StateQLD
Date of Visit03/06/2021
Technician's NameScott Benson
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number54878
EmailEmail hidden; Javascript is required.
The Good Guys Site in QLDtownsville

Location NameTownsville
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB 23 Y P
MSB 25 Y P
MSB 26 Y P
MSB 27 Y P
MSB 28 Y P
MSB 76 Y P
MSB 78 Y P
MSB 78 Y P
MSB 79 Y P
MSB 80 Y P
MSB 81 Y P
MSB 82 Y P
MSB 83 Y P
MSB 84 Y P
MSB 85 Y P
MSB 86 Y P
MSB 87 Y P
MSB 88 Y P
MSB 89 Y P
MSB 90 Y P
MSB 91 Y P
MSB 92 Y P
MSB 93 Y P
MSB 94 Y P
DBC-11A 6 Y P
DBC-11A 8 Y P
DBC-11A 9 Y P
DBC-11A 10 Y P
DBC-11A 11 Y P
DBC-11A 12 Y P
DBC-11A 13 Y P
DBC-11A 14 Y P
DBC-11A 15 Y P
DBC-11A 16 Y P
DBC-11A 17 Y P
DBC-11A 18 Y P
DBC-11A 19 Y P
DBC-11A 20 Y P
DB-KITCHEN 1 Y P
DB-KITCHEN 2 Y P
DB-KITCHEN 3 Y P
DB-KITCHEN 4 Y P
DB-KITCHEN 5 Y P
DB-KITCHEN 6 Y P
DB-KITCHEN 7 Y P
DB-KITCHEN 8 Y P
DB-KITCHEN 9 Y P
DB-KITCHEN 10 Y P
DB-KITCHEN 11 Y P
DB-KITCHEN 12 Y P
DB-KITCHEN 13 Y P
DB-KITCHEN 14 Y P
DB-KITCHEN 15 Y P
DB-KITCHEN 16 Y P
DB-KITCHEN 17 Y P
DB-KITCHEN 18 Y P
DB-KITCHEN 19 Y P
DB-KITCHEN 20 Y P
DB-KITCHEN 21 Y P
DB-KITCHEN 22 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 2 R Y Y Y P
MSB 4 R Y Y Y P
MSB 5 R Y Y Y P
MSB 7 S 2 X 36w Y Y Y P
MSB 8 S 2 X 36w Y Y Y P
MSB 11 S 2 X 36w Y Y Y P
MSB 12 S 2 X 36w Y Y Y P
MSB 13 S 2 X 36w Y Y Y P
MSB 15 S 2 X 36w Y Y Y P
MSB 16 S 2 X 36w Y Y Y P
MSB 17 S 2 X 36w Y Y Y P
MSB 18 S 2 X 36w Y Y Y P
MSB 19 S 2 X 36w Y Y Y P
MSB 20 S 2 X 36w Y Y Y P
MSB 21 S 2 X 36w Y Y Y P
MSB 22 S 2 X 36w Y Y Y P
MSB 23 S 2 X 36w Y Y Y P
DBC-11A 24 S 2 X 36w Y Y Y P
DBC-11A 25 S 2 X 36w Y Y Y P
DBC-11A 26 S 2 X 36w Y Y Y P
DBC-11A 27 S 2 X 36w Y Y Y P
DBC-11A 28 S 2 X 36w Y Y Y P
DBC-11A 30 S 2 X 36w Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 Y Y Y P
MSB 3 Y Y Y P
MSB 6 Y Y Y P
MSB 9 Y Y Y P
MSB 10 Y Y Y P
MSB 14 Y Y Y P
DBC-11A 29 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
2 X 28w BATTEN- DIFFUSED Y
FLUORO DISPLAY CASE LIGHT Y
HIGH BAY FITTING Y
LED STRIP LIGHT Y
LED DOWNLIGHTS IN KITCHEN DISPLAY Y
OYSTER FITTINGS 32w Y
OYSTER FITTINGS LED 18W Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
High bay lights Store 9 Not Working Davis N To be replaced under warranty
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Hisense display Fridges 1 Display flashing Y N N Replaced driver
Delonghi display Kitchen 1 Display not illuminating Y N N Replaced driver
Westinghouse display Kitchen 1 Display not working Y N N Replaced driver
Schweigen Kitchen 1 Display not working Y N N Replaced driver
Oyster light Male toilet 1 Not working Y N N Replaced lamp and starter
Site Status SelectorQLD - Maintenance has been completed in accordance to ASS2293.2 and QD MP6.1. - Store now fully compliant
Next Test Due in 6 months02/12/2021