Partner NameBuilt Electrical QLD
StateQLD
Date of Visit02/03/2021
Technician's NameBrodie Robertson
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54865
EmailEmail hidden; Javascript is required.
The Good Guys Site in QLDoxley

Location NameOxley
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 3 Y P
5 Y P
13 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
38 Y P
40 Y P
50 Y P
52 N F Failed push button Hager c20
54 Y P
56 Y P
58 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
67 Y P
69 Y P
71 Y P
DB2 2 Y P
4 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
33 Y P
34 Y P
35 Y P
DB3 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
18 Y P
19 Y P
21 Y P
23 Y P
25 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
75 R Y Y Y P
74 R Y Y Y P
15 S Y N Y F Failed 90 minute test Y N
11 R Y N Y F Failed 90 minute test Y N
32 S Y Y Y P
32a S Y Y Y P
18 S Y N Y F Failed 90 minute test Y N
20 S Y N Y F Failed 90 minute test Y N
35 S Y Y Y P
41 R Y N Y F Failed 90 minute test Y N
40 S Y Y Y P
Public Toilets 42 S Y N Y F Failed 90 minute test Y N
Printers 44 S Y N Y F Failed 90 minute test Y N
BOH near roller door 21 S Y N Y F Failed 90 minute test Y N
72 R Y Y Y P
73 S Y Y Y P
91 R Y Y Y P
92 R Y Y Y P
93 R Y Y Y P
94 R Y Y Y P
95 R Y Y Y P
96 R Y Y Y P
97 R Y Y Y P
98 R Y Y Y P
99 R Y Y Y P
100 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P
2 Y Y Y P
4 Y N Y F Failed 90 minute test Y N
70 Y Y Y P
29 Y Y Y P
33 Y Y Y P
16 Y Y Y P
17 Y Y Y P
76 Y Y Y P
77 Y Y Y P
78 Y Y Y P
11 Y Y Y P
89 Y Y Y P
90 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
UFO LED High Bay Y
12v Dichroics Y
36W Lamps in Poster Boxes Y
18W Lamps in Poster Boxes Y
LED Diffused Surface Fittings Y
1 x 36W Diffused Battens Y
Are there any Warranty items needing to be repaired?Yes
Geotag photo(s)
  • Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Surface Mounted Emergency 15 Store 1 Faulty battery Y N N
Recessed Emergency 41 Kitchen 1 Faulty battery Y N N
Surface Mounted Emergency 18 Comms room 1 Faulty battery Y N N
Surface Mounted Emergency 20 Office store room 1 Faulty battery Y N N
Surface Mounted Emergency 42 Public toilet 1 Faulty battery Y N N
Recessed Emergency 11 Tv’s. Under mezzanine 1 Faulty battery Y N N
Surface Mounted Emergency 44 Next to exit in Printers 1 Faulty battery Y N N
Surface Mounted Emergency 21 BOH near roller door 1 Faulty battery Y N N
Exit 4 BOH 1 Faulty battery Y N N
RCBO # 52 DB1 1 Failed push button test Y N N
EX/EM Layout Store 1 Not accurate N N N New layout required for whole store. Listed on summary of repairs spreadsheet
Site Status SelectorQLD - Maintenance has been completed in accordance to ASS2293.2 and QD MP6.1. - Store now fully compliant
Next Test Due in 6 months01/09/2021