| State | NSW |
|---|
| Date of Visit | 10/05/2022 |
|---|
| Technician's Name | Peter Hay |
|---|
| Which Company are you working for? | Sturdie Trade Services |
|---|
| Sturdie Job Number | 62345 |
|---|
| Email | Email hidden; Javascript is required. |
|---|
| The Good Guys Site in NSW | warrawong |
|---|
|
|
|---|
| Location Name | Warrawong |
|---|
| |
|---|
| HTML Block |
|
|---|
| Test Period | 6 Monthly (90 minutes) |
|---|
| Push Button Test | - Carry out push button test for correct operation
|
|---|
| Carry out push button test for correct operation | |
|---|
| HTML Block |
|
|---|
| Carry out test with RCD Tester | Carry out push button test and record the results below. |
|---|
| THERMOGRAPHIC TEST RESULTS |
THERMOGRAPHIC TEST RESULTS
|
|---|
| RCD Details (6 Month) | | Distribution Board No. |
Circuit No. |
Push Button (YorN) |
Pass / Fail (PorF) |
Fault? |
Repaired on Site (YorN) |
| MSB GEN L&P |
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
46 |
Y |
P |
|
|
|
47 |
Y |
P |
|
|
|
55 |
Y |
P |
|
|
|
56 |
Y |
P |
|
|
|
57 |
Y |
P |
|
|
|
58 |
Y |
P |
|
|
|
59 |
Y |
P |
|
|
|
60 |
Y |
P |
|
|
|
61 |
Y |
P |
|
|
|
62 |
Y |
P |
|
|
|
63 |
Y |
P |
|
|
|
64 |
Y |
P |
|
|
|
65 |
Y |
P |
|
|
|
66 |
Y |
P |
|
|
|
67 |
Y |
P |
|
|
|
71 |
Y |
P |
|
|
|
72 |
Y |
P |
|
|
| DB1 |
1 |
Y |
P |
|
|
|
2 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
| DB1 |
28/30/32 |
Y |
P |
|
|
| DB2 |
1 |
Y |
P |
|
|
|
2 |
Y |
P |
|
|
|
3 |
Y |
P |
|
|
|
4 |
Y |
P |
|
|
|
5 |
Y |
P |
|
|
|
6 |
Y |
P |
|
|
|
7 |
Y |
P |
|
|
|
8 |
Y |
P |
|
|
|
9 |
Y |
P |
|
|
|
10 |
Y |
P |
|
|
|
11 |
Y |
P |
|
|
|
12 |
Y |
P |
|
|
|
13 |
Y |
P |
|
|
|
14 |
Y |
P |
|
|
|
15 |
Y |
P |
|
|
|
16 |
Y |
P |
|
|
|
17 |
Y |
P |
|
|
|
18 |
Y |
P |
|
|
|
19 |
Y |
P |
|
|
|
20 |
Y |
P |
|
|
|
21 |
Y |
P |
|
|
|
22 |
Y |
P |
|
|
|
23 |
Y |
P |
|
|
|
24 |
Y |
P |
|
|
|
25 |
Y |
P |
|
|
|
26 |
Y |
P |
|
|
|
27 |
Y |
P |
|
|
|
28 |
Y |
P |
|
|
|
29 |
Y |
P |
|
|
|
30 |
Y |
P |
|
|
|
31 |
Y |
P |
|
|
|
32 |
Y |
P |
|
|
|
33 |
Y |
P |
|
|
|
35 |
Y |
P |
|
|
|
|---|
| SF43 Exit/Emergency |
SF43 EXIT/EMERGENCY LIGHTING
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
|
|---|
| Exit/Emergency Light Checklist | - Check there has been no power interruption for at least 16 hours prior to test
- Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
- Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
- Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
- Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
|
|---|
| Timers | - Check timers for correct operation and timing
|
|---|
| Switched Socket Outlets | - Carry out visual check on SSOs for signs of misuse, blackening or deterioration
- Check and report any outlets with multiple power boards overloading
- Ensure any power boards used have an integral over-current limiter
|
|---|
| HTML Block |
|
|---|
| EMERGENCY LIGHTS | | Distribution Board No. |
ID No. |
Surface mounted or recessed? (SorR) |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| MSB |
1 |
S |
Y |
Y |
Y |
P |
|
|
|
|
2 |
S |
Y |
Y |
Y |
P |
|
|
|
|
3 |
S |
Y |
Y |
Y |
P |
|
|
|
|
4 |
S |
Y |
Y |
Y |
P |
|
|
|
|
5 |
S |
Y |
Y |
Y |
P |
|
|
|
|
6 |
S |
Y |
Y |
Y |
P |
|
|
|
|
7 |
S |
Y |
Y |
Y |
P |
|
|
|
|
8 |
S |
Y |
Y |
Y |
P |
|
|
|
|
9 |
S |
Y |
Y |
Y |
P |
|
|
|
|
10 |
S |
Y |
Y |
Y |
P |
|
|
|
|
11 |
S |
Y |
Y |
Y |
P |
|
|
|
|
12 |
S |
Y |
Y |
Y |
P |
|
|
|
|
13 |
S |
Y |
Y |
Y |
P |
|
|
|
|
14 |
S |
Y |
Y |
Y |
P |
|
|
|
|
15 |
S |
Y |
Y |
Y |
P |
|
|
|
|
16 |
S |
Y |
Y |
Y |
P |
|
|
|
|
17 |
S |
Y |
Y |
Y |
P |
|
|
|
|
18 |
S |
Y |
Y |
Y |
P |
|
|
|
|
19 |
S |
Y |
Y |
Y |
P |
|
|
|
|
20 |
S |
Y |
Y |
Y |
P |
|
|
|
|
21 |
R |
Y |
Y |
Y |
P |
|
|
|
|
22 |
R |
Y |
Y |
Y |
P |
|
|
|
|
23 |
R |
Y |
Y |
Y |
P |
|
|
|
|
24 |
R |
Y |
Y |
Y |
P |
|
|
|
|
25 |
R |
Y |
Y |
Y |
P |
|
|
|
|
26 |
R |
Y |
Y |
Y |
P |
|
|
|
|
30 |
R |
Y |
Y |
Y |
P |
|
|
|
|
33 |
R |
Y |
Y |
Y |
P |
|
|
|
|
35 |
R |
Y |
Y |
Y |
P |
|
|
|
|
38 |
R |
Y |
Y |
Y |
P |
|
|
|
|
39 |
R |
Y |
Y |
Y |
P |
|
|
|
|
40 |
R |
Y |
Y |
Y |
P |
|
|
|
|
41 |
R |
Y |
Y |
Y |
P |
|
|
|
|
44 |
R |
Y |
Y |
Y |
P |
|
|
|
|
45 |
R |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| HTML Block |
|
|---|
| EXIT LIGHTS | | Distribution Board No. |
ID No. |
Lamp OK? (YorN) |
Battery OK? (YorN) |
Condition OK? (YorN) |
Pass / Fail (PorF) |
Fault |
Repaired on Site (YorN) |
Under Warranty (YorN) |
| MSB |
1 |
Y |
Y |
Y |
P |
|
|
|
|
2 |
Y |
Y |
Y |
P |
|
|
|
|
3 |
Y |
Y |
Y |
P |
|
|
|
|
4 |
Y |
Y |
Y |
P |
|
|
|
|
5 |
Y |
Y |
Y |
P |
|
|
|
|
6 |
Y |
Y |
Y |
P |
|
|
|
|
7 |
Y |
Y |
Y |
P |
|
|
|
|
8 |
Y |
Y |
N |
F |
Decal Missing |
Y |
N |
|
9 |
Y |
Y |
Y |
P |
|
|
|
|
10 |
Y |
Y |
Y |
P |
|
|
|
|
11 |
Y |
Y |
Y |
P |
|
|
|
|
12 |
Y |
Y |
Y |
P |
|
|
|
|
|---|
| SF44 General Lighting & Works |
SF44 GENERAL LIGHTING & WORKS
|
|---|
| General Checklist | - Check correct operation of all luminaries
- Report on any faulty luminaries/control gear
- Provide costing to repair/replace
|
|---|
| HTML Block |
|
|---|
| General Operation/Additional items | - Check with Store Manager to ensure there are no other issues
- Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
|
|---|
| HTML Block |
|
|---|
| Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.au | Yes |
|---|
| Lighting Report | | Description of all lighting installed in store (eg. 21w bare batten) |
Existing (YorN) |
| UFO LED high bays |
Y |
| 4ft widebody led battens |
Y |
| 210mm cfl downlights |
Y |
| Fluro wall bay light boxes |
Y |
| 70mm elv downlights tv section |
Y |
| 92mm led downlights |
Y |
| Led linkables kitchen display light boxes |
Y |
|
|---|
| Are there any Warranty items needing to be repaired? | No |
|---|
| LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's | | Defect Item |
Location of Item (on premises) |
Quantity |
Details of fault /problem |
Repaired on Site? (YorN) |
Quote to be sent? (YorN) |
To return to Site |
Comments |
| Emergency light test switch |
Msb |
1 |
Contactor faulty |
Y |
N |
N |
Replaced contactor |
| Downlights |
Tv section |
1 x section |
Driver de-energised |
Y |
N |
N |
Traced cabling to driver and found disconnected. Reconnected and working. |
| 210mm cfl downlight |
Upstairs male and female toilet |
7 |
Partially/not illuminated |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Samsung tv wallbay logo |
Tv section |
1 |
Partially illuminated |
N |
N |
N |
Vendor to rectify |
| Blue Led strip light |
Tv section wall bays |
2 |
Partially/not illuminated |
N |
N |
N |
Address on future relay |
| Fluro Wall bay light boxes |
Trading floor |
Majority |
Partially/not illuminated |
N |
N |
N |
Adress on future relay |
| 92mm downlights |
Accessories wall bay |
2 |
Dim |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Emergency and exit lighting |
Store |
1 |
Not compliant. Design not implemented. |
N |
N |
N |
Store not compliant, previously quoted and put on hold. |
| 25mm elv downlights |
Asko kitchen display |
2 |
Not illuminated |
N |
N |
N |
Vendor to rectify |
| Light box |
Electrolux Kitchen display |
1 |
Light box not energised |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Pendant lights |
Westinghouse kitchen display |
2 of 3 |
Not illuminated |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Awning lights |
Store entrance |
5 |
Not illuminated |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Light box |
Electrolux fridge display |
1 |
Not illuminated |
N |
N |
N |
Power confirmed to light box. Vendor to recifty |
| Led strip light |
Samsung fridge display |
1 |
Flickering |
N |
N |
N |
Vendor to rectify |
| Led strip light |
Hi-Sense fridge display |
1 |
Partially illuminated |
N |
N |
N |
Vendor to rectify |
| Pendant light |
Technika |
1 |
Not illuminated |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Pendant light |
Bosch kitchen display |
2 |
Not illuminated / missing lamps |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
| Light box |
Haier washing machine display |
1 |
1 of 3 haier logos not illuminated |
N |
N |
N |
Vendor to rectify |
| Tv rack |
LG TV display |
1 |
Multiple lights not illuminated |
N |
N |
N |
Vendor to rectify |
| Lack of rcbos |
Main switchboard |
Multiple |
Quote required to replace mcb's with rcbo's |
N |
TBA |
TBA |
Added to fortnightly repairs report, please advise if quote is required. |
|
|---|
| Site Status Selector | Completed but with repairs required |
|---|
| Next Test Due in 6 months | 10/11/2022 |
|---|
| |
|---|
| |