Partner Name | Rodda Electrical |
---|
State | SA |
---|
Date of Visit | 14/10/2021 |
---|
Technician's Name | Matt Rodda |
---|
Which Company are you working for? | Sturdie Trade Services |
---|
Sturdie Job Number | 58475 |
---|
Email | Email hidden; Javascript is required. |
---|
The Good Guys Site in SA | cavan_warehouse |
---|
|
|
---|
Location Name | Cavan Warehouse |
---|
| |
---|
HTML Block |
|
---|
Test Period | 12 Monthly (90 minutes) |
---|
Push Button Test | - Carry out push button test for correct operation
|
---|
Carry out push button test for correct operation | |
---|
HTML Block |
|
---|
Carry out test with RCD Tester | Carry out push button test and record the results below. |
---|
RCD Details (Initial/12 Months) | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
Unit 1 |
1 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
48 |
Y |
P |
|
|
unit 2 db |
2 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
40 |
Y |
P |
|
|
|
---|
THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
---|
SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
---|
Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
---|
Timers | - Check timers for correct operation and timing
|
---|
Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
---|
HTML Block |
|
---|
EMERGENCY LIGHTS | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
1 |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
N |
N |
N |
F |
Failed 90 minute test |
Y |
N |
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
N |
N |
N |
F |
Did not illuminate |
Y |
N |
|
---|
HTML Block |
|
---|
EXIT LIGHTS | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
|
1 |
Y |
N |
N |
F |
Failed 90 minute |
Y |
N |
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
---|
SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
---|
General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
---|
HTML Block |
|
---|
General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
---|
HTML Block |
|
---|
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
---|
Lighting Report | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
Highbay lights |
Y |
2 x 36w bare batten |
Y |
Batten holders |
Y |
10w LED downlights |
Y |
|
---|
Are there any Warranty items needing to be repaired? | No |
---|
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
EM/EX Plan |
Missing from site |
1 |
EM/EX Plan missing from site |
N |
N |
N |
Site closing down |
Exhaust fan |
Upstairs kitchen |
1 |
Exhaust fan not working |
Y |
N |
N |
Replaced with new |
Exhaust fan |
Upstairs toilet |
1 |
Exhaust fan not worksin |
Y |
N |
N |
Replaced with new |
Lights batten holder |
Upstairs toilet/shower |
2 |
No lamps |
Y |
N |
N |
Replaced with new |
Downlights |
Upstairs open room |
6 |
Downlights not working |
Y |
N |
N |
Replaced with new |
Downlight |
Downstairs office |
1 |
Downlight not working |
Y |
N |
N |
Replaced with new |
Exhaust fan |
Warehouse female toilet |
1 |
Exhaust fan not working |
Y |
N |
N |
Replaced with new |
Exit light |
Downstairs office |
1 |
Light does not illuminate at all. Possibly disconnected fitting |
Y |
N |
N |
Replaced with new |
Surface Mounted Twin fluoro light, possible emergency |
Main warehouse floor |
1 |
Failed 90 minute test |
Y |
N |
N |
Replaced lamps and starters. 10m high ceiling, Knuckle boom required |
Surface Mounted Emergency light |
Main warehouse |
1 |
Light did not illuminate during 90 minute test |
Y |
N |
N |
Connected fitting to emergency test switch facility. |
|
---|
Site Status Selector | Store now fully compliant |
---|
Next Test Due in 6 months | 14/04/2022 |
---|
| |
---|
| |