Partner NameBuilt Electrical QLD
StateQLD
Date of Visit30/03/2021
Technician's NameBrodie Rix
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54873
EmailEmail hidden; Javascript is required.
The Good Guys Site in QLDipswich

Location NameIpswich
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 2 Y P
4 Y P
6 Y P
7 Y P
8 Y P
10 Y P
19 Y P
29 Y P
31 Y P
37 Y P
DB2 33 Y P
34 Y P
35 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
48 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
66 Y P
67 Y P
68 Y P
70 Y P
72 Y P
73 Y P
74 Y P
76 Y P
77 Y P
79 Y P
81 Y P
83 Y P
DB3 6 Y P
37 Y P
39 Y P
45 Y P
47 Y P
49 Y P
51 Y P
53 Y P
55 Y P
57 Y P
71 Y P
73 Y P
74 Y P
75 Y P
76 Y P
77 Y P
78 Y P
79 Y P
80 Y P
81 Y P
82 Y P
83 Y P
84 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 1 S - 2 x 36w maintained Y Y Y P
2 S - 2 x 36w maintained Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S-light/em Y Y Y P
6 S-light/em Y Y Y P
7 S-fluro Y Y Y P
8 S-fluro Y Y Y P
9 S-fluro Y Y Y P
10 S-light/em Y Y Y P
11 S-light/em Y Y Y P
12 S-light/em Y Y Y P
13 S-light/em Y Y Y P
14 S-fluro Y Y Y P
DB 3 15 R Y Y Y P
16 S - maintained vb Y Y Y P
17 S - maintained Y Y Y P
18 S - maintained Y Y Y P
19 S - maintained Y Y Y P
20 S - maintained Y Y Y P
21 S - maintained Y Y Y P
22 S - maintained Y Y Y P
23 S Y Y Y P
24 S Y Y Y P
25 R Y N Y F Battery failed Y N
26 R Y Y Y P
27 S-fluro Y Y Y P
28 S-light/em Y Y Y P
DB 2 29 R Y Y Y P
30 R Y Y Y P
31 S-light/em Y Y Y P
32 R Y N Y F Battery failed Y N
33 R Y Y Y P
34 S-fluro Y Y Y P
35 S-fluro Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 1 1 Y Y Y P
2 Y Y Y P
3 Y N Y F Battery Failed Y N
4 Y Y Y P
5 Y Y N F Needs green running man Y N
6 Y Y Y P
DB 3 7-40m) Y Y Y P
8 Y Y Y P
9 (40m) Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
DB 2 13 Y N Y F Battery N N
14 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Metal Halide high bay lights Y
UFO LED high bay lights Y
2 x 36w diffused battens Y
2 x 36w caged battens Y
LED diffused batten Y
LED Downlights 70mm cut out Y
LED Downlights 90mm Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Ex3 Undercover car park entry fire door 1 Battery Failed Y N N Ladder access
Ex5 Undercover carpark 1 Green running man pointing right Y N N Ladder access
Em25 (recessed) Ground floor storage 1 Battery Failed Y N N Ladder access
Ex13 Top level 1 Battery Failed Y N N Ladder access
Em32 Top level female bathroom 1 Battery Failed Y N N Ladder access
Switchboard legends All switchboards 3 Outdated N TBA N Listed on fortnightly repairs summary
Logbook Office 1 Missing from site Y N N Sent new logbook to store
Site Status SelectorQLD - Maintenance has been completed in accordance to ASS2293.2 and QD MP6.1. - Store now fully compliant
Next Test Due in 6 months30/09/2021