Partner NameSturdie Trade Services
StateVIC
Date of Visit05/04/2022
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62262
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICessendon

Location NameEssendon
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-1/1 01 Y P
DB-1/1 02 Y P
DB-1/1 03 Y P
DB-1/1 04 Y P
DB-1/1 05 Y P
DB-1/1 09 Y P
DB-1/1 10 Y P
DB-1/1 11 Y P
DB-1/1 13 Y P
DB-1/1 14 Y P
DB-1/1 15 Y P
DB-1/1 16 Y P
DB-1/1 17 Y P
DB-1/1 18 Y P
DB-1/1A 02 Y P
DB-1/1A 04 Y P
DB-1/1A 06 Y P
DB-1/1A 08 Y P
DB-1/1A 10 Y P
DB-1/1A 12 Y P
DB-1/1A 14 Y P
DB-1/1A 16 Y P
DB-1/1A 18 Y P
DB-1/1A 20 Y P
DB-1/1A 22 Y P
DB-1/1A 24 Y P
DB-1/1A 26 Y P
DB-1/1A 28 Y P
DB-1/1A 30 Y P
DB-1/1A 32 Y P
DB-1/1A 34 Y P
DB-1/1A 36 Y P
DB-1/1A 38 Y P
DB-1/1A 40 Y P
DB-1/1A 42 Y P
DB-1/1A 44 Y P
DB-1/1A 46 Y P
DB-1/1A 48 Y P
DB-1/1A 50 Y P
DB-1/1A 83 Y P
DB-1/1A 84 Y P
DB-1/2 01 Y P
DB-1/2 02 Y P
DB-1/2 03 Y P
DB-1/2 04 Y P
DB-1/2 05 Y P
DB-1/2 06 Y P
DB-1/2 07 Y P
DB-1/2 08 Y P
DB-1/2 09 Y P
DB-1/2 10 Y P
DB-1/2 11 Y P
DB-1/2 12 Y P
DB-1/2 13 Y P
DB-1/2 14 Y P
DB-1/2 17 Y P
DB-1/2 18 Y P
DB-1/2 22 Y P
DB-1/2 23 Y P
DB-1/2 24 Y P
DB-1/2 25 Y P
DB-1/2 27 Y P
DB-1/2 29 Y P
DB-1/2 31 Y P
DB-1/2 32 Y P
DB-1/2 34 Y P
DB-1/2 36 Y P
DB-1/2 38 Y P
DB-1/2 40 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1/1 1 S Y Y Y P
DB-1/1 2 S Y N Y F FAILED BATTERY TEST Y N
DB-1/1 3 S Y Y Y P
DB-1/1 4 S Y Y Y P
DB-1/1 6 S Y Y Y P
DB-1/1 7 S Y Y Y P
DB-1/1 8 S Y Y Y P
DB-1/1 9 S Y Y Y P
DB-1/1 10 S Y Y Y P
DB-1/1 11 S Y Y Y P
DB-1/1 12 S Y Y Y P
DB-1/1 13 S Y Y Y P
DB-1/1 14 S Y Y Y P
DB-1/1 15 S Y Y Y P
DB-1/1 16 S Y Y Y P
DB-1/1 17 R Y Y Y P
DB-1/1 18 R Y Y Y P
DB-1/1 19 R Y Y Y P
DB-1/1 20 R Y Y Y P
DB-1/1 21 R Y Y Y P
DB-1/1 23 S Y Y Y P
DB-1/1 24 S Y Y Y P
DB-1/1 27 S Y Y Y P
DB-1/1 28 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1/1 1 Y Y Y P
DB-1/1 2 Y Y Y P
DB-1/1 3 Y Y Y P
DB-1/1 4 Y Y Y P
DB-1/1 5 Y Y Y P
DB-1/1 6 Y Y Y P
DB-1/1 7 Y Y Y P
DB-1/1 8 Y Y Y P
DB-1/1 9 Y Y Y P
DB-1/1 10 Y Y Y P
DB-1/1 11 Y Y Y P
DB-1/1 12 Y Y Y P
DB-1/1 13 Y Y Y P
DB-1/1 14 Y Y Y P
DB-1/1 15 Y Y Y P
DB-1/1 16 Y Y Y P
DB-1/1 17 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
High Bay Lights Y
Square High Bay Lights Y
LED Downlights Y
Twin Fluorescent Lights Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
BLACK HIGH BAY CENTER AISLE BETWEEN F AND P / ELECTROLUX WASHIMG MACHINES 1 FAILED TO ILLUMIMATE/DIM DAVIS - Y REPLACED WITH NEW - UNDER WARRANTY
BLACK HIGH BAY MIELE DISHWASHERS/VACUUMS 1 FAILED TO ILLUMIMATE DAVIS - Y REPLACED WITH NEW - UNDER WARRANTY
BLACK HIGH BAY FRONT ENTRANCE LHS 1 FAILED TO ILLUMIMATE DAVIS - Y REPLACED WITH NEW - UNDER WARRANTY
BLACK HIGH BAY FRYERS TOWARDS KETTLES 1 FAILED TO ILLUMIMATE DAVIS - N REQUESTED REPLACEMENT FROM SUPPLIER - WAIT TO RECEIVE BEFORE SCHEDULING RETURN VISIT
BLACK HIGH BAY CENTRE AISLE BETWEEN ELECTROLUX AND SAMSUNG TABLE 1 FAILED TO ILLUMIMATE/DIM/INTERMITTENT FAULT DAVIS - N REQUESTED REPLACEMENT FROM SUPPLIER - WAIT TO RECEIVE BEFORE SCHEDULING RETURN VISIT
BLACK HIGH BAY HEADPHONES CLOSE TO WALL 1 FAILED TO ILLUMIMATE DAVIS - N REQUESTED REPLACEMENT FROM SUPPLIER - WAIT TO RECEIVE BEFORE SCHEDULING RETURN VISIT
BLACK HIGH BAY GAMING ABOVE PS5 END CAP 1 FAILED TO ILLUMIMATE/ DIM DAVIS - N REQUESTED REPLACEMENT FROM SUPPLIER - WAIT TO RECEIVE BEFORE SCHEDULING RETURN VISIT
BLACK HIGH BAY BOH 1 FAILED TO ILLUMIMATE DAVIS - N REQUESTED REPLACEMENT FROM SUPPLIER - WAIT TO RECEIVE BEFORE SCHEDULING RETURN VISIT
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
LARGE DOWNLIGHT DISABLED TOILET 2 FAILED TO ILLUMINATE Y N N REPLACED WITH NEW
EM02 BOH NEAR COMMS ROOM 1 FAILED BATTERY TEST Y N N REPLACED WITH NEW - SCISSOR LIFT REQUIRED
LED RACK SIGN FRIDGES 1 FAILED TO ILLUMINATE Y N N INVESTIGATED AND FOUND DISCONNECTED, NO FURTHER ACTION REQUIRED
LED RACK SIGN HEATING/COOLING 1 FAILED TO ILLUMINATE Y N N INVESTIGATED AND FOUND DISCONNECTED, NO FURTHER ACTION REQUIRED
LED RACK SIGN AUDIO 1 FAILED TO ILLUMINATE Y N N REPLACED FAULTY DRIVER
LED RACK SIGN SOUNDBARS 1 FAILED TO ILLUMINATE Y N N INVESTIGATED AND FOUND DISCONNECTED, NO FURTHER ACTION REQUIRED
PENDANT LIGHT KINSMAN 1 FLASHING Y N N REPLACED LAMP WITH NEW
PENDANT LIGHT KINSMAN 1 FAILED TO ILLUMINATE Y N N REPLACED LAMP WITH NEW
LED WALL MOUNT FITTING OFFICE 1 FLASHING Y N N REPLACED FITTING WITH FLOODLIGHT - SCISSOR LIFT REQUIRED
Site Status SelectorStore now fully compliant
Next Test Due in 6 months05/10/2022