StateNSW
Date of Visit08/02/2022
Technician's NameGlenn Robinson
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62531
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWkotara

Location NameKotara
HTML Block
Test Period12 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

RCD Details (Initial/12 Months)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DBT12B 2 Y P
DBT12B 4 Y P
DBT12B 5 Y P
DBT12B 6 Y P
DBT12B 7 Y P
DBT12B 8 Y P
DBT12B 9 Y P
DBT12B 10 Y P
DBT12B 11 Y P
DBT12B 12 Y P
DBT12B 13 Y P
DBT12B 14 Y P
DBT12B 15 Y P
DBT12B 16 Y P
DBT12B 17 Y P
DBT12B 18 Y P
DBT12B 19 Y P
DBT12B 20 Y P
DBT12B 21 Y P
DBT12B 22 Y P
DBT12B 23 Y P
DBT12B 24 Y P
DBT12B 25 Y P
DBT12B 26 Y P
DBT12B 27 Y P
DBT12B 28 Y P
DBT12B 29 Y P
DBT12B 30 Y P
DBT12B 31 Y P
DBT12B 32 Y P
DBT12B 33 Y P
DBT12B 34 Y P
DBT12B 35 Y P
DBT12B 36 Y P
DBT12B 37 Y P
DBT12B 38 Y P
DBT12B 40 Y P
DBT12B 42 Y P
DBT12B 44 Y P
DBT12B 46 Y P
DBT12C 1 Y P
DBT12C 2 Y P
DBT12C 3 Y P
DBT12C 4 Y P
DBT12C 5 Y P
DBT12C 6 Y P
DBT12C 7 Y P
DBT12C 8 Y P
DBT12C 9 Y P
DBT12C 10 Y P
DBT12C 11 Y P
DBT12C 12 Y P
DBT12C 13 Y P
DBT12C 14 Y P
DBT12C 15 Y P
DBT12C 16 Y P
DBT12C 17 Y P
DBT12C 18 Y P
DBT12C 19 Y P
DBT12C 20 Y P
DBT12C 21 Y P
DBT12C 22 Y P
DBT12C 23 Y P
DBT12C 24 Y P
DBT12C 25 Y P
DBT12C 26 Y P
DBT12C 27 Y P
DBT12C 28 Y P
DBT12C 29 Y P
DBT12C 30 Y P
DBT12C 31 Y P
DBT12C 32 Y P
DBT12C 33 Y P
DBT12C 34 Y P
DBT12C 35 Y P
DBT12C 36 Y P
DBT12C 37 Y P
DBT12C 38 Y P
DBT12C 39 Y P
DBT12C 40 Y P
DBT12C 41 Y P
DBT12C 42 Y P
DBT12C 43 Y P
DBT12C 44 Y P
DBT12C 45 Y P
DBT12C 46 Y P
DBT12C 47 Y P
DBT12C 48 Y P
DBT12C 49 Y P
DBT12C 50 Y P
DBT12C 51 Y P
DBT12C 52 Y P
DBT12C 53 Y P
DBT12C 55 Y P
DBT12C 57 Y P
DBT12C 59 Y P
DBT12C 60 Y P
DBT12E 1 Y P
DBT12E 3 Y P
DBT12E 5 Y P
DBT12E 7 Y P
DBT12E 9 Y P
DBT12E 11 Y P
DBT12E 13 Y P
DBT12E 15 Y P
DBT12E 17 Y P
DBT12E 19 Y F Push button not working Y
DBT12E 21 Y P
DBT12D 1 Y P
DBT12D 2 Y P
DBT12D 3 Y P
DBT12D 4 Y P
DBT12D 5 Y P
DBT12D 6 Y P
DBT12D 7 Y P
DBT12D 8 Y P
DBT12D 9 Y P
DBT12D 10 Y P
DBT12D 11 Y P
DBT12D 12 Y P
DBT12D 13 Y P
DBT12D 14 Y P
DBT12D 15 Y P
DBT12D 16 Y P
DBT12D 17 Y P
DBT12D 18 Y P
DBT12D 19 Y P
DBT12D 20 Y P
DBT12D 21 Y P
DBT12D 22 Y P
DBT12D 23 Y P
DBT12D 25 Y P
DBT12D 25 Y P
DBT12D 27 Y P
DBT12D 29 Y P
THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T12C 1 S Y Y Y P
T12C 2 S Y Y Y P
T12C 6 S Y Y Y P
T12C 7 S Y Y Y P
T12C 11 S Y Y Y P
T12C 12 S Y Y Y P
T12C 13 S Y Y Y P
T12C 14 S Y Y Y P
T12C 15 S Y Y Y P
T12C 17 S Y Y Y P
T12C 18 S Y Y Y P
T12C 20 S Y Y Y P
T12C 23 R Y Y Y P
T12C 24 R Y Y Y P
T12C 25 R Y Y Y P
T12C 26 R Y Y Y P
T12C 28 R Y Y Y P
T12C 29 R Y Y Y P
T12C 30 S Y Y Y P
T12C 31 R Y Y Y P
T12C 33 S Y Y Y P
T12C 35 R Y Y Y P
T12C 40 S Y Y Y P
T12C 41 S Y Y Y P
T12C 42 S Y Y Y P
T12C 43 S Y Y Y P
T12C 44 S Y Y Y P
T12C 45 S Y Y Y P
T12C 46 S Y Y Y P
T12C 47 S Y Y Y P
T12C 51 S Y Y Y P
T12C 52 S Y Y Y P
T12C 54 R Y Y Y P
T12C 55 R Y Y Y P
T12C 57 R Y Y Y P
T12C 58 R Y Y Y P
T12C 59 R Y Y Y P
T12C 60 R Y Y Y P
T12C 61 R Y Y Y P
T12C 62 R Y Y Y P
T12C 63 R Y Y Y P
T12C 64 R Y Y Y P
T12C 65 R Y Y Y P
T12C 67 R Y Y Y P
T12C 69 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
T12C 3 Y Y Y P
T12C 4 Y Y Y P
T12C 5 Y Y Y P
T12C 8 Y Y Y P
T12C 9 Y Y Y P
T12C 10 Y Y Y P
T12C 16 Y Y Y P
T12C 19 Y Y Y P
T12C 21 Y Y Y P
T12C 22 Y Y Y P
T12C 27 Y Y Y P
T12C 32 Y Y Y P
T12C 34 Y Y Y P
T12C 36 Y Y Y P
T12C 37 Y Y Y P
T12C 38 Y Y Y P
T12C 39 Y Y Y P
T12C 48 Y Y Y P
T12C 49 Y Y Y P
T12C 50 Y Y Y P
T12C 53 Y Y Y P
T12C 56 Y Y Y P
T12C 66 Y Y Y P
T12C 68 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Ci-C Fluoro Y
2x36W Diffused Y
400W Flood Light Y
70mm Downlight Y
1x18 T5 Diffused Y
2x18W T5 Caged Fluoro Y
2x18W Waterproof T5 Y
140mm Downlight Y
18W Compact Fluoro Y
Twin Par 38 Sensor Y
250W Square Diffused Y
36W Lamps Y
Square Recessed Fluoro Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
DBT12E CB19 DBT12E 1 Push button RCD not working Y N N Replaced RCD
Switchboard legend Switchboard 1 Requires updating Y N N New legend placed onsite
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/08/2022