| State | NSW |
|---|
| Date of Visit | 06/04/2022 |
|---|
| Technician's Name | Con Karakiozis |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 62340 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in NSW | bankstown |
|---|
|
|
|---|
| Location Name | Bankstown |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| DB-5 |
2 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
y |
p |
|
|
|
12 |
y |
p |
|
|
|
14 |
y |
p |
|
|
|
16 |
y |
p |
|
|
|
18 |
y |
p |
|
|
|
20 |
y |
p |
|
|
|
22 |
y |
p |
|
|
|
24 |
y |
p |
|
|
|
28 |
y |
p |
|
|
|
30 |
y |
p |
|
|
|
42 |
y |
p |
|
|
|
44 |
y |
p |
|
|
|
19 |
y |
p |
|
|
|
21 |
y |
p |
|
|
|
23 |
y |
p |
|
|
|
25 |
y |
p |
|
|
|
27 |
y |
p |
|
|
|
29 |
y |
p |
|
|
|
31 |
y |
p |
|
|
|
33 |
y |
p |
|
|
|
35 |
y |
p |
|
|
|
37 |
y |
p |
|
|
|
45 |
y |
pp |
|
|
|
47 |
y |
p |
|
|
| DB-4 |
9 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
33 |
Y |
P |
|
|
|
34 |
Y |
P |
|
|
|
35 |
Y |
P |
|
|
|
36 |
Y |
P |
|
|
|
37 |
Y |
P |
|
|
|
38 |
Y |
P |
|
|
|
39 |
Y |
P |
|
|
|
40 |
Y |
P |
|
|
|
41 |
Y |
P |
|
|
| DB5.1 |
1 |
Y |
P |
|
|
|
2 |
Y |
P |
|
|
|
3 |
Y |
PP |
|
|
|
4 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
33 |
Y |
P |
|
|
|
35 |
Y |
P |
|
|
| DB4A BOH |
8 |
Y |
P |
|
|
| DB5A BOH |
7 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB-4 |
1 |
R |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
5 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
7 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
8 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
10 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
13 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
14 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
15 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
16 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
17 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
18 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
19 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
20 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
26 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
27 |
R |
Y |
Y |
Y |
P |
|
|
|
|
28 |
R |
Y |
Y |
Y |
P |
|
|
|
|
30 |
Em 4 Foot Fluoro |
F |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
31 |
Em 4 Foot Fluoro |
Y |
F |
Y |
F |
Failed 90 Min Test |
Y |
N |
|
32 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
|
|
|
|
33 |
Em 4 Foot Fluoro |
F |
F |
F |
F |
Failed 90 Min Test |
Y |
N |
|
34 |
R |
Y |
Y |
Y |
P |
|
|
|
|
35 |
R |
Y |
Y |
Y |
P |
|
|
|
|
36 |
S |
Y |
Y |
N |
F |
Relocated & Replaced |
Y |
N |
|
37 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
Newly installed |
Y |
N |
|
38 |
Em 4 Foot Fluoro |
Y |
Y |
Y |
P |
Newly installed |
Y |
N |
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| DB-4 |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
Y |
P |
|
|
|
|
9 |
Y |
Y |
Y |
P |
|
|
|
| Large exit |
13 |
Y |
Y |
Y |
P |
|
|
|
|
23 |
Y |
Y |
Y |
P |
|
|
|
|
25 |
Y |
Y |
Y |
P |
|
|
|
|
29 |
Y |
Y |
Y |
P |
|
|
|
|
31 |
Y |
Y |
Y |
P |
|
|
|
|
33 |
Y |
Y |
Y |
P |
|
|
|
|
40 |
Y |
Y |
Y |
P |
|
|
|
|
43 |
Y |
Y |
Y |
P |
|
|
|
|
46 |
Y |
Y |
Y |
P |
|
|
|
|
47 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| 2ft LED Fluoro 8W |
Y |
| LED Highbay 200W YML |
Y |
| LED Lowbay 150W YML |
Y |
| Single 4ft Fluoro |
Y |
| 10W LED Downlight Lumoled |
Y |
| Compact Fluoro ES SSS 7W Sunny |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| Geotag photo(s) | - Have you sent the Geotag photo(s) to maintenance@sturdie.com.au, referring to the Store Location in the email, e.g. Canberra City?
|
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Emergency Batten Light |
4, 6, 7, 8, 13, 16, 30, 31, 33 |
9 |
Failed 90 Min Test |
Y |
N |
N |
Replaced fittings |
| Recessed Emergency Light |
21 |
1 |
Failed 90 Min Test |
Y |
N |
N |
Replaced fitting |
| LED Batten |
Male toilets |
1 |
Water damaged |
N |
N |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Downlight |
TV area |
1 |
Faulty |
N |
N |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| RCBO |
Dyson vacuum display |
1 |
Tripping |
Y |
N |
N |
Replaced circuit breaker |
| Pole Fillers |
SB - Office |
6 |
Missing pole fillers |
Y |
N |
N |
Replaced |
| Track Light |
Bosch wall ovens |
1 |
Not working |
N |
N |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| LED Panel |
Office |
2 |
Half illuminated and yellow |
N |
N |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Downlight |
Westinghouse kitchen display |
2 |
Not illuminated |
Y |
N |
N |
Unplugged, repaired |
| Surface Emergency Light |
BOH - 36 |
1 |
Relocate EM36 to center of room for compliance |
Y |
N |
N |
Relocated and replaced fitting |
| Emergency Batten Light |
BOH - 37 |
1 |
Install new emergency batten in BOH for compliance |
Y |
N |
N |
Installed new fitting |
| Emergency Batten Light |
Front of Store - 38 |
1 |
Install new emergency batten in BOH for compliance |
Y |
N |
N |
Installed new fitting |
|
|---|
| Site Status Selector | Store now fully compliant |
|---|
| Next Test Due in 6 months | 06/10/2022 |
|---|
| |
|---|
| |