StateNSW
Date of Visit20/04/2022
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62343
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWartarmon

Location NameArtarmon
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
UG5 CH1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
9 Y P
10,12 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 Y P
21 Y P
23 Y P
25 Y P
27 Y P
29 Y P
31 Y P
33 Y P
35 Y P
UG5 CH2 1 Y P
3 Y P
4 Y P
6 Y P
8 Y P
10 Y P
12 Y P
14 Y P
16 Y P
18 Y P
20 Y P
22 Y P
24 Y P
26 Y P
28 Y P
30 Y P
DB1 CH1 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
34 Y P
35 Y P
36 Y P
37 Y P
38 Y P
39 Y P
40 Y P
41 Y P
42 Y P
43 Y P
44 Y P
45 Y P
46 Y P
47 Y P
49 Y P
51 Y P
53 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
63 Y P
64 Y P
65 Y P
66 Y P
67 Y P
68 Y P
69 Y P
70 Y P
71 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Not Required - Tested by LL - - - - - - - - -
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Not Required - Tested by LL - - - - - - - -
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
UFO led High Bay Y
Round led shop light Y
70mm tri LED Downlight Y
4ft widebody led batten Y
170mm cfl downlight Y
Led light box wall bay unknown
Tracked spot lights (kinsman)
92mm led downlights (kitchen displays)
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
Hi-Bay Computers, Media Players, Microwaves, Kitchen Displays 4 Not illuminated Davis UFO150EA5K3B09 Y Replaced under warranty
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Davis Widebody 4ft LED batten Cash Office 1 Not illuminated Y N N Replaced 4ft LED Batten. Further fault finding required, will investigate when service call 65465 is attended for intercom.
170mm Downlight Cash Office cupboard 1 Not illuminated Y N N Replaced with 2ft LED Batten. Further fault finding required, will investigate when service call 65465 is attended for intercom.
70mm LED downlight Tv section 2 Flickering Y N N Replaced fittings
Emergency Light Plan Office 2 Innaccurate Y N N Audited, marked up new plan and placed into site folder
Recessed Emergency Light EM47 1 Not illuminated N N N FYI only - Landlord to repair
Surface Mount Emergency Light EM18 1 Not illuminated N N N FYI only - Landlord to repair
Intercom BOH 1 Head Unit faulty N N Y To be repaired on service job 65465.
Site Status SelectorStore now fully compliant
Next Test Due in 6 months20/10/2022