Partner NameSturdie Trade Services
StateVIC
Date of Visit26/04/2022
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62267
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICbrighton

Location NameBrighton
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
Db1a 19 Y P
Db1a 20 Y P
Db1a 21 Y P
Db1a 22 Y P
Db1a 23 Y P
Db1a 24 Y P
Db1a 25 Y P
Db1a 26 Y P
Db1a 27 Y P
Db1a 28 Y P
Db1a 29 Y P
Db1a 30 Y P
Db1a 31 Y P
Db1a 32 Y P
Db1a 33 Y P
Db1a 34 Y P
Db1a 35 Y P
Db1a 36 Y P
Db1a 37 Y P
Db1a 38 Y P
Db1a 39 Y P
Db1a 40 Y P
Db1a 41 Y P
Db1a 42 Y P
Db1a 43 Y P
Db1a 45 Y P
Db1a 47 Y P
Db1a 49 Y P
Db1a 51 Y P
Db1a 53 Y P
Db1b 01 Y P
Db1b 02 Y P
Db1b 03 Y P
Db1b 04 Y P
Db1b 05 Y P
Db1b 06 Y P
Db1b 07 Y P
Db1b 08 Y P
Db1b 09 Y P
Db1b 10 Y P
Db1b 12 Y P
Db1b 13 Y P
Db1b 14 Y P
Db1b 15 Y P
Db1b 16 Y P
Db1b 17 Y P
Db1b 18 Y P
Db1b 19 Y P
Db1b 20 Y P
Db1b 21 Y P
Db1b 22 Y P
Db1b 23 Y P
Db1b 24 Y P
Db1b 25 Y P
Db1b 26 Y P
Db1b 27 Y P
Db1b 28 Y P
Db1b 29 Y P
Db1b 30 Y P
Db1b 31 Y P
Db1b 32 Y P
Db1b 33 Y P
Db1b 34 Y P
Db1b 35 Y P
Db1b 36 Y P
Db1b 37 Y P
Db1b 38 Y P
Db1b 39 Y P
Db1b 40 Y P
Db1b 41 Y P
Db1b 42 Y P
Db1b 43 Y P
Db1b 44 Y P
Db1b 45 Y P
Db1b 46 Y P
Db1b 47 Y P
Db1b 48 Y P
Db1b 49 Y P
Db1b 51 Y P
Db1b 53 Y P
Db1b 55 Y P
Db1b 57 Y P
DB2 02 Y P
DB2 04 Y P
DB2 06 Y P
DB2 07 Y P
DB2 08 Y P
DB2 09 Y P
DB2 10 Y P
DB2 11 Y P
DB2 12 Y P
DB2 13 Y P
DB2 14 Y P
DB2 15 Y P
DB2 16 Y P
DB2 17 Y P
DB2 18 Y P
DB2 19 Y P
DB2 20 Y P
DB2 21 Y P
DB2 22 Y P
DB2 23 Y P
DB2 24 Y P
DB2 25 Y P
DB2 26 Y P
DB2 27 Y P
DB2 28 Y P
DB2 29 Y P
DB2 30 Y P
DB2 31 Y P
DB2 32 Y P
DB2 33 Y P
DB2 34 Y P
DB2 35 Y P
DB2 36 Y P
DB2 37 Y P
DB2 38 Y P
DB2 39 Y P
DB2 40 Y P
DB2 41 Y P
DB2 42 Y P
DB2 43 Y P
DB2 44 Y P
DB2 45 Y P
DB2 46 Y P
DB2 48 Y P
DB2 50 Y P
DB3 01 Y P
DB3 02 Y P
DB3 03 Y P
DB3 04 Y P
DB3 05 Y P
DB3 06 Y P
DB3 07 Y P
DB3 08 Y P
DB3 09 Y P
DB3 10 Y P
DB3 11 Y P
DB3 12 Y P
DB3 13 Y P
DB3 14 Y P
DB3 15 Y P
DB3 16 Y P
DB3 17 Y P
DB3 18 Y P
DB3 19 Y P
DB3 20 Y P
DB3 21 Y P
DB3 22 Y P
DB3 23 Y P
DB3 24 Y P
DB3 25 Y P
DB3 26 Y P
DB3 27 Y P
DB3 28 Y P
DB3 29 Y P
DB3 30 Y P
DB3 31 Y P
DB3 32 Y P
DB3 33 Y P
DB3 34 Y P
DB3 35 Y P
DB3 36 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 1 R Y Y Y P
Db1 2 R Y Y Y P
Db1 3 R Y Y Y P
Db1 4 R Y Y Y P
Db1 5 R Y Y Y P
Db1 6 R Y Y Y P
Db1 7 R Y Y Y P
Db1 8 R Y Y Y P
Db1 9 R Y Y Y P
Db1 10 R Y Y Y P
Db1 11 R Y Y Y P
Db1 12 R Y Y Y P
Db1 13 R Y Y Y P
Db1 14 R Y Y Y P
Db1 15 R Y Y Y P
Db1 16 R Y Y Y P
Db1 17 R Y Y Y P
Db1 18 R Y Y Y P
Db1 19 R Y Y Y P
Db1 20 R Y Y Y P
Db1 21 R Y Y Y P
Db1 22 R Y Y Y P
Db1 23 R Y Y Y P
Db1 24 R Y Y Y P
Db1 25 R Y Y Y P
Db1 26 R Y Y Y P
Db1 27 R Y Y Y P
Db1 28 R Y Y Y P
Db1 29 R Y Y Y P
Db1 30 R Y Y Y P
Db1 31 R Y Y Y P
Db1 32 R Y Y Y P
Db1 33 R Y Y Y P
Db1 34 R Y Y Y P
Db1 35 R Y Y Y P
Db1 36 R Y Y Y P
Db1 37 R Y Y Y P
Db1 38 R Y Y Y P
Db1 39 R Y Y Y P
Db1 40 R Y Y Y P
Db1 41 R Y Y Y P
Db1 42 R Y Y Y P
Db1 43 R Y Y Y P
Db1 44 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
Db1 1 Y Y Y P
Db1 2 Y Y Y P
Db1 3 Y Y Y P
Db1 4 Y Y Y P
Db1 5 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auNo
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
Recessed Double T5 fluorescent light fitting Y
Single 36W fluorescent light fitting Y
Mercury vapour Hi-bay light fitting Y
70mm Downlights Y
MR16 track spot lights LED Y
Halogen recessed spot light Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
SURFACE MOUNT ROUND LIGHT FITTING FEMALE TOILET 1 FAULTY Y N N RETURNED TO SITE & REPLACED WITH NEW.
DAVIS LED BATTEN SMALL STORE ROOM 1 DAMAGED DIFFUSER Y N N REPLACED DIFFUSER
EMERGENCY LIGHTING LAYOUT SITE 1 UPDATED EMERGENCY LIGHTING LAYOUT REQUIRED N/A N/A N/A UPDATED EMERGENCY LAYOUT DURING NEXT AUDIT
FINGER PRINT TIME CLOCK DOWN STAIRES STAFF AREA 1 NO CONNECTING TO SOFTWARE, STAFF CURRENTLY CANNOT USE SCANNER HAVE TO USE SCANNER IN BUILDING 2 Y N N RETURNED TO SITE AND REPAIRED.
PDA'S NOT CONNECTING TO WIFI IN BACK AREA OF STORE NEAR KINSMAN STORE - PDA COMNECTED TO WIFI NOT WORKING AT REAR OF STORE NEAR KINSMAN DISPLAY, STAFF CURRENTLY USING PDA CONNECTED TO 4G N/A N/A N/A MANGER TO SUBMIT JOB REQUEST WITH IT
EXTERNAL LIGHTING STORE - MANAGER REPORTED LIGHTS NOT TURNING ON AT NIGHT TIME Y N N ADJUSTED TIME CLOCK TO MATCH OTHER TIMERS IN BUILDING, CURRENTLY SET TO On 5:45 off 8:35 on 17:30 off 22:15. MONITOR AND CONFIRM CORRECT OPERATION.
AUTO DOOR BUTTON COUNTER 1 ADDITIONAL AUTO DOOR BUTTON TO BE INSTALLED AT COUNTER TO OPEN AUTO DOORS, WAS PREVIOUSLY INSTALLED BEFORE RELAY N/A N/A N/A JOB REQUEST TO BE SUBMITTED BY MANAGER
SWITCHBOARD LEGENDS N/SA 1 NO DB LEGEND N/A N/A N/A UPDATED LEGEND TO BE INSTALLED DURING NEXT AUDIT
CB09 DB03 1 CB TRIPPING Y N N REPAIRED ON SITE.
EXTERNAL PAR 38 FLOOD LIGHT SERVICE RD, UNDER COVER 2 LED PAR 38 GLOBE FAILED TO ILLUMINATE Y N N RETURNED TO SITE AND REPLACED WITH NEW.
EXTERNAL LED FLOODLIGHT CARPARK CLOSEST TO ENTRANCE GATE MOUNTED ON WALL 1 FAILED TO ILLUMINATE N/A N/A N/A SCISSOR LIFT REQUIRED, 5.6m, EXTEND OVER PATH 1.8M. ADDED TO FORTNIGHTLY REPAIRS LIST
Site Status SelectorStore now fully compliant
Next Test Due in 6 months26/10/2022