Partner NameBuilt Services
StateWA
Date of Visit08/06/2022
Technician's NameNeil Allen
Which Company are you working for?Sturdie Trade Services
Sturdie Job Number62617
EmailEmail hidden; Javascript is required.
The Good Guys Site in WAbusselton

Location NameBusselton
HTML Block
Test Period6 Monthly (90 minutes)
Push Button Test
  • Carry out push button test for correct operation
Carry out push button test for correct operation
HTML Block
Carry out test with RCD Tester

Carry out push button test and record the results below.

THERMOGRAPHIC TEST RESULTS

THERMOGRAPHIC TEST RESULTS

RCD Details (6 Month)
Distribution Board No. Circuit No. Push Button (YorN) Pass / Fail (PorF) Fault? Repaired on Site (YorN)
DB - B 1 N P Not RCD
3 N P Not RCD
5 N P Not RCD
7 N P Not RCD
9 N P Not RCD
11 N P Not RCD
13 N P Not RCD
15 N P Not RCD
17 N P Not RCD
19 N P Not RCD
21 N P Not RCD
23 N P Not RCD
25 N P Not RCD
27 N P Not RCD
29 Y P
31 Y P
33 Y P
35 Y P
37 Y F Failed Push Button Test Y
39 Y P
41 Y P
43 N P Not RCD
2 N P Not RCD
4 N P Not RCD
6 Y P
8 Y P
10 Y P
12 Y P
14 N P Not RCD
16 N P Not RCD
18 N P Not RCD
20 N P Not RCD
22 N P Not RCD
24 N P Not RCD
26 N P Not RCD
28 N P Not RCD
30 N P Not RCD
32 Y P
34 Y P
36 Y P
38 N P Not RCD
40 N P Not RCD
DB - A 1 Y P
3 Y P
5 Y P
7 Y P
9 Y P
11 Y P
13 Y P
15 Y P
17 Y P
19 Y P
21 Y P
23 N P Not RCD
25 N P Not RCD
27 N P Not RCD
29 N P Not RCD
31 N P Not RCD
33 N P Not RCD
35 Y P
2 N P Blank
4 N P Blank
6 N P Blank
8 Y P
10 Y P
12 Y P
14 N P Not RCD
16 Y P
18 Y P
20 Y P
22 Y P
24 N P Not RCD
26 N P Not RCD
28 N P Not RCD
30 N P Not RCD
32 N P Not RCD
34 N P Not RCD
36 N P Not RCD
SF43 Exit/Emergency

SF43 EXIT/EMERGENCY LIGHTING

Exit/Emergency Light Checklist
  • Check there has been no power interruption for at least 16 hours prior to test
  • Carry out discharge test to ensure the luminaries remain illuminated for the required in service duration (90 minutes)
  • Re-instate power to luminaries and check that the battery charge operation indicator functions correctly
  • Report any failures and replace faulty fittings with stock provided by Sturdie Trade Services – install label with date & fitting number
Timers
  • Check timers for correct operation and timing
Switched Socket Outlets
  • Carry out visual check on SSOs for signs of misuse, blackening or deterioration
  • Check and report any outlets with multiple power boards overloading
  • Ensure any power boards used have an integral over-current limiter
HTML Block
EMERGENCY LIGHTS
Distribution Board No. ID No. Surface mounted or recessed? (SorR) Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB - B 2 R Y Y Y P
3 R Y Y Y P
4 R Y Y Y P
5 R Y Y Y P
6 R Y Y Y P
7 R Y Y Y P
8 R Y Y Y P
9 R Y Y Y P
10 R Y Y Y P
12 R Y Y Y P
14 R Y Y Y P
15 R Y Y Y P
17 R Y Y Y P
18 R Y Y Y P
20 R Y Y Y P
HTML Block
EXIT LIGHTS
Distribution Board No. ID No. Lamp OK? (YorN) Battery OK? (YorN) Condition OK? (YorN) Pass / Fail (PorF) Fault Repaired on Site (YorN) Under Warranty (YorN)
DB - B 1 Y Y Y P
11 Y Y Y P
13 Y Y Y P
16 Y Y Y P
19 Y Y Y P
SF44 General Lighting & Works

SF44 GENERAL LIGHTING & WORKS

General Checklist
  • Check correct operation of all luminaries
  • Report on any faulty luminaries/control gear
  • Provide costing to repair/replace
HTML Block
General Operation/Additional items
  • Check with Store Manager to ensure there are no other issues
  • Ensure any other electrical work is completed as per Sturdie Trade Services ie, affix label to switchboard
HTML Block
Are there accurate switchboard legends within each switchboard? Please take a photo of legend/s & send with report to maintenance@sturdie.com.auYes
Lighting Report
Description of all lighting installed in store (eg. 21w bare batten) Existing (YorN)
30w LED Panel Y
150w LED Highbay Y
35w LED Batten Y
15w LED Oyster Lights Y
400w HID Flood Lights Y
Are there any Warranty items needing to be repaired?No
LIST OF REPAIRS & ADDITIONAL WORKS REQUIRED - (ALL FIELDS MANDATORY) - Please supply photo's
Defect Item Location of Item (on premises) Quantity Details of fault /problem Repaired on Site? (YorN) Quote to be sent? (YorN) To return to Site Comments
RCD #37 (DB - B) Switchboard 1 Failed push button test Y N N
Power boards TV Area Multiple Multiple power boards are daisy chained N N TBA Quote recommendation listed on fortnightly report
Droppers Throughout sotore Multiple Droppers are not up to standards N N TBA Quote recommendation listed on fortnightly report
Site Status SelectorStore now fully compliant
Next Test Due in 6 months08/12/2022