Carry out push button test and record the results below.
RCD Details (Initial/12 Months)
Distribution Board No.
Circuit No.
Push Button (YorN)
Pass / Fail (PorF)
Fault?
Repaired on Site (YorN)
DB-T11
2
Y
P
4
Y
P
6
Y
P
8
Y
P
9
Y
P
10
Y
P
11
Y
P
12
Y
P
13
Y
P
14
Y
P
15
Y
P
17
Y
P
19
Y
P
21
Y
P
22
Y
P
23
Y
P
24
Y
P
25
Y
P
26
Y
P
27
Y
P
28
Y
P
29
Y
P
30
Y
P
31
Y
P
32
Y
P
33
Y
P
34
Y
P
35
Y
P
36
Y
P
37
Y
P
38
Y
P
39
Y
P
40
Y
P
41
Y
P
42
Y
P
44
Y
P
46
Y
P
48
Y
P
50
Y
P
52
Y
P
54
Y
P
55
Y
P
56
Y
P
57
Y
P
58
Y
P
59
Y
P
60
Y
P
61
Y
P
62
Y
P
63
Y
P
64
Y
P
65
Y
P
66
Y
P
67
Y
P
68
Y
P
70
Y
P
71
Y
P
72
Y
P
73
Y
P
74
Y
P
75
Y
P
76
Y
P
78
Y
P
80
Y
P
82
Y
P
84
Y
P
THERMOGRAPHIC TEST RESULTS
THERMOGRAPHIC TEST RESULTS
SF43 Exit/Emergency
SF43 EXIT/EMERGENCY LIGHTING
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
Check there has been no power interruption for at least 16 hours prior to test
Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
Check timers for correct operation and timing
Switched Socket Outlets
Carry out visual check on SSOs for signs of misuse, blackening or deterioration
Check and report any outlets with multiple power boards overloading
Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No.
ID No.
Surface mounted or recessed? (SorR)
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB T11
1
R
Y
Y
Y
P
2
R
Y
Y
Y
P
3
R
Y
Y
Y
P
4
R
Y
Y
Y
P
5
R
Y
Y
Y
P
6
R
Y
Y
Y
P
7
R
Y
Y
Y
P
8
R
Y
Y
Y
P
9
R
Y
Y
Y
P
10
R
Y
Y
Y
P
11
R
Y
Y
Y
P
12
R
Y
Y
Y
P
13
R
Y
Y
Y
P
HTML Block
EXIT LIGHTS
Distribution Board No.
ID No.
Lamp OK? (YorN)
Battery OK? (YorN)
Condition OK? (YorN)
Pass / Fail (PorF)
Fault
Repaired on Site (YorN)
Under Warranty (YorN)
DB T11
1
Y
Y
Y
P
2
Y
Y
Y
P
3
Y
Y
Y
P
4
Y
Y
Y
P
5
Y
Y
Y
P
6
Y
Y
Y
P
7
Y
Y
Y
P
20
Y
Y
Y
P
SF44 General Lighting & Works
SF44 GENERAL LIGHTING & WORKS
General Checklist
Check correct operation of all luminaries
Report on any faulty luminaries/control gear
Provide costing to repair/replace
HTML Block
General Operation/Additional items
Check with Store Manager to ensure there are no other issues
Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au
Yes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten)
Existing (YorN)
36W Double Batten
Y
LED Troffer Lights
Y
Halogen Downlights
Y
Compact Fluorescent Lights
Y
Exit Lights
Y
Emergency Lights
Y
Are there any Warranty items needing to be repaired?
No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item
Location of Item (on premises)
Quantity
Details of fault /problem
Repaired on Site? (YorN)
Quote to be sent? (YorN)
To return to Site
Comments
Extension Lead
Falcon TV's
3
Used as power droppers
N
TBA
TBA
Extension lead used for dropper with no ceiling support. Please advise if Sturdie are to provide a quote to install power dropper
Extension Lead
Sony TV
1
Used as power dropper
N
TBA
TBA
Extension lead used for dropper with no ceiling support. Please advise if Sturdie are to provide a quote to install power dropper
Extension Lead
LG TV
1
Used as power dropper
N
TBA
TBA
Extension lead used for dropper with no ceiling support. Please advise if Sturdie are to provide a quote to install power dropper
Power Dropper
Bosch Washing Machines
1
Incorrect position
N
TBA
TBA
Dropper to be re- located or ceiling support hooks to hang cable in correct position. Scissor lift required. Please advise if Sturdie are to provide a quote
Display Lights
Printing Supplies
1
Failed to illuminate
N
TBA
TBA
To be replaced with LED linkable lights. Please advise if Sturdie are to provide a quote
Display Lights
TV Brackets
1
Failed to illuminate
N
TBA
TBA
To be replaced with LED linkable lights. Please advise if Sturdie are to provide a quote
Display Lights
Sound Bars
1
Failed to illuminate
N
TBA
TBA
To be replaced with LED linkable lights. Please advise if Sturdie are to provide a quote
Display Lights
Mobile Plans
1
Failed to illuminate
N
TBA
TBA
To be replaced with LED linkable lights. Please advise if Sturdie are to provide a quote
Test and Tag
Store
80+
Overdue
N
N
N
Observation
Site Status Selector
Store now fully compliant
Next Test Due in 6 months
09/05/2022
The Built Services Group seeks to apply innovation and technology for greater client services, business efficiencies and thinking Green.