StateNSW
Date of Visit20/10/2021
Technician's NameJames Graham
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58296
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcoffs_harbour

Location NameCoffs Harbour
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 14 Y P
16 Y P
18 Y P
44 Y P
46 Y P
48 Y P
50 Y P
52 Y P
54 Y P
56 Y P
58 Y P
60 Y P
62 Y P
64 Y P
66 Y P
68 Y P
70 Y P
72 Y P
DB2 2 Y P
4 Y P
6 Y P
8 Y P
12 Y P
16 Y P
18 Y P
22 Y P
DB3 2 Y P
4 Y P
6 Y P
8 Y P
10 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y F Faulty Y
17 Y P
18 Y P
20 Y P
22 Y P
23 Y P
24 Y P
DB4 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
20 Y P
21 Y P
22 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 2 S Y Y Y P
3 S Y Y Y P
5 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
17 S Y Y Y P
DB2 18 R Y Y Y P
20 R Y Y Y P
21 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
DB1 25 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB1 1 Y Y Y P
4 Y Y Y P
6 Y Y Y P
11 Y Y Y P
14 Y Y Y P
15 Y Y Y P
16 Y Y Y P
26 Y Y Y P
DB2 19 Y Y Y P
24 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED Hibay Y
LED Panel Lights Y
LED Battens Y
36W Battens Y
18W Battens Y
PL Lamp Downlights Y
18W Recessed LED Downlights Y
Floodlights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
58W Lamp Shop floor 19 Not illuminated Y N N Replaced lamps
42W Lamp Shop floor 6 Not illuminated Y N N Replaced lamps
Fluoro Lamp Shop floor 10 Not illuminated Y N N Replaced lamps
Linear Fluoro Lamp T8 Shop floor 3 Not illuminated Y N N Replaced lamps
Fluorescent Starter Switches 4W-65W Shop floor 7 Faulty Y N N Replaced starters for lamps
TGG Front Sign Front of store 1 Half of the sign isn't working N Y TBA Repairs added to fortnightly summary report
18W-20W Ballast Shop floor 2 Not illuminated N N TBA Repairs added to fortnightly summary report
36W-40W Ballast Shop floor 3 Not illuminated N N TBA Repairs added to fortnightly summary report
Ballast EC58/65 Shop floor 4 Not illumuniated N N TBA Repairs added to fortnightly summary report
RCD #16 DB3 1 Faulty Y N N Replaced RCBO
Site Status SelectorStore now fully compliant
Next Test Due in 6 months20/04/2022