StateNSW
Date of Visit12/08/2021
Technician's NameGlenn Robinson
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58039
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWmaitland_east

Location NameMaitland East
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 CB2 Y P
DB1 CB4 Y P
DB1 CB6 Y P
DB1 CB8 Y P
DB1 CB10 Y P
DB1 CB14 Y P
DB1 CB30 Y P
DB1 CB31 Y P
DB1 CB32 Y P
DB1 CB34 Y P
DB1 CB36 Y P
DB1 CB38 Y P
DB1 CB40 Y P
DB1 CB42 Y P
DB1 CB42 Y P
DB1 CB44 Y P
DB1 CB46 Y P
DB1 CB48 Y P
DB1 CB50 Y P
DB1 CB52 Y P
DB1 CB54 Y P
DB1 CB56 Y P
DB1 CB58 Y P
DB1 CB60 Y P
DB2 CB2 Y P
DB2 CB4 Y P
DB2 CB6 Y P
DB2 CB8 Y P
DB2 CB38 Y P
DB2 CB39 Y P
DB2 CB40 Y P
DB2 CB41 Y P
DB2 CB42 Y P
DB2 CB43 Y P
DB2 CB45 Y P
DB2 CB47 Y P
DB2 CB49 Y P
DB3 CB5 Y P
DB3 CB7 Y P
DB3 CB8 Y P
DB3 CB9 Y P
DB3 CB11 Y P
DB3 CB12 Y P
DB3 CB13 Y P
DB3 CB14 Y P
DB3 CB16 Y P
DB3 CB18 Y P
DB3 CB21 Y P
DB3 CB25 Y P
DB3 CB33 Y P
DB4 CB1 Y P
DB4 CB2 Y P
DB4 CB3 Y P
DB4 CB4 Y P
DB4 CB5 Y P
DB4 CB6 Y P
DB4 CB7 Y P
DB4 CB8 Y P
DB4 CB9 Y P
DB4 CB10 Y P
DB4 CB11 Y P
DB4 CB12 Y P
DB4 CB13 Y P
DB4 CB14 Y P
DB4 CB15 Y P
DB4 CB16 Y P
DB4 CB17 Y P
DB4 CB18 Y P
DB4 CB19 Y P
DB4 CB21 Y P
DB4 CB23 Y P
DB4 CB25 Y P
DB4 CB27 Y P
DB4 CB29 Y P
DB4 CB31 Y P
DB4 CB33 Y P
DB4 CB35 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 2 S Y Y Y P
DB1 3 S Y Y Y P
DB1 5 S Y Y Y P
DB1 6 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 Y Y Y P
DB1 4 Y Y Y P
DB1 7 Y Y Y P
DB3 8 Y Y Y P
DB3 9 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
28W Bare Batten Y
28W Troffer Y
Circular Hi-Bay Y
Are there any Warranty items needing to be repaired?No
Site Status SelectorStore now fully compliant
Next Test Due in 6 months12/02/2022