Carry out push button test and record the results below.
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
RCD Details (6 Month)
Distribution Board No.
Circuit No.
Push Button (YorN)
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB-3
1
Y
P
DB-3
3
Y
P
DB-3
5
Y
P
DB-3
7
Y
P
DB-3
9
Y
P
DB-3
11
Y
P
DB-3
13
Y
P
DB-3
15
Y
P
DB-3
17
Y
P
DB-3
19
Y
P
DB-3
37
Y
P
DB-3
39
Y
P
DB-3
41
Y
P
DB-3
43
Y
P
DB-3
45
Y
P
DB-3
47
Y
P
DB-3
49
Y
P
DB-3
51
Y
P
DB-3
53
Y
P
DB-3
55
Y
P
DB-3
57
Y
P
DB-3
59
Y
P
DB-3
61
Y
P
DB-3
63
Y
P
DB-2
1
Y
P
DB-2
3
Y
P
DB-2
5
Y
P
DB-2
7
Y
P
DB-2
9
Y
P
DB-2
11
Y
P
DB-2
13
Y
P
DB-2
15
Y
P
DB-2
17
Y
P
DB-2
18
Y
P
DB-2
19
Y
P
DB-2
20
Y
P
DB-2
21
Y
P
DB-2
22
Y
P
DB-2
23
Y
P
DB-2
24
Y
P
DB-2
25
Y
P
DB-2
26
Y
P
DB-2
27
Y
P
DB-2
28
Y
P
DB-2
29
Y
P
DB-2
31
Y
P
DB-2
33
Y
P
DB-2
35
Y
P
DB-2
37
Y
P
DB-2
39
Y
P
DB-2
41
Y
P
DB-1
1
Y
P
DB-1
3
Y
P
DB-1
5
Y
P
DB-1
11
Y
P
DB-1
13
Y
P
DB-1
15
Y
P
DB-1
17
Y
P
DB-1
19
Y
P
DB-1
21
Y
P
DB-1
23
Y
P
DB-1
25
Y
P
DB-1
27
Y
P
DB-1
34
Y
P
DB-1
35
Y
P
DB-1
36
Y
P
DB-1
38
Y
P
DB-1
40
Y
P
DB-1
42
Y
P
DB-1
47
Y
P
Dyson suboard 1
2
Y
P
Dyson suboard 1
4
Y
P
Dyson suboard 2
2
Y
P
Dyson suboard 2
4
Y
P
Dyson suboard 2
6
Y
P
Dyson suboard 2
8
Y
P
Dyson suboard 2
10
Y
P
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB-3
2
S
Y
Y
Y
P
DB-3
5
S
Y
Y
Y
P
DB-3
6
S
Y
Y
Y
P
DB-3
7
S
Y
Y
Y
P
DB-3
8
S
Y
Y
Y
P
DB-3
9
S
Y
Y
Y
P
DB-3
10
S
Y
Y
Y
P
DB-3
15
S
Y
Y
Y
P
DB-3
16
R
Y
N
Y
F
FAILED BATTERY TEST
Y
N
DB-3
17
R
Y
Y
Y
P
DB-1
18
R
Y
Y
Y
P
DB-1
19
S
Y
Y
Y
P
DB-1
20
S
Y
Y
Y
P
DB-1
21
S
Y
Y
Y
P
DB-1
22
S
Y
Y
Y
P
DB-1
24
S
Y
Y
Y
P
DB-1
25
S
Y
Y
Y
P
DB-1
27
S
Y
N
Y
F
FAILED BATTERY TEST
Y
N
DB-1
28
S
Y
Y
Y
P
DB-2
31
R
Y
Y
Y
P
DB-2
32
R
Y
Y
Y
P
DB-2
33
S
Y
Y
Y
P
DB-2
34
S
Y
Y
Y
P
DB-2
37
R
Y
Y
Y
P
DB-2
38
R
Y
Y
Y
P
DB-2
39
R
Y
N
Y
F
FAILED BATTERY TEST
Y
N
DB-2
40
R
Y
Y
Y
P
DB-2
41
R
Y
Y
Y
P
DB-2
42
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB-3
1
Y
Y
Y
P
DB-3
3
Y
Y
Y
P
DB-3
4
Y
Y
Y
P
DB-3
11
Y
Y
Y
P
DB-3
12
Y
Y
Y
P
DB-3
13
Y
Y
Y
P
DB-3
14
Y
Y
Y
P
DB-1
23
Y
Y
Y
P
DB-1
26
Y
Y
Y
P
DB-1
29
Y
Y
Y
P
DB-2
30
Y
Y
Y
P
DB-2
35
Y
Y
Y
P
DB-2
36
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
Hi-Bay Lights
Y
LED Down Lights
Y
36W Diffuser Lights
Y
Single 58W/865 WP Fittings
Y
Are there any Warranty items needing to be repaired?
Yes
WARRANTY
Defect Item
Location of Item (on premises)
Quantity
Details of fault/problem
Manufacturer
Part Number
Repaired on Site
Comments
BLACK DAVIS HI-BAY
TELCO
1
FAILED TO ILLUMINATE
DAVIS
N
WAIT FOR SUPPLIER TO PROVIDE REPLACEMENT PART
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
RCBO CB01
DB-02
1
RCBO TRIPS WHEN RESET FOR THE FIRST TIME, WHEN RESET SECOND TIME WILL HOLD ON, INTERMITTENTLY NOT PASSING POWER
Y
N
N
REPLACED WITH NEW
RECESSED COMPACT FLURO FITTING
SHOWER ROOM STAFF AREA
1
FAILED TO ILLUMINATE
Y
N
N
REPLACED WITH 18W LAMP
EM16
FEMALE TOILET
1
FAILED BATTERY TEST
Y
N
N
REPLACED WITH NEW
EM27
TV AREA
1
FAILED BATTERY TEST
Y
N
N
REPLACED WITH NEW - SCISSOR LIFT REQUIRED FOR HIGH ACCESS WORKS
EM39
BOH REAR AISLE
1
FAILED BATTERY TEST
Y
N
N
REPLACED WITH NEW
WP SINGLE 36W FLURO FITTING
EXTERNAL FRONT CANOPY
1
FAILED TO ILLUMINATE
Y
N
N
REPLACED LAMP
CBUS UNIT
ABOVE DB-02 STAFF AREA
1
1 × CBUS UNIT FAULTY, AFFECT 1/3 OF DOWNLIGHTS IN TV AREA, SWITCHES FOR CBUS ADJACENT TO STAFF DOOR IN TV AREA DO NOT WORK. DOWNLIGHTS CAN ONLY BE TURNED ON MANUALLY AT WORKING CBUS UNITS UPSTAIRS
N
TBC
TBC
PREVIOUSLY QUOTED. PLEASE ADVISE IF YOU WOULD LIKE STURDIE TO PROVIDE QUOTE TO INVESTIGATE/REPAIR FAULT
SIGN FLOODLIGHTS
EXTERNAL FRONT
9
FAILED TO ILLUMINATE
N
TBC
TBC
PREVIOUSLY QUOTED. PLEASE ADVISE IF YOU WOULD LIKE STURDIE TO PROVIDE QUOTE TO INVESTIGATE/REPAIR FAULT
RACK LIGHT BOX
STORE
2.4M ×3 3.6M × 10
FAILED TO ILLUMINATE
N
N
N
WORKS TO BE CARRIED OUT ON APPROVED QUOTE 1759
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
12/10/2021
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.