Partner Name | Built Electrical QLD |
---|
State | QLD |
---|
Date of Visit | 02/03/2021 |
---|
Technician's Name | Brodie Robertson |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 54865 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in QLD | oxley |
---|
|
|
---|
Location Name | Oxley |
---|
| |
---|
HTML Block |
|
---|
Test Period | 6 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
RCD Details (6 Month) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
DB1 |
3 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
33 |
Y |
P |
|
|
|
34 |
Y |
P |
|
|
|
35 |
Y |
P |
|
|
|
36 |
Y |
P |
|
|
|
38 |
Y |
P |
|
|
|
40 |
Y |
P |
|
|
|
50 |
Y |
P |
|
|
|
52 |
N |
F |
Failed push button |
Hager c20 |
|
54 |
Y |
P |
|
|
|
56 |
Y |
P |
|
|
|
58 |
Y |
P |
|
|
|
60 |
Y |
P |
|
|
|
61 |
Y |
P |
|
|
|
62 |
Y |
P |
|
|
|
63 |
Y |
P |
|
|
|
64 |
Y |
P |
|
|
|
65 |
Y |
P |
|
|
|
67 |
Y |
P |
|
|
|
69 |
Y |
P |
|
|
|
71 |
Y |
P |
|
|
DB2 |
2 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
33 |
Y |
P |
|
|
|
34 |
Y |
P |
|
|
|
35 |
Y |
P |
|
|
DB3 |
1 |
Y |
P |
|
|
|
2 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
75 |
R |
Y |
Y |
Y |
P |
|
|
|
|
74 |
R |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
11 |
R |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
32 |
S |
Y |
Y |
Y |
P |
|
|
|
|
32a |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
20 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
35 |
S |
Y |
Y |
Y |
P |
|
|
|
|
41 |
R |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
40 |
S |
Y |
Y |
Y |
P |
|
|
|
Public Toilets |
42 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
Printers |
44 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
BOH near roller door |
21 |
S |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
72 |
R |
Y |
Y |
Y |
P |
|
|
|
|
73 |
S |
Y |
Y |
Y |
P |
|
|
|
|
91 |
R |
Y |
Y |
Y |
P |
|
|
|
|
92 |
R |
Y |
Y |
Y |
P |
|
|
|
|
93 |
R |
Y |
Y |
Y |
P |
|
|
|
|
94 |
R |
Y |
Y |
Y |
P |
|
|
|
|
95 |
R |
Y |
Y |
Y |
P |
|
|
|
|
96 |
R |
Y |
Y |
Y |
P |
|
|
|
|
97 |
R |
Y |
Y |
Y |
P |
|
|
|
|
98 |
R |
Y |
Y |
Y |
P |
|
|
|
|
99 |
R |
Y |
Y |
Y |
P |
|
|
|
|
100 |
R |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
N |
Y |
F |
Failed 90 minute test |
Y |
N |
|
70 |
Y |
Y |
Y |
P |
|
|
|
|
29 |
Y |
Y |
Y |
P |
|
|
|
|
33 |
Y |
Y |
Y |
P |
|
|
|
|
16 |
Y |
Y |
Y |
P |
|
|
|
|
17 |
Y |
Y |
Y |
P |
|
|
|
|
76 |
Y |
Y |
Y |
P |
|
|
|
|
77 |
Y |
Y |
Y |
P |
|
|
|
|
78 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
89 |
Y |
Y |
Y |
P |
|
|
|
|
90 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
UFO LED High Bay |
Y |
12v Dichroics |
Y |
36W Lamps in Poster Boxes |
Y |
18W Lamps in Poster Boxes |
Y |
LED Diffused Surface Fittings |
Y |
1 x 36W Diffused Battens |
Y |
|
---|
Are there any Warranty items needing to be repaired? | Yes |
---|
Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
Surface Mounted Emergency 15 |
Store |
1 |
Faulty battery |
Y |
N |
N |
|
Recessed Emergency 41 |
Kitchen |
1 |
Faulty battery |
Y |
N |
N |
|
Surface Mounted Emergency 18 |
Comms room |
1 |
Faulty battery |
Y |
N |
N |
|
Surface Mounted Emergency 20 |
Office store room |
1 |
Faulty battery |
Y |
N |
N |
|
Surface Mounted Emergency 42 |
Public toilet |
1 |
Faulty battery |
Y |
N |
N |
|
Recessed Emergency 11 |
Tv’s. Under mezzanine |
1 |
Faulty battery |
Y |
N |
N |
|
Surface Mounted Emergency 44 |
Next to exit in Printers |
1 |
Faulty battery |
Y |
N |
N |
|
Surface Mounted Emergency 21 |
BOH near roller door |
1 |
Faulty battery |
Y |
N |
N |
|
Exit 4 |
BOH |
1 |
Faulty battery |
Y |
N |
N |
|
RCBO # 52 |
DB1 |
1 |
Failed push button test |
Y |
N |
N |
|
EX/EM Layout |
Store |
1 |
Not accurate |
N |
N |
N |
New layout required for whole store. Listed on summary of repairs spreadsheet |
|
---|
Site Status Selector | QLD - Maintenance has been completed in accordance to ASS2293.2 and QD MP6.1. - Store now fully compliant |
---|
Next Test Due in 6 months | 01/09/2021 |
---|
| |
---|
| |