Partner NameBuilt Services
StateSA
Date of Visit19/11/2021
Technician's NamePeter Tsoukarellis
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58477
EmailEmail hidden; Javascript is required.
The Good Guys Site in SAnoarlunga

Location NameNoarlunga
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB SHOP 8 Y P
DB SHOP 10 Y P
DB SHOP 12 Y P
DB SHOP 14 Y P
DB SHOP 16 Y P
DB SHOP 18 Y P
DB SHOP 20 Y P
DB SHOP 22 Y P
DB SHOP 24 Y P
DB SHOP 26 Y P
DB SHOP 30 Y P
DB SHOP 32 Y P
DB SHOP 36 Y P
DB SHOP 38 Y P
DB SHOP 40 Y P
DB SHOP 42 Y P
DB SHOP 44 Y P
DB SHOP 48 Y P
DB SHOP 50 Y P
DB SHOP 52 Y P
DB SHOP 54 Y P
DB SHOP 56 Y P
DB SHOP 60 Y P
DB SHOP 3 Y P
DB SHOP 5 Y P
DB SHOP 7 Y P
DB SHOP 9 Y P
DB SHOP 11 Y P
DB SHOP 13 Y P
DB SHOP 15 Y P
DB SHOP 17 Y P
DB SHOP 19 Y P
DB SHOP 21 Y P
DB SHOP 23 Y P
DB SHOP 27 Y P
DB SHOP 29 Y P
DB SHOP 31 Y P
DB SHOP 33 Y P
DB SHOP 35 Y P
DB SHOP 37 Y P
DB SHOP 39 Y P
DB SHOP 41 Y P
DB SHOP 43 Y P
DB SHOP 47 Y P
DB SHOP 49 Y P
DB SHOP 62 Y P
DB SHOP 64 Y P
DB SHOP 66 Y P
DB SHOP 68 Y P
DB SHOP 70 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB EM1 R Y Y Y P
MSB EM2 R Y Y Y P
MSB EM3 R Y Y Y P
MSB EM4 R Y Y Y P
MSB EM5 R Y Y Y P
MSB EM6 R Y Y Y P
MSB EM11 R Y Y Y P
MSB EM12 S Y N Y F Failed 90 minute Test Y N
MSB EM13 R Y Y Y P
MSB EM14 R Y Y Y P
MSB EM15 R Y Y Y P
MSB EM16 R Y Y Y P
MSB EM17 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB EX7 Y Y N F Exposed cables Y Y
MSB EX8 Y Y N F Exposed cables Y Y
MSB EX9 Y Y N F Exposed cables Y N
MSB EX10 Y Y N F Exposed cables Y N
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
36w bare batten Y
48w bare batten Y
28w bare batten Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
EM 12 Out side of toilets 1 Failed 90 minute test Y N N Replaced Fitting.
All Exit lights Through out store 4x Exposed cables - Not within Australian standards Y N N Rectified to Australian standards
Site Status SelectorStore now fully compliant
Next Test Due in 6 months19/05/2022