Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB G07A 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 Y P
20 Y P
21 Y P
23 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
31 Y P
33 Y P
35 Y P
DB G07 3 Y P
12 Y P
23 Y P
24 Y P
34 Y P
35 Y P
36 Y P
41 Y P
43 Y P
44 Y P
48 Y P
DB G07 12 Y P
24 Y P
37 Y P
38 Y P
39 Y P
40 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
E1 S N Y Y F Failed lamp Y N
E2 S N Y Y F Failed lamp Y N
E3 S N Y Y F Failed lamp Y N
E4 S Y Y Y P
E5 S Y Y Y P
E6 S Y Y Y P
E7 S Y Y Y P
E8 S Y Y Y F Not in test mode Y N
E9 S Y Y Y P
E10 S Y Y Y P
E11 S Y Y Y P
E12 S N Y Y F Failed lamps Y N
E13 S Y N Y F Failed 90 Min Test Y N
E14 S N Y Y F Failed Lamps Y N
E15 S N Y Y F Failed lamps Y N
E16 S N Y Y F Failed lamps Y N
E17 S Y Y Y P
E18 S N Y Y F Failed Lamp Y N
S1 R Y Y Y P
S2 R Y Y Y P
S3 R Y Y Y P
S4 R Y Y Y P
S5 R Y Y Y P
S6 R Y Y Y P
S7 R Y Y Y P
S8 R Y Y Y P
S9 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Ex1 Y Y Y P
Ex2 Y Y Y P
Ex3 Y Y N F Not in test mode Y N
Ex4 Y Y Y P
Ex5 Y Y Y P
Ex6 Y Y Y P
Ex7 Y Y Y F Partially obstructed Need relocation. Y N
Ex8 Y Y Y P
Ex9 Y Y Y P
Ex10 Y Y Y P
Ex11 Y Y Y P
Ex12 Y Y Y P
Ex13 Y Y Y F Wrong decal Y N
Ex14 Y Y Y P
Ex15 Y Y Y P
Ex16 Y Y Y P
Ex17 Y N Y F Remove from fire pipe. Suspend from slab to appropriate height. Y N
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
High Bays Halo Globe Y
50mm LED Downlight Y
T8 Converted to 28W Fluoro Fitting Y
Rectangle LED Wall Light Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency Batten 01, 02, 03, 12, 14, 15, 16, 17, 18 12 Failed lamps Y N N Replaced 12 x lamps and 12 x starters
Emergency Batten 13 1 Failed 90 Min Test Y N N Replaced fitting, scissor lift required
Exit Light 03 1 Failed 90 Min Test & Not in test mode Y N N Replaced fitting and wired into test switch
Emergency Light 08 1 Not in test mode Y N N Traced fault and re-wired into test switch
Exit Light 07 1 Obstructed Y N N Relocated
Exit Light 17 1 Connected to fire pipe Y N N Removed and relocated
Exit Light 13 1 Incorrect decal Y N N Replaced using spare
Emergency Light Test Switch Switchboards 2 Faulty Y N N Replaced units
Next Test Due in 6 months12/04/2022