Partner NameBuilt Electrical Australia
StateVIC
Date of Visit12/04/2021
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54199
EmailEmail hidden; Javascript is required.
The Good Guys Site in VIChoppers_crossing

Location NameHOPPERS CROSSING
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-3 1 Y P
DB-3 3 Y P
DB-3 5 Y P
DB-3 7 Y P
DB-3 9 Y P
DB-3 11 Y P
DB-3 13 Y P
DB-3 15 Y P
DB-3 17 Y P
DB-3 19 Y P
DB-3 37 Y P
DB-3 39 Y P
DB-3 41 Y P
DB-3 43 Y P
DB-3 45 Y P
DB-3 47 Y P
DB-3 49 Y P
DB-3 51 Y P
DB-3 53 Y P
DB-3 55 Y P
DB-3 57 Y P
DB-3 59 Y P
DB-3 61 Y P
DB-3 63 Y P
DB-2 1 Y P
DB-2 3 Y P
DB-2 5 Y P
DB-2 7 Y P
DB-2 9 Y P
DB-2 11 Y P
DB-2 13 Y P
DB-2 15 Y P
DB-2 17 Y P
DB-2 18 Y P
DB-2 19 Y P
DB-2 20 Y P
DB-2 21 Y P
DB-2 22 Y P
DB-2 23 Y P
DB-2 24 Y P
DB-2 25 Y P
DB-2 26 Y P
DB-2 27 Y P
DB-2 28 Y P
DB-2 29 Y P
DB-2 31 Y P
DB-2 33 Y P
DB-2 35 Y P
DB-2 37 Y P
DB-2 39 Y P
DB-2 41 Y P
DB-1 1 Y P
DB-1 3 Y P
DB-1 5 Y P
DB-1 11 Y P
DB-1 13 Y P
DB-1 15 Y P
DB-1 17 Y P
DB-1 19 Y P
DB-1 21 Y P
DB-1 23 Y P
DB-1 25 Y P
DB-1 27 Y P
DB-1 34 Y P
DB-1 35 Y P
DB-1 36 Y P
DB-1 38 Y P
DB-1 40 Y P
DB-1 42 Y P
DB-1 47 Y P
Dyson suboard 1 2 Y P
Dyson suboard 1 4 Y P
Dyson suboard 2 2 Y P
Dyson suboard 2 4 Y P
Dyson suboard 2 6 Y P
Dyson suboard 2 8 Y P
Dyson suboard 2 10 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-3 2 S Y Y Y P
DB-3 5 S Y Y Y P
DB-3 6 S Y Y Y P
DB-3 7 S Y Y Y P
DB-3 8 S Y Y Y P
DB-3 9 S Y Y Y P
DB-3 10 S Y Y Y P
DB-3 15 S Y Y Y P
DB-3 16 R Y N Y F FAILED BATTERY TEST Y N
DB-3 17 R Y Y Y P
DB-1 18 R Y Y Y P
DB-1 19 S Y Y Y P
DB-1 20 S Y Y Y P
DB-1 21 S Y Y Y P
DB-1 22 S Y Y Y P
DB-1 24 S Y Y Y P
DB-1 25 S Y Y Y P
DB-1 27 S Y N Y F FAILED BATTERY TEST Y N
DB-1 28 S Y Y Y P
DB-2 31 R Y Y Y P
DB-2 32 R Y Y Y P
DB-2 33 S Y Y Y P
DB-2 34 S Y Y Y P
DB-2 37 R Y Y Y P
DB-2 38 R Y Y Y P
DB-2 39 R Y N Y F FAILED BATTERY TEST Y N
DB-2 40 R Y Y Y P
DB-2 41 R Y Y Y P
DB-2 42 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-3 1 Y Y Y P
DB-3 3 Y Y Y P
DB-3 4 Y Y Y P
DB-3 11 Y Y Y P
DB-3 12 Y Y Y P
DB-3 13 Y Y Y P
DB-3 14 Y Y Y P
DB-1 23 Y Y Y P
DB-1 26 Y Y Y P
DB-1 29 Y Y Y P
DB-2 30 Y Y Y P
DB-2 35 Y Y Y P
DB-2 36 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi-Bay Lights Y
LED Down Lights Y
36W Diffuser Lights Y
Single 58W/865 WP Fittings Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
BLACK DAVIS HI-BAY TELCO 1 FAILED TO ILLUMINATE DAVIS N WAIT FOR SUPPLIER TO PROVIDE REPLACEMENT PART
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCBO CB01 DB-02 1 RCBO TRIPS WHEN RESET FOR THE FIRST TIME, WHEN RESET SECOND TIME WILL HOLD ON, INTERMITTENTLY NOT PASSING POWER Y N N REPLACED WITH NEW
RECESSED COMPACT FLURO FITTING SHOWER ROOM STAFF AREA 1 FAILED TO ILLUMINATE Y N N REPLACED WITH 18W LAMP
EM16 FEMALE TOILET 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
EM27 TV AREA 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR LIFT REQUIRED FOR HIGH ACCESS WORKS
EM39 BOH REAR AISLE 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW
WP SINGLE 36W FLURO FITTING EXTERNAL FRONT CANOPY 1 FAILED TO ILLUMINATE Y N N REPLACED LAMP
CBUS UNIT ABOVE DB-02 STAFF AREA 1 1 × CBUS UNIT FAULTY, AFFECT 1/3 OF DOWNLIGHTS IN TV AREA, SWITCHES FOR CBUS ADJACENT TO STAFF DOOR IN TV AREA DO NOT WORK. DOWNLIGHTS CAN ONLY BE TURNED ON MANUALLY AT WORKING CBUS UNITS UPSTAIRS N TBC TBC PREVIOUSLY QUOTED. PLEASE ADVISE IF YOU WOULD LIKE STURDIE TO PROVIDE QUOTE TO INVESTIGATE/REPAIR FAULT
SIGN FLOODLIGHTS EXTERNAL FRONT 9 FAILED TO ILLUMINATE N TBC TBC PREVIOUSLY QUOTED. PLEASE ADVISE IF YOU WOULD LIKE STURDIE TO PROVIDE QUOTE TO INVESTIGATE/REPAIR FAULT
RACK LIGHT BOX STORE 2.4M ×3 3.6M × 10 FAILED TO ILLUMINATE N N N WORKS TO BE CARRIED OUT ON APPROVED QUOTE 1759
Site Status SelectorStore now fully compliant
Next Test Due in 6 months12/10/2021