Partner NameSturdie Trade Services
StateVIC
Date of Visit03/02/2022
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62247
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmaribyrnong

Location NameMaribyrnong
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-2 01 Y P
DB-2 02 Y P
DB-2 03 Y P
DB-2 04 Y P
DB-2 05 Y P
DB-2 06 Y P
DB-2 07 Y P
DB-2 08 Y P
DB-2 09 Y P
DB-2 10 Y P
DB-2 11 Y P
DB-2 12 Y P
DB-2 13 Y P
DB-2 14 Y P
DB-2 15 Y P
DB-2 16 Y P
DB-2 17 Y P
DB-2 18 Y P
DB-2 19 Y P
DB-2 20 Y P
DB-2 21 Y P
DB-2 22 Y P
DB-2 23 Y P
DB-2 24 Y P
DB-2 25 Y P
DB-2 26 Y P
DB-2 27 Y P
DB-2 28 Y P
DB-2 29 Y P
DB-2 30 Y P
DB-2 31 Y P
DB-2 32 Y P
DB-2 33 Y P
DB-2 34 Y P
DB-2 35 Y P
DB-2 36 Y P
DB-2 37 Y P
DB-2 38 Y P
DB-2 39 Y P
DB-2 40 Y P
DB-2 41 Y P
DB-2 42 Y P
DB-2 43 Y P
DB-2 44 Y P
DB-2 45 Y P
DB-2 46 Y P
DB-2 47 Y P
DB-2 48 Y P
DB-2 49 Y P
DB-2 50 Y P
DB-2 51 Y P
DB-2 52 Y P
DB-2 53 Y P
DB-2 54 Y P
DB-2 55 Y P
DB-2 56 Y P
DB-2 57 Y P
DB-2 58 Y P
DB-2 59 Y P
DB-2 60 Y P
DB-2 62 Y P
DB-2 64 Y P
DB-2 66 Y P
DB-2 67 Y P
DB-2 68 Y P
DB-2 69 Y P
DB-2 70 Y P
DB-2 71 Y P
DB-2 72 Y P
DB-2 73 Y P
DB-1A 01 Y P
DB-1A 02 Y P
DB-1A 03 Y P
DB-1A 05 Y P
DB-1A 07 Y P
DB-1A 08 Y P
DB-1A 09 Y P
DB-1A 10 Y P
DB-1A 11 Y P
DB-1A 12 Y P
DB-1A 17 Y P
DB-1A 19 Y P
DB-1A 21 Y P
DB-1A 27 Y P
DB-1A 29 Y P
DB-1A 31 Y P
DB-1B 01 Y P
DB-1B 02 Y P
DB-1B 03 Y P
DB-1B 04 Y P
DB-1B 05 Y P
DB-1B 05 Y P
DB-1B 07 Y P
DB-1B 08 Y P
DB-1B 09 Y P
DB-1B 10 Y P
DB-1B 11 Y P
DB-1B 12 Y P
DB-1B 13 Y P
DB-1B 14 Y P
DB-1B 15 Y P
DB-1B 16 Y P
DB-1B 17 Y P
DB-1B 18 Y P
DB-1B 19 Y P
DB-1B 20 Y P
DB-1B 21 Y P
DB-1B 22 Y P
DB-1B 23 Y P
DB-1B 24 Y P
DB-1B 25 Y P
DB-1B 26 Y P
DB-1B 27 Y P
DB-1B 28 Y P
DB-1B 29 Y P
DB-1B 30 Y P
DB-1B 31 Y P
DB-1B 32 Y P
DB-1B 33 Y P
DB-1B 34 Y P
DB-1B 35 Y P
DB-1B 36 Y P
DB-1B 37 Y P
DB-1B 38 Y P
DB-1B 39 Y P
DB-1B 40 Y P
DB-1B 41 Y P
DB-1B 42 Y P
DB-1B 43 Y P
DB-1B 44 Y P
DB-1B 45 Y P
DB-1B 46 Y P
DB-1B 47 Y P
DB-1B 48 Y P
DB-1B 49 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-2 2 R Y Y Y P
DB-2 6 S Y Y Y P
DB-2 7 S Y Y Y P
DB-2 9 S Y Y Y P
DB-2 11 S Y Y Y P
DB-2 13 S Y Y Y P
DB-2 14 S Y Y Y P
DB-2 17 S Y Y Y P
DB-2 18 S Y Y Y P
DB-2 19 S Y Y Y P
DB-2 20 R Y Y Y P
DB-2 22 R Y Y Y P
DB-2 24 S Y Y Y P
DB-2 26 S Y Y Y P
DB-2 27 S Y Y Y P
DB-2 28 S Y Y Y P
DB-2 29 S Y Y Y P
DB-3 30 S Y Y Y P
DB-3 31 S Y Y Y P
DB-3 32 S Y Y Y P
DB-3 36 R Y Y Y P
DB-3 39 R Y Y Y P
DB-3 40 S Y Y Y P
DB-3 42 R Y Y Y P
DB-3 43 R Y Y Y P
DB-3 44 R Y Y Y P
DB-2 46 R Y Y Y P
DB-2 47 R Y Y Y P
DB-2 48 R Y Y Y P
DB-2 49 R Y Y Y P
DB-2 50 R Y Y Y P
DB-2 51 R Y Y Y P
DB-2 52 S Y Y Y P
DB-2 53 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-2 1 Y Y Y P
DB-2 3 N Y Y F FAILED TO ILLUMINATE Y N
DB-2 4 Y N Y F FAILED BATTERY TEST Y N
DB-2 5 N Y Y F FAILED TO ILLUMINATE Y N
DB-2 6 Y N Y F FAILED BATTERY TEST Y N
DB-2 8 Y Y Y P
DB-2 10 N Y Y F FAILED TO ILLUMINATE Y N
DB-2 12 Y Y Y P
DB-2 15 Y Y Y P
DB-2 16 Y Y Y P
DB-2 21 Y Y Y P
DB-2 23 Y Y Y P
DB-2 25 Y Y Y P
DB-3 33 Y Y Y P
DB-3 34 Y Y Y P
DB-3 35 Y Y Y P
DB-3 36 Y Y Y P
DB-3 37 Y Y Y P
DB-3 41 Y Y Y P
DB-3 45 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
LED High Bay Y
LED Downlights Y
T5 Bare Batten Twin Y
T5 Single Defused Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
DAVIS HIGH BAY BOH ABOVE RACKING/DESK 1 FLASHING DAVIS Y REPLACED WITH NEW HIGH BAY UNTIL REPLACEMENT PART IS RECEIVED. USED PART THAT WAS INTENDED FOR "BETWEEN WATER AND NOVELTY GONDOLAS, CLOSER TO TVS"
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
DB2 CB24 DB2 1 RCD TAPED OFF Y N N INVESTIGATED, RESET AND OPERATING AS INTENDED
DB2 CB39 DB2 1 RCD TAPED OFF Y N N INVESTIGATED, RESET AND OPERATING AS INTENDED
DB2 CB59 DB2 1 RCD TAPED OFF Y N N INVESTIGATED, FRONT TGG SIGN, KNOWN INTERNAL FAULT, NO FURTHER ACTION REQUIRED
DB2 CB70 DB2 1 RCD TAPED OFF Y N N INVESTIGATED, RESET AND OPERATING AS INTENDED
DB-1B CB14 DB-1B 1 RCD TRIPPING WHEN RESET N N TBA URGENTLY INVESTIGATED, LABELED HWS 2, UPSTAIRS HOT WATER SYSTEM IN KITCHEN. AFTER INVESTIGATION FOUND FAULTY HOT WATER SYSTEM IN CEILING SPACE ACCESSED FROM UPSTAIRS STORE ROOM. HWS DISCONNECTED AND MADE SAFE, PLUMBER REQUIRED TO REPLACE HWS, RETURN VISIT TO RECONNECT. MANAGER NOTIFIED AND MAINTENANCE TEAM HAS BEEN EMAILED
DB ACCESS DB-1B 1 LARGE AMOUNT OF BOXES IN FRONT OF DB, CLEAR ACCESS REQUIRED N N N OBSERVATION - PLEASE ENSURE STOCK DOES NOT BLOCK ACCESS TO SWITCHBOARD
LARGE HIGHBAY FRIDGES ABOVE WESTINGHOUSE AND ELECTROLUX DISPLAY FRIDGES 1 DIM, FAILED TO ILLUMINATE Y N N REPLACED WITH NEW - COMPLIANCE APPROVED
LARGE HIGHBAY COFFEE 1 DIM, FAILED TO ILLUMINATE Y N N REPLACED WITH NEW - COMPLIANCE APPROVED
LARGE HIGHBAY BETWEEN WATER AND NOVELTY GONDOLAS, CLOSER TO TVS 1 DIM, FAILED TO ILLUMINATE N N Y ORDERED PART TO REPLACE FAULTY FITTING, HOWEVER ON RETURN VISIT TECHNICIAN NOTICED ANOTHER HIGH BAY REQUIRED REPLACING THAT WAS IN AN AREA WITH OH&S ISSUE. THIS HIGH BAY WAS BOH AND UNDER WARRANTY. ONCE WARRANTY REPLACEMENT HAS BEEN PROVIDED THEN TECHNICIAN WILL RE-INSTALL IN THIS LOCATION
SITE FOLDER STORE 1 NO SITE FOLDER ON SITE Y N N EXPRESS POSTED NEW FOLDER - APPROVED BY COMPLIANCE
70MM DOWNLIGHT TV AREA 1 FAILED TO ILLUMINATE N N TBA ADDED TO FORTNIGHLY REPAIR LIST
EX06 BOH SINGLE MAN DOOR 1 FAILED BATTERY TEST Y N N JUMBO EXIT REPLACED WITH NEW
EX04 SHOP FLOOR NEAR DYSON 1 FAILED BATTERY TEST Y N N JUMBO EXIT REPLACED WITH NEW
EX10 SHOP FLOOR NEAR MICROWAVES 1 FAILED TO ILLUMINATE Y N N JUMBO EXIT REPLACED WITH NEW
EX03 SHOP FLOOR NEAR ENTRANCE 1 FAILED TO ILLUMINATE Y N N JUMBO EXIT REPLACED WITH NEW
EX05 SHOP FLOOR ABOVE SINGLE MAN DOOR NEAR MAIN DB 1 FAILED TO ILLUMINATE Y N N JUMBO EXIT REPLACED WITH NEW
EXT WALL BUNKER LIGHT EXT FRONT WALL NEAR PET STORE 1 FAULTY FITTING N N TBA ADDED TO FORTNIGHLY REPAIR LIST
EXT FLOODLIGHT CUSTOMER PICK UP AREA 1 FAILED TO ILLUMINATE, FAULTY FITTING N N TBA ADDED TO FORTNIGHLY REPAIR LIST
EXT FRONT LAMP EXT FRONT UNDER CANOPY 1 FAILED TO ILLUMINATE N N TBA ADDED TO FORTNIGHLY REPAIR LIST
LIGHTING IN FRONT STOREROOM FRONT STORE ROOM NEAR ENTRANCE 3 FAILED TO ILLUMINATE N N TBA FOUND FAULTY 360 PIR SENSOR SURFACE MOUNT, WILL NEED TO BE REPLACED. SENSOR HAS BEEN BYPASSED TO ALLOW LIGHTS TO WORK OFF SWITCH. ADDED TO FORTNIGHLY REPAIR LIST
ROUND RECESSED FITTING CLEANER STORE ROOM 1 FAILED TO ILLUMINATE N N TBA ADDED TO FORTNIGHLY REPAIR LIST
MECHANICAL PROTECTION SECURITY GATES FRONT ENTRANCE 1 NO MECHANICAL COVERS OVER CABLES N TBA TBA WOULD NEED A COVER TO ME MADE/INSTALLED. ADDED TO FORTNIGHLY REPAIR LIST
Site Status SelectorStore now fully compliant
Next Test Due in 6 months03/08/2022