Partner NameSturdie Trade Services
StateVIC
Date of Visit27/04/2022
Technician's NameNathan McBain
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62270
EmailEmail hidden; Javascript is required.
The Good Guys Site in VICmelton

Location NameMelton
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB-1 1 Y P
DB-1 3 Y P
DB-1 5 Y P
DB-1 7 Y P
DB-1 9 Y P
DB-1 10 Y P
DB-1 11 Y P
DB-1 12 Y P
DB-1 13 Y P
DB-1 14 Y P
DB-1 15 Y P
DB-1 16 Y P
DB-1 17 Y P
DB-1 18 Y P
DB-1 19 Y P
DB-1 20 Y P
DB-1 21 Y P
DB-1 22 Y P
DB-1 23 Y P
DB-1 24 Y P
DB-1 25 Y P
DB-1 26 Y P
DB-1 27 Y P
DB-1 28 Y P
DB-1 29 Y P
DB-1 30 Y P
DB-1 32 Y P
DB-1 34 Y P
DB-2 1 Y P
DB-2 2 Y P
DB-2 3 Y P
DB-2 4 Y P
DB-2 5 Y P
DB-2 6 Y P
DB-2 7 Y P
DB-2 8 Y P
DB-2 9 Y P
DB-2 10 Y P
DB-2 11 Y P
DB-2 12 Y P
DB-2 13 Y P
DB-2 14 Y P
DB-2 15 Y P
DB-2 16 Y P
DB-2 17 Y P
DB-2 18 Y P
DB-2 19 Y P
DB-2 20 Y P
DB-2 21 Y P
DB-2 22 Y P
DB-2 23 Y P
DB-2 24 Y P
DB-2 25 Y P
DB-2 27 Y P
DB-2 29 Y P
DB-2 31 Y P
DB-2 32 Y P
DB-2 33 Y P
DB-3 1 Y P
DB-3 2 Y P
DB-3 3 Y P
DB-3 4 Y P
DB-3 5 Y P
DB-3 6 Y P
DB-3 7 Y P
DB-3 8 Y P
DB-3 9 Y P
DB-3 10 Y P
DB-3 11 Y P
DB-3 12 Y P
DB-3 13 Y P
DB-3 14 Y P
DB-3 15 Y P
DB-3 16 Y P
DB-3 17 Y P
DB-3 18 Y P
DB-3 19 Y P
DB-3 20 Y P
DB-3 21 Y P
DB-3 22 Y P
DB-3 23 Y P
DB-3 24 Y P
DB-3 25 Y P
DB-3 26 Y P
DB-3 27 Y P
DB-3 28 Y P
DB-3 29 Y P
DB-3 30 Y P
DB-3 31 Y P
DB-3 32 Y P
DB-3 33 Y P
DB-3 34 Y P
DB-3 35 Y P
DB-3 36 Y P
DB-3 37 Y P
DB-3 38 Y P
DB-3 39 Y P
DB-3 40 Y P
DB-3 41 Y P
DB-3 42 Y P
DB-3 43 Y P
DB-3 44 Y P
DB-3 46 Y P
DB-3 54 Y P
DB-3 56 Y P
DB-3 58 Y P
DB-3 64 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1 2 S Y Y Y P
DB-1 3 S Y Y Y P
DB-1 4 S Y Y Y P
DB-1 6 S Y Y Y P
DB-1 8 S Y Y Y P
DB-1 9 R Y Y Y P
DB-1 10 R Y N Y F FAILED BATTERY TEST Y N
DB-1 11 S Y Y Y P
DB-1 12 S Y N Y F FAILED BATTERY TEST Y N
DB-1 13 S Y Y Y P
DB-1 15 R Y Y Y P
DB-1 16 R Y Y Y P
DB-1 18 S Y Y Y P
DB-1 20 R Y Y Y P
DB-1 21 R Y Y Y P
DB-1 22 R Y Y Y P
DB-1 23 R Y Y Y P
DB-1 25 S Y N Y F FAILED BATTERY TEST Y N
DB-1 26 S Y Y Y P
DB-1 27 S Y Y Y P
DB-1 29 S Y Y Y P
DB-1 30 S Y Y Y P
DB-1 31 S Y Y Y P
DB-1 33 S Y N Y F FAILED BATTERY TEST Y N
DB-1 35 S Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB-1 1 Y Y Y P
DB-1 5 Y Y Y P
DB-1 7 Y Y Y P
Db-1 14 Y Y Y P
DB-1 17 Y Y Y P
DB-1 19 Y N Y F FAILED BATTERY TEST Y N
DB-1 24 Y Y Y P
DB-1 28 Y Y Y P
DB-1 32 Y Y Y P
DB-1 34 Y N Y F FAILED BATTERY TEST Y N
DB-1 36 Y Y Y P
DB-1 37 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
HIGHBAY LIGHTS Y
SQUARE HIGHBAY LIGHTS Y
HALOGEN 50W LIGHTS Y
36W DIFFUSED SINGLE LIGHTS Y
Are there any Warranty items needing to be repaired?Yes
WARRANTY
Defect Item Location of Item (on premises) Quantity Details of fault/problem Manufacturer Part Number Repaired on Site Comments
BLACK HIGHBAY SAMSUNG / BOSCH WASHING MACHINES 1 FAILED TO ILLUMINATE DAVIS Y SCISSOR LIFT WAS REQUIRED
BLACK HIGHBAY NOVELTY 1 FAILED TO ILLUMINATE DAVIS Y SCISSOR LIFT WAS REQUIRED
BLACK HIGHBAY WEBER 1 FAILED TO ILLUMINATE DAVIS Y SCISSOR LIFT WAS REQUIRED
BLACK HIGHBAY FOOD PROC / PRINTERS 1 FAILED TO ILLUMINATE DAVIS Y SCISSOR LIFT WAS REQUIRED
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
TEST AND TAG STORE 80+ TEST AND TAG IN-DATE, NEXT TEST DUE 18 FEB 2023 N N N FOR YOUR INFORMATION
SURFACE MOUNT EMERGENCY #12 VACUUMS 1 FAILED BATTERY TEST Y N N
RECESSED EMERGENCY #10 VAULT NEAR OFFICE 1 FAILED BATTERY TEST Y N N
SURFACE MOUNT EMERGENCY #25 BOH 1 FAILED BATTERY TEST Y N N
SURFACE MOUNT EMERGENCY #33 BOH 1 FAILED BATTERY TEST Y N N
JUMBO EXIT #34 BOH 1 FAILED BATTERY TEST Y N N
JUMBO EXIT #19 BOH NEAR ROLLER DOOR 1 FAILED BATTERY TEST Y N N
TV CIRCUITS DB3 11 CIRCUITS CB CURRENTLY SWITCHED OFF AT DB3 - WOULD NEED TO INSTALL CONTACTORS AND SWITCH TO CONTROL TV SWITCHING N Y TBA 11 CIRCUITS TO BE SWITCHED (CB6,CB8,CB10,CB12,CB14,CB16,CB24,CB34,CB36,CB40,CB64). - SPACE INSIDE DB NEXT TO MAIN SWITCH TO MOUNT CONTACTORS. SPACE NEXT TO DB TO INSTALL MOUNTING BLOCK AND SWITCH FOR SWITCHING. QUOTE RECOMMENDATION LISTED ON FORTNIGHTLY REPORT
Site Status SelectorStore now fully compliant
Next Test Due in 6 months27/10/2022