |
|
|
MAIN DB POWER |
60 |
Y |
P |
|
|
MAIN DB POWER |
61 |
Y |
P |
|
|
MAIN DB POWER |
62 |
Y |
P |
|
|
MAIN DB POWER |
63 |
Y |
P |
|
|
MAIN DB POWER |
64 |
Y |
P |
|
|
MAIN DB POWER |
65 |
Y |
P |
|
|
MAIN DB POWER |
66 |
Y |
P |
|
|
MAIN DB POWER |
67 |
Y |
P |
|
|
MAIN DB POWER |
68 |
Y |
P |
|
|
MAIN DB POWER |
69 |
Y |
P |
|
|
MAIN DB POWER |
70 |
Y |
P |
|
|
MAIN DB POWER |
71 |
Y |
P |
|
|
MAIN DB POWER |
72 |
Y |
P |
|
|
MAIN DB POWER |
73 |
Y |
P |
|
|
MAIN DB POWER |
74 |
Y |
P |
|
|
MAIN DB POWER |
75 |
Y |
P |
|
|
MAIN DB POWER |
76 |
Y |
P |
|
|
MAIN DB POWER |
77 |
Y |
P |
|
|
MAIN DB POWER |
78 |
Y |
P |
|
|
MAIN DB POWER |
79 |
Y |
P |
|
|
MAIN DB POWER |
80 |
Y |
P |
|
|
MAIN DB POWER |
81 |
Y |
P |
|
|
MAIN DB POWER |
82 |
Y |
P |
|
|
MAIN DB POWER |
83 |
Y |
P |
|
|
MAIN DB POWER |
84 |
Y |
P |
|
|
MAIN DB POWER |
84 |
Y |
P |
|
|
MAIN DB POWER |
86 |
Y |
P |
|
|
MAIN DB POWER |
87 |
Y |
P |
|
|
MAIN DB POWER |
88 |
Y |
P |
|
|
MAIN DB POWER |
89 |
Y |
P |
|
|
MAIN DB POWER |
90 |
Y |
P |
|
|
MAIN DB POWER |
91 |
Y |
P |
|
|
MAIN DB POWER |
92 |
Y |
P |
|
|
MAIN DB POWER |
93 |
Y |
P |
|
|
MAIN DB POWER |
94 |
Y |
P |
|
|
MAIN DB POWER |
95 |
Y |
P |
|
|
MAIN DB POWER |
96 |
Y |
P |
|
|
MAIN DB LIGHTING |
01 |
Y |
P |
|
|
MAIN DB LIGHTING |
02 |
Y |
P |
|
|
MAIN DB LIGHTING |
03 |
Y |
P |
|
|
MAIN DB LIGHTING |
04 |
Y |
P |
|
|
MAIN DB LIGHTING |
05 |
Y |
P |
|
|
MAIN DB LIGHTING |
06 |
Y |
P |
|
|
MAIN DB LIGHTING |
07 |
Y |
P |
|
|
MAIN DB LIGHTING |
08 |
Y |
P |
|
|
MAIN DB LIGHTING |
09 |
Y |
P |
|
|
MAIN DB LIGHTING |
10 |
Y |
P |
|
|
MAIN DB LIGHTING |
11 |
Y |
P |
|
|
MAIN DB LIGHTING |
12 |
Y |
P |
|
|
MAIN DB LIGHTING |
13 |
Y |
P |
|
|
MAIN DB LIGHTING |
14 |
Y |
P |
|
|
MAIN DB LIGHTING |
15 |
Y |
P |
|
|
MAIN DB LIGHTING |
16 |
Y |
P |
|
|
MAIN DB LIGHTING |
17 |
Y |
P |
|
|
MAIN DB LIGHTING |
18 |
Y |
P |
|
|
MAIN DB LIGHTING |
19 |
Y |
P |
|
|
MAIN DB LIGHTING |
20 |
Y |
P |
|
|
MAIN DB LIGHTING |
21 |
Y |
P |
|
|
MAIN DB LIGHTING |
22 |
Y |
P |
|
|
MAIN DB LIGHTING |
23 |
Y |
P |
|
|
MAIN DB LIGHTING |
24 |
Y |
P |
|
|
DB1 |
01 |
Y |
P |
|
|
DB1 |
02 |
Y |
P |
|
|
DB1 |
03 |
Y |
P |
|
|
DB1 |
04 |
Y |
P |
|
|
DB1 |
05 |
Y |
P |
|
|
DB1 |
06 |
Y |
P |
|
|
DB1 |
07 |
Y |
P |
|
|
DB1 |
08 |
Y |
P |
|
|
DB1 |
09 |
Y |
P |
|
|
DB1 |
10 |
Y |
P |
|
|
DB1 |
11 |
Y |
P |
|
|
DB1 |
12 |
Y |
P |
|
|
DB1 |
13 |
Y |
P |
|
|
DB1 |
14 |
Y |
P |
|
|
DB1 |
15 |
Y |
P |
|
|
DB1 |
16 |
Y |
P |
|
|
DB1 |
17 |
Y |
P |
|
|
DB1 |
18 |
Y |
P |
|
|
DB1 |
19 |
Y |
P |
|
|
DB1 |
20 |
Y |
P |
|
|
DB1 |
21 |
Y |
P |
|
|
DB1 |
22 |
Y |
P |
|
|
DB1 |
23 |
Y |
P |
|
|
DB1 |
24 |
Y |
P |
|
|
DB1 |
25 |
Y |
P |
|
|
DB1 |
26 |
Y |
P |
|
|
DB1 |
27 |
Y |
P |
|
|
DB1 |
28 |
Y |
P |
|
|
DB1 |
29 |
Y |
P |
|
|
DB1 |
30 |
Y |
P |
|
|
DB1 |
31 |
Y |
P |
|
|
DB1 |
32 |
Y |
P |
|
|
DB1 |
33 |
Y |
P |
|
|
DB1 |
34 |
Y |
P |
|
|
DB1 |
35 |
Y |
P |
|
|
DB1 |
36 |
Y |
P |
|
|
DB1 |
37 |
Y |
P |
|
|
DB1 |
38 |
Y |
P |
|
|
DB1 |
39 |
Y |
P |
|
|
DB1 |
40 |
Y |
P |
|
|
DB1 |
41 |
Y |
P |
|
|
DB1 |
42 |
Y |
P |
|
|
DB1 |
43 |
Y |
P |
|
|
DB1 |
44 |
Y |
P |
|
|
DB1 |
45 |
Y |
P |
|
|
DB1 |
46 |
Y |
P |
|
|
DB1 |
47 |
Y |
P |
|
|
DB1 |
48 |
Y |
P |
|
|
DB1 |
49 |
Y |
P |
|
|
DB1 |
50 |
Y |
P |
|
|
DB1 |
51 |
Y |
P |
|
|
DB1 |
52 |
Y |
P |
|
|
DB1 |
53 |
Y |
P |
|
|
DB1 |
54 |
Y |
P |
|
|
DB1 |
55 |
Y |
P |
|
|
DB1 |
56 |
Y |
P |
|
|
DB1 |
57 |
Y |
P |
|
|
DB1 |
58 |
Y |
P |
|
|
DB1 |
59 |
Y |
P |
|
|
DB1 |
60 |
Y |
P |
|
|
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MAIN DB LIGHTING |
EM06 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM07 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM08 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EM09 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
EM16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
MAIN DB LIGHTING |
EX01 |
Y |
Y |
Y |
P |
|
|
|
|
EX02 |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
EX03 |
Y |
Y |
Y |
P |
|
|
|
|
EX04 |
Y |
Y |
Y |
P |
|
|
|
|
EX05 |
Y |
Y |
Y |
P |
|
|
|
|
EX13 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
90mm LED Downlights |
Y |
70mm LED Downlights |
Y |
Black Davis LED Hi-Bay Lights |
Y |
Recessed Emergency Lights |
Y |
Clevertronics Ceiling Mount Exit Lights |
Y |
Clevertronics Wall Mount Exit Lights |
Y |
LED Hi-Bay Light Fitting (Store Room) |
Y |
Track Spot Lights Black |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
WARRANTY | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault/problem |
Manufacturer |
Part Number |
Repaired on Site |
Comments |
HIGHBAY BLACK |
ASKO KITCHEN DISPLAY/TVS NEAR BOH ENTRANCE |
2 |
FAILED TO ILLUMINATE |
DAVIS |
|
N |
STURDIE WILL RETURN TO SITE ONCE HI-BAYS ARE PROCURED FROM SUPPLIER |
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
EXTERNAL FLOODLIGHTS |
EXTERNAL FRONT OF BUILDING |
7 |
FAILED TO ILLUMINATE |
N |
Y |
TBC |
QUOTE 2873 HAD BEEN SUBMITTED TO HEAD OFFICE FOR APPROVAL IN DECEMEBER 2020 |
TEST AND TAG |
STORE |
80+ |
TEST AND TAG IN DATE, NEXT TEST DUE 23/11/21 |
N |
N |
N |
OBSERVATION |
EX02 |
NEAR COUNTER |
1 |
FAILED BATTERY TEST |
Y |
N |
N |
REPLACED WITH NEW |
PB4'S |
TV DISPLAY |
2 |
ADDITIONAL 2 × PB4S REQUIRED AT TV DISPLAY |
Y |
N |
N |
ADDED PB4S AND REMOVED POWERBOARD |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 12/09/2021 |
---|
| |
---|
| |