Partner NameBuilt Electrical Australia
StateNSW
Date of Visit27/01/2022
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62332
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWcasula

Location NameCasula
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Tenancy 18 DB 7 Y P
8 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
49 Y P
50 Y P
51 Y P
52 Y P
53 Y P
54 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
67 Y P
69 Y P
71 Y P
DBA 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
28 Y P
30 Y P
32 Y P
34 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Tenancy DB 18 EM1 S Y Y Y P
EM2 S Y Y Y P
EM3 S Y Y Y P
EM4 S Y Y Y P
EM5 S Y Y Y P
EM6 S Y Y Y P
EM7 S Y Y Y P
EM8 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Tenancy DB 18 EX1 Y Y Y P
EX2 Y Y Y P
EX3 Y Y Y P
EX4 Y Y Y P
EX5 Y Y Y P
EX6 Y Y Y P
EX7 Y Y Y P
EX8 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Hi Bay Halo Globe Y
2 x 28W Fluoro Y
2 x 28W Caged Fluoro Y
1200mm LED Batten Y
LED Pelmet Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LED Driver Fisher & Paykel Display 1 Faulty Y N N Replaced driver
Exposed ELV Wires Electrolux Vacuum Display 1 Wiring between driver and light box has detached from light box. Y N N Repaired wiring and replaced driver
Light Box Electrolux Fridges 1 Not illuminated N TBA TBA Fault finding required, please advise if quote is required.
Not enough power outlets Hi Sense Fridges 1 PB4 and 1.5m elsafe lead required N TBA TBA Please advise if quote is required.
Light Box Solt Washing Machines 1 Flickering N TBA TBA Fault finding required, please advise if quote is required.
Light Box Hi Sense Tv Display 1 Not illuminated N TBA TBA Fault finding required, please advise if quote is required.
Light Box Fisher & Paykel Washing Machine Display 1 Not illuminated N TBA TBA Fault finding required, please advise if quote is required.
Light Box Swann Smart Home 1 Not illuminated N TBA TBA Fault finding required, please advise if quote is required.
LED Panel Microsoft Laptop Table 1 Not illuminated N N N Supplier to replace Panel.
Light Box Smart Home/ Accessories/ Monitors Wall Bays 3 Not illuminated N TBA TBA Fault finding required, please advise if quote is required.
Domestic Power Boards Heating/Cooling Display 4 Easily accessible to be touched by staff and public. Should be changed to PB4's. N TBA TBA 4 x pb4, 3 x 1.5m Elsafe leads, 1 x 3m elsafe lead. Please advise if quote is required.
Power Dropper Bosch/Weber Display Store Entrance 2 Too Short/Wrong Location N TBA TBA Scissor required, please advise if quote is required.
Light Box Vax 1 Flickering N TBA TBA Fault finding required, please advise if quote is required.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months27/07/2022