Carry out push button test and record the results below.
RCD Details (Initial/12 Months)
Distribution Board No.
Circuit No.
Push Button (YorN)
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
EDB-
4
Y
P
6
Y
P
8
Y
P
10
Y
P
12
Y
P
14
Y
P
16
Y
P
18
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
37
Y
P
38
Y
P
39
Y
P
40
Y
P
41
Y
P
42
Y
P
43
Y
P
44
Y
P
45
Y
P
46
Y
P
47
Y
P
48
Y
P
49
Y
P
50
Y
P
51
Y
P
52
Y
P
53
Y
P
55
Y
P
56
Y
P
57
Y
P
58
Y
P
59
Y
P
60
Y
P
Db-1
4
Y
P
6
Y
P
8
Y
P
9
Y
P
10
Y
P
11
Y
P
12
Y
P
13
Y
P
14
Y
P
15
Y
P
16
Y
P
17
Y
P
18
Y
P
19
Y
P
20
Y
P
21
Y
P
22
Y
P
23
Y
P
25
Y
P
27
Y
P
29
Y
P
31
Y
P
33
Y
P
35
Y
P
37
Y
P
EDB-5
2
Y
P
4
Y
P
7
Y
P
8
Y
P
9
Y
P
10
Y
P
11
Y
P
12
Y
P
13
Y
P
14
Y
P
16
Y
P
17
Y
P
19
Y
P
22
Y
P
24
Y
P
26
Y
P
28
Y
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB1 Extension
1
R
Y
F
Y
F
Failed Battery Test
Y
N
2
R
Y
Y
Y
P
3
R
Y
Y
Y
P
4
R
Y
Y
Y
P
5
R
Y
Y
Y
P
6
R
Y
Y
Y
P
7
R
Y
Y
Y
P
8
R
Y
Y
Y
P
9
R
Y
Y
Y
P
10
R
Y
Y
Y
P
11
R
Y
Y
Y
P
12
R
Y
Y
Y
P
13
R
Y
Y
Y
P
14
R
Y
Y
Y
P
15
R
Y
F
Y
F
Failed Battery Test
Y
N
16
R
Y
Y
Y
P
18
R
Y
Y
Y
P
19
R
Y
F
Y
F
Failed Battery Test
Y
N
20
S
Y
Y
Y
P
21
S
Y
Y
Y
P
24
R
Y
Y
Y
P
25
R
Y
Y
Y
P
26
R
Y
Y
Y
P
27
R
Y
Y
Y
P
28
S
Y
Y
Y
P
99
R
Y
Y
Y
P
105
R
Y
Y
Y
P
106
R
Y
Y
Y
P
107
R
Y
Y
Y
P
108
R
Y
Y
Y
P
109
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB1 Extension
1
Y
Y
Y
P
2
Y
Y
Y
P
3
Y
Y
Y
P
17
Y
Y
Y
P
22
Y
Y
Y
P
23
Y
Y
Y
P
29
Y
Y
Y
P
31
Y
Y
Y
P
32
Y
Y
Y
P
95
Y
Y
Y
P
96
Y
Y
Y
P
97
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
T5 Double Fluorescent Lights
Y
Single 36W Fluorescent Lights
Y
70mm Downlights
Y
Exit Lights
Y
Emergency Lights
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
External Flood Lights
Roof Top Car Park
2
Failed to illuminate
N
TBA
TBA
Due to Covid lockdown, general lighting repairs have been postponed until next audit
Downlights
Smarthome
4
Failed to illuminate
N
TBA
TBA
Due to Covid lockdown, general lighting repairs have been postponed until next audit
External Wall Lights
Rooftop Carpark
2
Failed to illuminate
N
TBA
TBA
Due to Covid lockdown, general lighting repairs have been postponed until next audit
LED Panel Lights
Throughout Sore (+ Upstairs)
TBC
Discolored
N
N
N
Sturdie are currently in discussions with the supplier. Supplier rep to meet Sturdie on site after lockdown. Or otherwise, if required sooner, please provide approval via email to maintenance
Light Display Lamps
Sound Bars
6
Failed to illuminate
Y
N
N
Replaced with LED linkable lights
Light Display Lamps
Audio Systems
2
Failed to illuminate
Y
N
N
Replaced with LED linkable lights
EM01
Radios
1
Failed Battery Test
Y
N
N
Replaced with new
EM15
TV's
1
Failed Battery Test
Y
N
N
Replaced with new
EM19
Lunch Room
1
Failed Battery Test
Y
N
N
Replaced with new
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
13/04/2022
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.