StateNSW
Date of Visit10/05/2022
Technician's NamePeter Hay
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62345
EmailEmail hidden; Javascript is required.
The Good Guys Site in NSWwarrawong

Location NameWarrawong
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
MSB GEN L&P 19 Y P
20 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
46 Y P
47 Y P
55 Y P
56 Y P
57 Y P
58 Y P
59 Y P
60 Y P
61 Y P
62 Y P
63 Y P
64 Y P
65 Y P
66 Y P
67 Y P
71 Y P
72 Y P
DB1 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
26 Y P
31 Y P
DB1 28/30/32 Y P
DB2 1 Y P
2 Y P
3 Y P
4 Y P
5 Y P
6 Y P
7 Y P
8 Y P
9 Y P
10 Y P
11 Y P
12 Y P
13 Y P
14 Y P
15 Y P
16 Y P
17 Y P
18 Y P
19 Y P
20 Y P
21 Y P
22 Y P
23 Y P
24 Y P
25 Y P
26 Y P
27 Y P
28 Y P
29 Y P
30 Y P
31 Y P
32 Y P
33 Y P
35 Y P
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install sticker with date & fitting number
  • Using a clean cloth, clean reflective surfaces of all exit and emergency luminaires.
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 S Y Y Y P
2 S Y Y Y P
3 S Y Y Y P
4 S Y Y Y P
5 S Y Y Y P
6 S Y Y Y P
7 S Y Y Y P
8 S Y Y Y P
9 S Y Y Y P
10 S Y Y Y P
11 S Y Y Y P
12 S Y Y Y P
13 S Y Y Y P
14 S Y Y Y P
15 S Y Y Y P
16 S Y Y Y P
17 S Y Y Y P
18 S Y Y Y P
19 S Y Y Y P
20 S Y Y Y P
21 R Y Y Y P
22 R Y Y Y P
23 R Y Y Y P
24 R Y Y Y P
25 R Y Y Y P
26 R Y Y Y P
30 R Y Y Y P
33 R Y Y Y P
35 R Y Y Y P
38 R Y Y Y P
39 R Y Y Y P
40 R Y Y Y P
41 R Y Y Y P
44 R Y Y Y P
45 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
MSB 1 Y Y Y P
2 Y Y Y P
3 Y Y Y P
4 Y Y Y P
5 Y Y Y P
6 Y Y Y P
7 Y Y Y P
8 Y Y N F Decal Missing Y N
9 Y Y Y P
10 Y Y Y P
11 Y Y Y P
12 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
UFO LED high bays Y
4ft widebody led battens Y
210mm cfl downlights Y
Fluro wall bay light boxes Y
70mm elv downlights tv section Y
92mm led downlights Y
Led linkables kitchen display light boxes Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
Emergency light test switch Msb 1 Contactor faulty Y N N Replaced contactor
Downlights Tv section 1 x section Driver de-energised Y N N Traced cabling to driver and found disconnected. Reconnected and working.
210mm cfl downlight Upstairs male and female toilet 7 Partially/not illuminated N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Samsung tv wallbay logo Tv section 1 Partially illuminated N N N Vendor to rectify
Blue Led strip light Tv section wall bays 2 Partially/not illuminated N N N Address on future relay
Fluro Wall bay light boxes Trading floor Majority Partially/not illuminated N N N Adress on future relay
92mm downlights Accessories wall bay 2 Dim N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Emergency and exit lighting Store 1 Not compliant. Design not implemented. N N N Store not compliant, previously quoted and put on hold.
25mm elv downlights Asko kitchen display 2 Not illuminated N N N Vendor to rectify
Light box Electrolux Kitchen display 1 Light box not energised N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Pendant lights Westinghouse kitchen display 2 of 3 Not illuminated N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Awning lights Store entrance 5 Not illuminated N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Light box Electrolux fridge display 1 Not illuminated N N N Power confirmed to light box. Vendor to recifty
Led strip light Samsung fridge display 1 Flickering N N N Vendor to rectify
Led strip light Hi-Sense fridge display 1 Partially illuminated N N N Vendor to rectify
Pendant light Technika 1 Not illuminated N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Pendant light Bosch kitchen display 2 Not illuminated / missing lamps N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Light box Haier washing machine display 1 1 of 3 haier logos not illuminated N N N Vendor to rectify
Tv rack LG TV display 1 Multiple lights not illuminated N N N Vendor to rectify
Lack of rcbos Main switchboard Multiple Quote required to replace mcb's with rcbo's N TBA TBA Added to fortnightly repairs report, please advise if quote is required.
Site Status SelectorCompleted but with repairs required
Next Test Due in 6 months10/11/2022