Partner NameTransit Electrical Pty Ltd
StateWA
Date of Visit08/12/2021
Technician's NameDaniel Guler
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58155
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAbusselton

Location NameBusselton
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB 1 A 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
19 Y P
21 Y P
35 Y P
8 Y P
10 Y P
12 Y P
16 Y P
18 Y P
20 Y P
22 Y P
DB 2 B 4 Y P
6 Y P
8 Y P
10 Y P
12 Y P
32 Y P
34 Y P
36 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 02 2 R Y Y Y P
DB 02 3 R Y Y Y P
DB 02 4 R Y Y Y P
DB 02 5 R Y Y Y P
DB 02 6 R Y Y Y P
DB 02 7 R Y Y Y P
DB 02 8 R Y Y Y P
DB 02 9 R Y Y Y P
DB 02 10 R Y Y Y P
DB 02 12 R Y Y Y P
DB 02 14 R Y Y Y P
DB 02 15 R Y Y Y P
DB 02 17 R Y Y Y P
DB 02 18 R Y Y Y P
DB 02 20 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB 02 1 Y Y Y P
DB 02 11 Y Y Y P
DB 02 13 Y Y Y P
DB 02 16 Y Y Y P
DB 02 19 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
2 by 26w Troffer Y
2 by 36w WP Batten Y
400w Low Bay Y
LED Oyster Light Y
Exit Y
Emergency Spitfire Y
250w MH Hibay Y
1 by 36w Bare Batten Y
1 by 18w Bare Batten Y
1by 30w Bare Batten Y
50w Downlights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
1 In store 18 Droppers not up to standards N N N Quote recommendation listed on fortnightly report
2 TV racks 5 Multiple power boards connected / daisy chained N N N Quote recommendation listed on fortnightly report. OH&S - Too many power boards looped
3 Comms Room 4 Need four extra GPO's installed Y N N Extra GPO's were required for security panels
4 Shop near fridges 1 TBar LED troffer out Y N N Located in a very dark corner of the shop. Replaced with new LED panel
5 Back of house 1 Broken GPO and falling off wall Y N N Replaced GPO with a blank plate
6 Switchboard 8 Lights in shop not on RCDs N N N Quote recommendation listed on fortnightly report. Replace 8 MCBs with RCDs
7 Comms Room 1 Fan making very loud noise Y N N Found UPS that was plugged into security panel had failed. Bypassed UPS to stop noise and reported to Manager
8 Mobile Plans 8 LED linkable battens not illuminated Y N N
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/06/2022