Partner Name | Built Electrical Australia |
---|
State | NSW |
---|
Date of Visit | 11/08/2021 |
---|
Technician's Name | Peter Hay |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 58422 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in NSW | tempe |
---|
|
|
---|
Location Name | Tempe |
---|
| |
---|
HTML Block |
|
---|
Test Period | 12 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB2A CB42 |
S1 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S2 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S3 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S4 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S5 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S6 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S7 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S8 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S9 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S1o0 |
R |
Y |
N |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
S11 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S12 |
R |
Y |
Y |
Y |
P |
|
|
|
|
S13 |
R |
Y |
Y |
Y |
P |
|
|
|
|
EF1 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF2 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF3 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF4 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF5 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF6 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF7 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF8 |
4ft Twin Fluro |
Y |
Y |
Y |
P |
|
|
|
|
EF9 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF10 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF11 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF12 |
4ft Twin Fluoro |
N |
|
Y |
F |
Failed 90 Min Test |
Y |
N |
|
EF13 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF14 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF15 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF16 |
4ft Twin Fluoro |
N |
Y |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
EF17 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF18 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF19 |
4ft Twin Fluoro |
N |
Y |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
EF20 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF21 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
EF22 |
4ft Twin Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
DB2A-CB42 |
EX1 |
Y |
Y |
Y |
P |
|
|
|
|
EX2 |
Y |
Y |
Y |
P |
|
|
|
|
EX3 |
Y |
Y |
Y |
P |
|
|
|
|
EX4 |
Y |
Y |
Y |
P |
|
|
|
|
EX5 |
Y |
Y |
Y |
P |
|
|
|
|
EX6 |
Y |
Y |
Y |
P |
|
|
|
|
EX7 |
Y |
Y |
Y |
P |
|
|
|
|
EX8 |
Y |
Y |
Y |
P |
|
|
|
|
EX9 |
Y |
Y |
Y |
P |
|
|
|
|
EX10 |
Y |
Y |
Y |
P |
|
|
|
|
EX11 |
Y |
Y |
Y |
P |
|
|
|
|
EX12 |
Y |
Y |
Y |
P |
|
|
|
|
EX13 |
Y |
Y |
Y |
P |
|
|
|
|
EX14 |
Y |
Y |
Y |
P |
|
|
|
|
EX15 |
Y |
Y |
Y |
P |
|
|
|
|
EX16 |
Y |
Y |
Y |
P |
|
|
|
|
EX17 |
Y |
Y |
Y |
P |
|
|
|
|
EX18 |
Y |
Y |
Y |
P |
|
|
|
|
EX19 |
Y |
Y |
Y |
P |
|
|
|
|
EX20 |
Y |
Y |
Y |
P |
|
|
|
|
EX21 |
Y |
Y |
Y |
P |
|
|
|
|
EX22 |
Y |
Y |
Y |
P |
|
|
|
|
EX23 |
Y |
Y |
Y |
P |
|
|
|
|
EX24 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
LED High Bays 150W |
Y |
LED Downlight 210mm 31W S9075DP WH |
Y |
Ledline 4ft 40W SLD4000CW |
Y |
LED Strip Display Signs DC24V |
Y |
LED Downlight 11W S9071CP WH |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
High bay light |
Adj Hisense fridges |
1 |
Low light output |
Y |
N |
N |
Replaced fitting |
LED Driver |
TV Wall |
1 |
Faulty driver |
Y |
N |
N |
Replaced driver |
Recessed Emergency Light |
S1, S2, S3, S4, S8, S9, S10 |
7 |
Failed 90 Min Test |
Y |
N |
N |
Replaced fittings |
Emergency Batten |
EF12, EF16, EF19 |
3 |
Failed 90 Min Test |
Y |
N |
N |
Scissor required, replaced with surface mount emergency lights |
LED Strip Light |
Fridge Section |
1 |
Damaged |
N |
N |
TBA |
Further investigation required. If repairs are required, please send through work request. |
LED Strip Connection |
TV Wall |
1 |
Connection intermittent |
N |
N |
TBA |
Further investigation required. If repairs are required, please send through work request. |
Display Light |
Adjacent store entry |
2 |
Asko and Fisher Paykel signs not illuminated |
N |
N |
TBA |
Fault finding required. If repairs are required, please send through work request. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 11/02/2022 |
---|
| |
---|
| |