Partner NameBuilt Electrical Australia
StateNSW
Date of Visit11/11/21
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58430
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWwarrawong

Location NameWarrawong
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB GEN L&P 19 Y P
20 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
46 Y F Failed push button test Y
47 Y F Failed push button test Y
55 Y P
56 Y P
57 Y F Failed push button test Y
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
66 Y P
67 Y P
71 Y F Failed push button test Y
72 Y F Failed push button test Y
DB1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y F Failed push button test Y
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
31 Y P
DB2 6 Y F Failed push button test Y
8 Y P
9 Y P
10 Y F Failed push button test Y
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
23 Y P
25 Y P
27 Y P
29 Y P
31 Y P
33 Y P
35 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 S Y Y Y P
2 S Y Y Y P
Laptops 3 S Y Y Y F Failed 90 Min Test Y N
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
Westinghouse island bench 9 S Y Y Y F Failed 90 Min Test Y N
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
14 S Y Y Y P
15 S Y Y Y P
Tradefloor rear exit door right 16 S Y Y Y F Failed 90 Min Test Y N
17 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
Boh adj exit door 20 S Y Y Y F Failed 90 Min Tes Y N
21 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y F Failed 90 Min Test Y N
30 R Y Y Y P
33 R Y Y Y P
35 R Y Y Y P
38 R Y Y Y P
39 R Y Y Y P
40 R Y Y Y P
41 R Y Y Y P
44 R Y Y Y P
45 R Y Y Y P
Boh adj hold room 46 S Y Y Y F Failed 90 Min Test Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 Y Y Y P
2 Y Y Y P
3 Y N Y F Failed 90 Min Test Y N
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y N Y F Failed 90 Min Test Y N
9 Y N Y F Failed 90 Min Test Y N
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi Bays Halo Globe Y
50mm LED Downlight Y
Fluoro Pelmet Lights Y
200mm Downlight Folded Fluoro Twin Globe Y
2x30W Caged Fluoro Fitting Y
1x30W Diffused Fluoro Fitting Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Schneider 20A Rcbo CB15 Db1 1 Failed push button test Y N N Replaced
Dinsafe 20A Rcbo CB 6 & 11 Db2 2 Failed push button test Y N N Replaced
Elq 20A Rcbos CB 46, 47, 57, 71 & 72 Msb 5 Failed push button test Y N N Replaced
Exit Light 03, 08 & 09 3 Failed 90 Min Test Y N N Replaced fittings
Recessed Emergency Light 25 1 Failed 90 Min Test Y N N Replaced fitting
Surface Mount Emergency Light 03, 09, 16, 20 & 27 5 Failed 90 Min Test Y N N Replaced fittings, scissor lift used
Wall bay Light Boxes Trading floor 15 Partial or full lighting faulty N N N FYI only
Blue Led Strip Tv Wall 3 Partially illuminated N N N FYI only
Weber Light Box FOS 1 Not illuminated N N N FYI only
Asko light box Store entry 2 Downlight faulty N N N FYI
Smeg kitchen display Left/middle trading floor 1 Downlight faulty Y N N Replaced
Westinghouse island bench Left/middle trading floor 1 Lamp faulty Y N N Replaced
Bosch kitchen display Store entry 1 Downlight faulty Y N N Replaced
Accessories wall bay fos Front of store 1 Downlight faulty Y N N Replaced
Site Status SelectorCompleted but with repairs required
Next Test Due in 6 months18/02/2022