Partner NameBuilt Services
StateNSW
Date of Visit07/10/2021
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58426
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWpenrith

Location NamePenrith
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB01 9 Y P
16 Y P
67 Y P
68 Y P
69 Y P
70 Y P
71 Y P
76 Y P
77 Y P
78 Y P
79 Y P
80 Y P
81 Y P
82 Y P
83 Y P
84 Y P
85 Y P
86 Y P
87 Y P
88 Y P
89 Y P
90 Y P
91 Y P
92 Y P
93 Y P
94 Y P
95 Y P
96 Y P
97 Y P
98 Y P
99 Y P
100 Y P
101 Y P
102 Y P
103 Y P
104 Y P
111 Y P
112 Y P
113 Y P
114 Y P
115 Y P
116 Y P
117 Y P
118 Y P
119 Y P
120 Y P
121 Y P
122 Y P
123 Y P
124 Y P
125 Y P
127 Y P
128 Y P
129 Y P
130 Y P
131 Y P
DB01A 1 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
19 Y P
21 Y P
31 Y P
33 Y P
34 Y P
35 Y P
36 Y P
41 Y P
42 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
EM1 R Y Y Y P
EM2 R Y N Y F Failed 90 Min Test Y N
EM3 R Y Y Y P
EM4 R Y Y Y P
EM5 R Y Y Y P
EM6 R Y Y Y P
EM7 R Y Y Y P
EM8 R Y Y Y P
EM9 R Y Y Y P
EM10 R Y Y Y P
EM11 R Y Y Y P
EM12 R Y Y Y P
EM13 Floodlight Y Y Y P
EM14 2ft Twin Fluoro Y N Y F Failed 90 Min Test and Not in test mode Y N
EM15 2ft Twin Fluoro Y Y Y P
EM16 R Y Y Y P
EM17 R Y Y Y P
EM18 4ft Twin Fluoro Y N Y F Failed 90 Min Test Y N
EM19 R Y Y Y P
EM20 S Y Y Y P
EM21 R Y Y Y P
EM22 S Y Y Y P
EM23 4ft Twin Fluoro Y N Y F Failed 90 Min Test Y N
EM24 4ft Twin Fluoro N N N F New fitting required Y N
EM25 S N N N F Failed 90 Min Test Y N
EM26 S N N N F Failed 90 Min Test Y N
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB01 - Test Switch EX1 Y Y Y P
EX2 Y N Y F Failed 90 Min Test Y N
EX6 Y Y Y P
EX12 Y N Y F Failed 90 Min Test Y N
EX36 Y Y Y P
DB01A - Test Switch EX3 Y Y Y P
EX4 Y Y Y P
EX5 Y Y Y P
EX7 Y Y Y P
EX8 Y N Y F Failed 90 Min Test Y N
EX9 Y Y Y P
EX10 Y Y Y P
EX11 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
4ft Twin Fluoro 840 Y
2ft Twin Fluoro 840 Y
Highbays LED 150W Y
35W 865 T5 Single Lights Shop Y
4ft Light x 3 Lamps 36W 860 Y
4ft Twin Lights 840 Y
4ft Twin T5 28W Lamps 865 Y
2 x 3ft LED Strips LPF-40D-12 Y
Entry Circular Long Life ES20W 865 Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Exit Light 02, 08 & 12 3 Failed 90 Min Test Y N N Replaced fiittings
2ft Fluoro Emergency Light 14 1 Not in test mode, failed 90 min test Y N N New emergency active cable run and replaced fitting
4ft Fluoro Emergency Light 18, 24 & 23 3 Not in test mode, failed 90 min test Y N N New emergency active cable run and replaced fitting
Surface Mount Emergency Light 25 & 26 2 Failed 90 Min Test Y N N Replaced fittings, scissor lift required
Recessed Emergency Light 2 1 Failed 90 Min Test Y N N Replaced fitting
Circuit Dyson Display 1 Circuit tripping, Dyson to rectify N N N FYI only
Light Boxes Wall Bays 2 Not illuminated N N N No repair required as per Caitlin
Display Light Westinghouse 1 Not illuminated N N N No repair required as per Caitlin
4ft Batten Light Manager's Office 1 Not illuminated N N N No repair required as per Caitlin
LED Strip Light TV Wall 2 Not illuminated N N N No repair required as per Caitlin
Fluoro Troffer Omega Display 1 Partially illuminated N N N No repair required as per Caitlin
Suspended Fluoro Troffer Throughout store Numerous Poorly illuminated N N N No repair required as per Caitlin
Recessed Downlight Front of store 1 Not illuminated N N N No repair required as per Caitlin
Switchboard Schedule Switchboard 1 Not accurate N N N To be re-typed and taken back to store
Site Folder Office 1 Not found Y N N New folder sent to site
Next Test Due in 6 months07/04/2022