| State | NSW |
|---|
| Date of Visit | 08/02/2022 |
|---|
| Technician's Name | Glenn Robinson |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 62531 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in NSW | kotara |
|---|
|
|
|---|
| Location Name | Kotara |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 12 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| RCD Details (Initial/12 Months) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DBT12B |
2 |
Y |
P |
|
|
| DBT12B |
4 |
Y |
P |
|
|
| DBT12B |
5 |
Y |
P |
|
|
| DBT12B |
6 |
Y |
P |
|
|
| DBT12B |
7 |
Y |
P |
|
|
| DBT12B |
8 |
Y |
P |
|
|
| DBT12B |
9 |
Y |
P |
|
|
| DBT12B |
10 |
Y |
P |
|
|
| DBT12B |
11 |
Y |
P |
|
|
| DBT12B |
12 |
Y |
P |
|
|
| DBT12B |
13 |
Y |
P |
|
|
| DBT12B |
14 |
Y |
P |
|
|
| DBT12B |
15 |
Y |
P |
|
|
| DBT12B |
16 |
Y |
P |
|
|
| DBT12B |
17 |
Y |
P |
|
|
| DBT12B |
18 |
Y |
P |
|
|
| DBT12B |
19 |
Y |
P |
|
|
| DBT12B |
20 |
Y |
P |
|
|
| DBT12B |
21 |
Y |
P |
|
|
| DBT12B |
22 |
Y |
P |
|
|
| DBT12B |
23 |
Y |
P |
|
|
| DBT12B |
24 |
Y |
P |
|
|
| DBT12B |
25 |
Y |
P |
|
|
| DBT12B |
26 |
Y |
P |
|
|
| DBT12B |
27 |
Y |
P |
|
|
| DBT12B |
28 |
Y |
P |
|
|
| DBT12B |
29 |
Y |
P |
|
|
| DBT12B |
30 |
Y |
P |
|
|
| DBT12B |
31 |
Y |
P |
|
|
| DBT12B |
32 |
Y |
P |
|
|
| DBT12B |
33 |
Y |
P |
|
|
| DBT12B |
34 |
Y |
P |
|
|
| DBT12B |
35 |
Y |
P |
|
|
| DBT12B |
36 |
Y |
P |
|
|
| DBT12B |
37 |
Y |
P |
|
|
| DBT12B |
38 |
Y |
P |
|
|
| DBT12B |
40 |
Y |
P |
|
|
| DBT12B |
42 |
Y |
P |
|
|
| DBT12B |
44 |
Y |
P |
|
|
| DBT12B |
46 |
Y |
P |
|
|
| DBT12C |
1 |
Y |
P |
|
|
| DBT12C |
2 |
Y |
P |
|
|
| DBT12C |
3 |
Y |
P |
|
|
| DBT12C |
4 |
Y |
P |
|
|
| DBT12C |
5 |
Y |
P |
|
|
| DBT12C |
6 |
Y |
P |
|
|
| DBT12C |
7 |
Y |
P |
|
|
| DBT12C |
8 |
Y |
P |
|
|
| DBT12C |
9 |
Y |
P |
|
|
| DBT12C |
10 |
Y |
P |
|
|
| DBT12C |
11 |
Y |
P |
|
|
| DBT12C |
12 |
Y |
P |
|
|
| DBT12C |
13 |
Y |
P |
|
|
| DBT12C |
14 |
Y |
P |
|
|
| DBT12C |
15 |
Y |
P |
|
|
| DBT12C |
16 |
Y |
P |
|
|
| DBT12C |
17 |
Y |
P |
|
|
| DBT12C |
18 |
Y |
P |
|
|
| DBT12C |
19 |
Y |
P |
|
|
| DBT12C |
20 |
Y |
P |
|
|
| DBT12C |
21 |
Y |
P |
|
|
| DBT12C |
22 |
Y |
P |
|
|
| DBT12C |
23 |
Y |
P |
|
|
| DBT12C |
24 |
Y |
P |
|
|
| DBT12C |
25 |
Y |
P |
|
|
| DBT12C |
26 |
Y |
P |
|
|
| DBT12C |
27 |
Y |
P |
|
|
| DBT12C |
28 |
Y |
P |
|
|
| DBT12C |
29 |
Y |
P |
|
|
| DBT12C |
30 |
Y |
P |
|
|
| DBT12C |
31 |
Y |
P |
|
|
| DBT12C |
32 |
Y |
P |
|
|
| DBT12C |
33 |
Y |
P |
|
|
| DBT12C |
34 |
Y |
P |
|
|
| DBT12C |
35 |
Y |
P |
|
|
| DBT12C |
36 |
Y |
P |
|
|
| DBT12C |
37 |
Y |
P |
|
|
| DBT12C |
38 |
Y |
P |
|
|
| DBT12C |
39 |
Y |
P |
|
|
| DBT12C |
40 |
Y |
P |
|
|
| DBT12C |
41 |
Y |
P |
|
|
| DBT12C |
42 |
Y |
P |
|
|
| DBT12C |
43 |
Y |
P |
|
|
| DBT12C |
44 |
Y |
P |
|
|
| DBT12C |
45 |
Y |
P |
|
|
| DBT12C |
46 |
Y |
P |
|
|
| DBT12C |
47 |
Y |
P |
|
|
| DBT12C |
48 |
Y |
P |
|
|
| DBT12C |
49 |
Y |
P |
|
|
| DBT12C |
50 |
Y |
P |
|
|
| DBT12C |
51 |
Y |
P |
|
|
| DBT12C |
52 |
Y |
P |
|
|
| DBT12C |
53 |
Y |
P |
|
|
| DBT12C |
55 |
Y |
P |
|
|
| DBT12C |
57 |
Y |
P |
|
|
| DBT12C |
59 |
Y |
P |
|
|
| DBT12C |
60 |
Y |
P |
|
|
| DBT12E |
1 |
Y |
P |
|
|
| DBT12E |
3 |
Y |
P |
|
|
| DBT12E |
5 |
Y |
P |
|
|
| DBT12E |
7 |
Y |
P |
|
|
| DBT12E |
9 |
Y |
P |
|
|
| DBT12E |
11 |
Y |
P |
|
|
| DBT12E |
13 |
Y |
P |
|
|
| DBT12E |
15 |
Y |
P |
|
|
| DBT12E |
17 |
Y |
P |
|
|
| DBT12E |
19 |
Y |
F |
Push button not working |
Y |
| DBT12E |
21 |
Y |
P |
|
|
| DBT12D |
1 |
Y |
P |
|
|
| DBT12D |
2 |
Y |
P |
|
|
| DBT12D |
3 |
Y |
P |
|
|
| DBT12D |
4 |
Y |
P |
|
|
| DBT12D |
5 |
Y |
P |
|
|
| DBT12D |
6 |
Y |
P |
|
|
| DBT12D |
7 |
Y |
P |
|
|
| DBT12D |
8 |
Y |
P |
|
|
| DBT12D |
9 |
Y |
P |
|
|
| DBT12D |
10 |
Y |
P |
|
|
| DBT12D |
11 |
Y |
P |
|
|
| DBT12D |
12 |
Y |
P |
|
|
| DBT12D |
13 |
Y |
P |
|
|
| DBT12D |
14 |
Y |
P |
|
|
| DBT12D |
15 |
Y |
P |
|
|
| DBT12D |
16 |
Y |
P |
|
|
| DBT12D |
17 |
Y |
P |
|
|
| DBT12D |
18 |
Y |
P |
|
|
| DBT12D |
19 |
Y |
P |
|
|
| DBT12D |
20 |
Y |
P |
|
|
| DBT12D |
21 |
Y |
P |
|
|
| DBT12D |
22 |
Y |
P |
|
|
| DBT12D |
23 |
Y |
P |
|
|
| DBT12D |
25 |
Y |
P |
|
|
| DBT12D |
25 |
Y |
P |
|
|
| DBT12D |
27 |
Y |
P |
|
|
| DBT12D |
29 |
Y |
P |
|
|
|
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| T12C |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
2 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
6 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
7 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
11 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
12 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
13 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
14 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
15 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
17 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
18 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
20 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
23 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
24 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
25 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
26 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
28 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
29 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
30 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
31 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
33 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
35 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
40 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
41 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
42 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
43 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
44 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
45 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
46 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
47 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
51 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
52 |
S |
Y |
Y |
Y |
P |
|
|
|
| T12C |
54 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
55 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
57 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
58 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
59 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
60 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
61 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
62 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
63 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
64 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
65 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
67 |
R |
Y |
Y |
Y |
P |
|
|
|
| T12C |
69 |
R |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| T12C |
3 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
4 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
5 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
8 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
9 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
10 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
16 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
19 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
21 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
22 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
27 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
32 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
34 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
36 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
37 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
38 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
39 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
48 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
49 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
50 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
53 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
56 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
66 |
Y |
Y |
Y |
P |
|
|
|
| T12C |
68 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| Ci-C Fluoro |
Y |
| 2x36W Diffused |
Y |
| 400W Flood Light |
Y |
| 70mm Downlight |
Y |
| 1x18 T5 Diffused |
Y |
| 2x18W T5 Caged Fluoro |
Y |
| 2x18W Waterproof T5 |
Y |
| 140mm Downlight |
Y |
| 18W Compact Fluoro |
Y |
| Twin Par 38 Sensor |
Y |
| 250W Square Diffused |
Y |
| 36W Lamps |
Y |
| Square Recessed Fluoro |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| DBT12E CB19 |
DBT12E |
1 |
Push button RCD not working |
Y |
N |
N |
Replaced RCD |
| Switchboard legend |
Switchboard |
1 |
Requires updating |
Y |
N |
N |
New legend placed onsite |
|
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Next Test Due in 6 months | 08/08/2022 |
|---|
| |
|---|
| |