Partner NameSturdie Trade Services
StateVIC
Date of Visit04/03/2022
Technician's NameSimon Odd
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62253
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmoorabbin

Location NameMoorabbin
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-T9A1/POWER 7 Y P
DB-T9A1/POWER 8 Y P
DB-T9A1/POWER 9 Y P
DB-T9A1/POWER 10 Y P
DB-T9A1/POWER 11 Y P
DB-T9A1/POWER 12 Y P
DB-T9A1/POWER 13 Y P
DB-T9A1/POWER 14 Y P
DB-T9A1/POWER 15 Y P
DB-T9A1/POWER 16 Y P
DB-T9A1/POWER 17 Y P
DB-T9A1/POWER 18 Y P
DB-T9A1/POWER 19 Y P
DB-T9A1/POWER 20 Y P
DB-T9A1/POWER 21 Y P
DB-T9A1/POWER 22 Y P
DB-T9A1/POWER 23 Y P
DB-T9A1/POWER 24 Y P
DB-T9A1/POWER 25 Y P
DB-T9A1/POWER 26 Y P
DB-T9A1/POWER 27 Y P
DB-T9A1/POWER 28 Y P
DB-T9A1/POWER 29 Y P
DB-T9A1/POWER 30 Y P
DB-T9A1/POWER 31 Y P
DB-T9A1/POWER 32 Y P
DB-T9A1/POWER 33 Y P
DB-T9A1/POWER 34 Y P
DB-T9A1/POWER 35 Y P
DB-T9A1/POWER 36 Y P
DB-T9A1/POWER 37 Y P
DB-T9A1/POWER 38 Y P
DB-T9A1/POWER 39 Y P
DB-T9A1/POWER 40 Y P
DB-T9A1/POWER 41 Y P
DB-T9A1/POWER 42 Y P
DB-T9A1/LIGHTS 1 Y P
DB-T9A1/LIGHTS 2 Y P
DB-T9A1/LIGHTS 3 Y P
DB-T9A1/LIGHTS 4 Y P
DB-T9A1/LIGHTS 5 Y P
DB-T9A1/LIGHTS 6 Y P
DB-T9A1/LIGHTS 7 Y P
DB-T9A1/LIGHTS 8 Y P
DB-T9A1/LIGHTS 9 Y P
DB-T9A1/LIGHTS 10 Y P
DB-T9A1/LIGHTS 11 Y P
DB- T9A1/LIGHTS 12 Y P
DB-T9A1/LIGHTS 13 Y P
DB-T9A1/LIGHTS 14 Y P
DB-T9A1/LIGHTS 15 Y P
DB-T9A1/LIGHTS 16 Y P
DB-T9A1/LIGHTS 17 Y P
DB-T9A1/LIGHTS 18 Y P
DB-T9A1/LIGHTS 19 Y P
DB-T9A1/LIGHTS 20 Y P
DB-T9A1/LIGHTS 21 Y P
DB-T9A1/LIGHTS 22 Y P
DB-T9A1/LIGHTS 23 Y P
DB-T9A1/LIGHTS 24 Y P
DB-T9A1/LIGHTS 26 Y P
DB-T9A3 1 Y P
DB-T9A3 2 Y P
DB-T9A3 3 Y P
DB-T9A3 4 Y P
DB-T9A3 5 Y P
DB-T9A3 6 Y P
DB-T9A3 7 Y P
DB-T9A3 8 Y P
DB-T9A3 9 N F Faulty Y
DB-T9A3 10 Y P
DB-T9A3 11 Y P
DB-T9A3 12 Y P
DB-T9A3 13 Y P
DB-T9A2 2 Y P
DB-T9A2 4 Y P
DB-T9A2 6 Y P
DB-T9A2 7 Y P
DB-T9A2 8 Y P
DB-T9A2 9 Y P
DB-T9A2 10 Y P
DB-T9A2 11 Y P
DB-T9A2 12 Y P
DB-T9A2 13 Y P
DB-T9A2 14 Y P
DB-T9A2 15 Y P
DB-T9A2 16 Y P
DB-T9A2 17 Y P
DB-T9A2 18 Y P
DB-T9A2 19 Y P
DB-T9A2 20 Y P
DB-T9A2 21 Y P
DB-T9A2 22 Y P
DB-T9A2 23 Y P
DB-T9A2 24 Y P
DB-T9A2 25 Y P
DB-T9A2 27 Y P
DB-T9A2 28 Y P
DB-T9A2 30 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T9A1 2 R Y Y Y P
DB-T9A1 5 R Y Y Y P
DB- T9A1 6 R Y Y Y P
DB-T9A1 7 R Y Y Y P
DB-T9A1 8 R Y Y Y P
DB-T9A1 10 S Y Y Y P
DB-T9A1 11 S Y Y Y P
DB-T9A1 12 S Y N Y F Failed Battery Test Y N
DB-T9A1 16 R Y Y Y P
DB-T9A1 18 S Y Y Y P
DB-T9A1 19 S Y Y Y P
DB-T9A1 21 S Y N Y F Failed Battery Test Y N
DB-T9A1 22 S Y Y Y P
DB-T9A1 23 S Y Y Y P
DB-T9A1 24 S Y N Y F Failed Battery Test Y N
DB-T9A1 28 R Y Y Y P
DB-T9A1 29 R Y Y Y P
DB-T9A1 30 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-T9A1 1 Y Y Y P
DB- T9A1 3 Y Y Y P
DB- T9A1 4 Y Y Y P
DB-T9A1 9 Y Y Y P
DB-T9A1 13 Y Y Y P
DB-T9A1 14 Y Y Y P
DB-T9A1 15 Y Y Y P
DB-T9A1 17 Y Y Y P
DB-T9A1 20 Y Y Y P
DB-T9A1 25 Y Y Y P
DB-T9A1 26 Y Y Y P
DB-T9A1 27 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
High Bay Lights LED Y
36W Diffuser LED Y
Square High Bay Lights LED Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Faulty RCBO DB-T9A3 CB 9 1 Did not trip and could not turn breaker off as it was jammed Y N N Replaced with new
EM12 TV's 1 Didn't last the 90 minutes Y N N Replaced with new - Scissor lift required
EM21 LG Dishwashers 1 Didn't last the 90 minutes Y N N Replaced with new - Scissor lift required
EM23 Fridges 1 Didn't last the 90 minutes Y N N Replaced with new - Scissor lift required
Site Status SelectorStore now fully compliant
Next Test Due in 6 months04/09/2022