Partner NameSturdie Trade Services
StateVIC
Date of Visit21/03/2022
Technician's NameMatt Setches
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62259
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICcranbourne

Location NameCranbourne
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB1 15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
34 Y P
36 Y P
44 Y P
46 Y P
48 Y P
TDB.1 12 Y P
13 Y P
14 Y P
18 Y P
19 Y P
20 Y P
21 Y P
MSB-24 60 Y P
58 Y P
57 Y P
56 Y P
55 Y P
54 Y P
53 Y P
52 Y P
51 Y P
49 Y P
48 Y P
46 Y P
44 Y P
36 Y P
34 Y P
33 Y P
32 Y P
31 Y P
30 Y P
29 Y P
28 Y P
27 Y P
26 Y P
25 Y P
24 Y P
23 Y P
22 Y P
21 Y P
20 Y P
DB1-1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB-24 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
DB1 13 S Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
TDB.1 16 R Y Y Y P
17 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB-24 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
DB1 8 Y Y Y P
MSB-24 9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
TDB.1 13 Y Y Y P
14 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
400W Hi-Bay Mercury Vapour Fitting Y
4FT 36W Fluorescent Fittings Y
Single Batten Fluorescent Emergency 36W Fitting Y
Double Batten Fluorescent Emergency 36W Fitting Y
70mm Downlights Y
Single Bare Batten 36W Fluorescent Fitting Y
200W Hi-Bay Mercury Vapour Fitting Y
Single Batten 36W Fluorescent Diffuser Y
Recessed Emergency Light Fitting Y
90mm LED Downlights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Downlights TV's 11 Failed to illuminate Y N N Replaced with new
Lamps Front of Store 4 Failed to illuminate Y N N Replaced with new
The Good Guys Sign Front of Store 11 Letters Cover for the letter S has fallen off and electrical components exposed to the weather N TBA TBA Emailed Compliance team - Sturdie can install new S cover if supplied at the same time as below
The Good Guys Sign Front of Store 1 All lighting no longer work or are very dim N TBA TBA Emailed Compliance team and also added to fortnightly repair list as this is a costly repair that will exceed pre-approval limit
Site Status SelectorStore now fully compliant
Next Test Due in 6 months21/09/2022