StateVIC
Date of Visit26/03/2021
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54190
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICpreston

Location NamePRESTON
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB2 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
45 Y P
Db4 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 Y P
21 Y P
23 Y P
25 Y P
27 Y P
29 Y P
31 Y P
24 Y P
26 Y P
28 Y P
30 Y P
32 Y P
34 Y P
36 Y P
Db3 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
16 Y P
Db1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
45 Y P
47 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
57 Y P
59 Y P
61 Y P
63 Y P
65 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
2 R Y Y Y P - Not maintained by Sturdie
4 R Y Y Y P - Not maintained by Sturdie
5 R Y Y Y P - Not maintained by Sturdie
6 R Y Y Y P - Not maintained by Sturdie
7 R Y Y Y P - Not maintained by Sturdie
8 R Y Y Y P - Not maintained by Sturdie
9 R Y Y Y P - Not maintained by Sturdie
11 R Y Y Y P - Not maintained by Sturdie
14 R Y Y Y P - Not maintained by Sturdie
16 R Y Y Y P - Not maintained by Sturdie
17 R Y Y Y P - Not maintained by Sturdie
18 R Y Y Y P - Not maintained by Sturdie
M 9 R Y Y Y P - Not maintained by Sturdie
20 R Y Y Y P - Not maintained by Sturdie
21 R Y Y Y P - Not maintained by Sturdie
22 R Y Y Y P - Not maintained by Sturdie
23 R Y Y Y P - Not maintained by Sturdie
24 R Y Y Y P - Not maintained by Sturdie
25 R Y Y Y P - Not maintained by Sturdie
26 R Y Y Y P - Not maintained by Sturdie
27 R Y Y Y P - Not maintained by Sturdie
28 R Y Y Y P - Not maintained by Sturdie
32 R Y Y Y P - Not maintained by Sturdie
33 R Y Y Y P - Not maintained by Sturdie
34 R Y Y Y P - Not maintained by Sturdie
36 R Y Y Y P - Not maintained by Sturdie
38 R Y Y Y P - Not maintained by Sturdie
39 R Y Y Y P - Not maintained by Sturdie
40 R Y Y Y P - Not maintained by Sturdie
42 R Y Y Y P - Not maintained by Sturdie
43 R Y Y Y P - Not maintained by Sturdie
44 R Y Y Y P - Not maintained by Sturdie
45 R Y Y Y P - Not maintained by Sturdie
46 R Y Y Y P - Not maintained by Sturdie
47 R Y Y Y P - Not maintained by Sturdie
48 R Y Y Y P - Not maintained by Sturdie
49 R Y Y Y P - Not maintained by Sturdie
51 R Y Y Y P - Not maintained by Sturdie
54 S Y Y Y P - Not maintained by Sturdie
55 S Y Y Y P - Not maintained by Sturdie
57 S Y Y Y P - Not maintained by Sturdie
58 S Y Y Y P - Not maintained by Sturdie
58 S Y Y Y P - Not maintained by Sturdie
60 S Y Y Y P - Not maintained by Sturdie
63 S Y Y Y P - Not maintained by Sturdie
64 S Y Y Y P - Not maintained by Sturdie
65 S Y Y Y P - Not maintained by Sturdie
66 S Y Y Y P - Not maintained by Sturdie
67 R Y Y Y P - Not maintained by Sturdie
69 R Y Y Y P - Not maintained by Sturdie
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
1 Y Y Y P - Not maintained by Sturdie
3 Y Y Y P - Not maintained by Sturdie
10 Y Y Y P - Not maintained by Sturdie
13 Y Y Y P - Not maintained by Sturdie
15 Y Y Y P - Not maintained by Sturdie
29 Y Y Y P - Not maintained by Sturdie
30 Y Y Y P - Not maintained by Sturdie
31 Y Y Y P - Not maintained by Sturdie
35 Y Y Y P - Not maintained by Sturdie
37 Y Y Y P - Not maintained by Sturdie
41 Y Y Y P - Not maintained by Sturdie
50 Y Y Y P - Not maintained by Sturdie
52 Y Y Y P - Not maintained by Sturdie
53 Y Y Y P - Not maintained by Sturdie
68 Y Y Y P - Not maintained by Sturdie
61 Y Y Y P - Not maintained by Sturdie
62 Y Y Y P - Not maintained by Sturdie
56 Y Y Y P - Not maintained by Sturdie
59 Y Y Y P - Not maintained by Sturdie
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Single Batten 15W Y
LED Double Batten 15W Y
LED Quad Lamps Y
LED Panel 4FT Y
LED Hi-Bay Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG REAR OFFICE RECEIVING/ ADMIN OFFICE NEAR COMMS ROOM 20 ITEMS OUT OF DATE AS OF 20 JAN 2021 N N N OBSERVATION - TEST AND TAG OF WHOLE STORE IN DATE , NEXT TEST DUE 20 JAN 2022, LISTED AREAS HAVE NOT BEEN TESTED AND ARE OUT OF DATE AS OF 20 JAN 2021
CEILING FALLING COMMS ROOM 1 CEILING DAMAGED N N N EMAILED COMPLIANCE TO MAKE THEM AWARE THAT THE CEILING IN COMMS ROOMS HAS SLIGHLY COLLAPSED AND IS NOT SECURE
EXIT/EMERGENCY STORE WIDE ALL EXIT AND EMERGENY LIGHTS NOT TESTED BY STURDIE AT TIME OF AUDIT N N N AS REQUESTED BY HEAD OFFICE, STURDIE WILL NOT MANAGE EXIT AND EMEGENCY LIGHTS FOR THE PRESTON STORE
Site Status SelectorStore now fully compliant
Next Test Due in 6 months26/09/2021