StateNT
Date of Visit08/12/2021
Technician's NameTom Banks
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number58356
EmailEmail hidden; Javascript is required.
The Good Guys Site in NTdarwin

Location NameDarwin
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db1 7 Y P
Db1 19 Y P
Db1 23 Y P
Db1 25 Y P
Db1 27 Y P
Db1 29 Y P
Db1 33 Y P
Db1 35 Y P
Db1 37 Y P
Db1 39 Y P
Db1 41 Y P
Db1 43 Y P
Db1 45 Y P
Db1 47 Y P
Db1 49 Y P
Db1 51 Y P
Db1 53 Y P
Db1 55 Y P
Db1 57 Y P
Db1 59 Y P
Db1 61 Y P
Db1 63 Y P
Db1 65 Y P
Db1 66 Y P
Db1 67 Y P
Db1 68 Y P
Db1 70 Y P
Db2 2 Y P
Db2 4 Y P
Db2 6 Y P
Db2 14 Y P
Db2 16 Y P
Db2 18 Y P
Db2 20 Y P
Db2 22 Y P
Db2 24 Y P
Db2 25 Y P
Db2 26 Y P
Db2 28 Y P
Db2 29 Y P
Db2 30 Y P
Db2 32 Y P
Db2 33 Y P
Db2 34 Y P
Db2 35 Y P
Db2 36 Y P
Db2 37 Y P
Db2 38 Y P
Db2 39 Y P
Db2 40 Y P
Db2 41 Y P
Db2 42 Y P
Db2 43 Y P
Db2 45 Y P
Db2 47 Y P
Db2 49 Y P
Db2 51 Y P
Db2 53 Y P
Db2 55 Y P
Db2 58 Y P
Db2 59 Y P
Db2 61 Y P
Db2 63 Y P
Db2 65 Y P
Db2 67 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 2 R Y Y Y P
Db1 4 S Y Y Y P
Db1 5 S Y Y Y P
Db1 6 S Y Y Y P
Db1 7 S Y N Y F Battery failed 90 minute test Y N
Db1 8 S Y Y Y P
Db1 9 S Y Y Y P
Db1 10 S Y Y Y P
Db1 11 S Y Y Y P
Db1 12 S Y Y Y P
Db1 13 S Y Y Y P
Db1 14 S Y Y Y P
Db1 15 S Y Y Y P
Db1 17 R Y Y Y P
Db1 18 R Y Y Y P
Db1 21 S Y Y Y P
Db1 22 S Y Y Y P
Db1 24 S Y Y Y P
Db1 27 R Y Y Y P
Db1 29 R Y Y Y P
Db1 31 R Y Y Y P
Db1 32 R Y Y Y P
Db1 33 R Y Y Y P
Db1 34 R Y Y Y P
Db1 35 R Y N Y F Battery failed 90 minute test Y N
Db1 36 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 1 Y Y Y P
Db1 3 Y Y Y P
Db1 16 Y Y Y P
Db1 19 Y Y Y P
Db1 20 Y Y Y P
Db1 23 Y Y Y P
Db1 25 Y Y Y P
Db1 26 Y Y Y P
Db1 28 Y Y Y P
Db1 30 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Exit LED Y
Exit Ultrablade Y
Led Spitfire Y
Halgon Spitfire Y
36W Emergency Diffused Fitting Y
36w Diffused Fitting Y
Fluoro Hibay Y
Fluoro Low Bay Y
LED Down Light Y
Halgon Down Light Y
Oyster Light Y
LED Strip Y
Led Flood Light Y
18W WP Fitting Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
LED Hibays Fridges 2 Not illuminated Davis UFO150EA5K3B09 Y Replaced LED Highbays
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Bc Lamps Ladies bathroom 2 Missing Y N N Replaced lamps
Downlight TVs 1 Not illuminated Y N N Replaced downlight
Surface Mount Emergency #7 Kitchen 1 Battery failed 90 minute test Y N N Replaced emergency light
Recessed Emergency Light #35 Office hallway 1 Battery failed 90 minute test Y N N Replaced emergency light
Site Status SelectorStore now fully compliant
Next Test Due in 6 months09/06/2022