Partner NameBuilt Electrical Australia
StateVIC
Date of Visit15/03/2021
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54176
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICchadstone_t6

Location NameCHADSTONE
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DBT-6 1 Y P
3 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
57 Y P
59 Y P
61 Y P
63 Y P
65 Y P
67 Y P
68 Y P
69 Y P
71 Y P
73 Y P
94 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT-6 EM01 S Y Y Y P
EM02 S Y Y Y P
EM03 S Y Y Y P
EM04 R Y Y Y P
EM05 R Y Y Y P
EM06 R Y Y Y P
EM07 S Y Y Y P
EW08 R Y Y Y P
EM09 S Y Y Y P
EM10 S Y N Y F FAILED BATTERY TEST Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DBT-6 EX01 Y Y Y P
EX02 Y Y Y P
EX03 Y Y Y P
EX04 Y Y Y P
EX05 Y Y Y P
EX06 Y Y Y P
EX07 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
HI-BAY LIGHTS Y
SINGLE BATTEN T5 Y
LED STRIP LIGHT DISPLAY Y
EXIT LIGHT Y
RECESSED EMERGENCY Y
SURFACE MOUNT EMERGENCY Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 80+ TEST IN DATE, NEXT TEST DUE 19/NOV/2021 N N N OBSERVATION
RACK LIGHT BOX FRIDGES 3 × 2.4M, 2 × 3.6M, 1 × 3.0M FAILED TO ILLUMINATE/FAULTY N N N REPLACE WITH LED LINKABLE LIGHTS AT NEXT AUDIT
RACK LIGHT BOX SOUNDBARS/SMART HOME/SEASONAL/AIR TREATMENT/MASSAGE/TELEVISION 4 × 2.4M, 3 × 3.6M FAILED TO ILLUMINATE/FAULTY N N N WORKS TO BE CARRIED OUT ON APPROVED QUOTE, JOB 55641
EM10 BOH 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
PENDANT LIGHT KITCHENS 1 FAILED TO ILLUMINATE Y N N REPLACED LAMP
DOWNLIGHT OMEGA KITCHEN DISPLAY 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
28w/840 FLURO LAMP OMEGA KITCHEN DISPLAY 2 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
28W/840 FLURO LAMP DELONGHI KITCHEN 1 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
FISHER AND PAYKEL SIGN FISHER AND PAYKEL KITCHEN DISPLAY 1 FAULTY FITTING Y N N REPLACED WITH DAVIS LED LINKABLE
Site Status SelectorStore now fully compliant
Next Test Due in 6 months15/09/2021